Study guide
17.2 Overfeed Ratios and Recirculation Rate
RETA CIRO Certified Industrial Refrigeration Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 Test-Day Tools, On-Screen References, and Calculators 1.3 CIRO vs CARO and the RETA Credential Path
2 IIAR and ASHRAE Standards
2.1 IIAR 2 and ASHRAE 15 Machinery-Room Design 2.2 IIAR 6 Inspection, Testing, and Maintenance 2.3 IIAR 7 Operating Procedures and IIAR 9 Existing Systems
3 OSHA Process Safety Management
3.1 PSM Applicability and the 14 Elements 3.2 Process Safety Information 3.3 Process Hazard Analysis 3.4 Operating Procedures, Training, Contractors, and PSSR
4 Integrity, Change, and Emergency Programs
4.1 Mechanical Integrity and Pressure-Relief Valves 4.2 Hot Work and Management of Change 4.3 Incident Investigation and Compliance Audits 4.4 Emergency Planning, EPA RMP, and the General Duty Clause
5 Ammonia Hazards and Machinery-Room Safety
5.1 Ammonia Properties, SDS, and Exposure Limits 5.2 Detection, Ventilation, and Emergency Shutdown 5.3 Eyewash, PPE, Materials Compatibility, and ASME B31.5 Piping
6 Three-Phase Motors and Starting
6.1 Three-Phase Motors, Nameplates, and FLA 6.2 Wye-Delta and Reduced-Voltage Starting 6.3 Voltage Unbalance 6.4 Single-Phasing, Rotation Checks, and Screw Compressors
7 Ladder Diagrams, VFDs, and Power
7.1 Ladder Diagrams, Seal-In Circuits, and Safety Interlocks 7.2 Variable-Frequency Drives in Refrigeration Plants 7.3 Power Factor, kW/HP, Overloads, and Machinery-Room Electrical Classification
8 Pressure-Enthalpy Diagrams and Properties
8.1 Reading the Ammonia P-h Diagram 8.2 Saturated Properties, psia vs psig, and Saturation Temperature 8.3 Superheat, Subcooling, and Flash Gas
9 Capacity, COP, and Efficiency
9.1 Enthalpy, Latent Heat, and Net Refrigerating Effect 9.2 COP, Tons of Refrigeration, and Heat Rejection Ratio 9.3 BHP/ton, Isentropic Efficiency, and Theoretical Discharge Temperature
10 Heat Transfer and Rejection
10.1 Q = UAΔT, LMTD, and Heat Exchangers 10.2 Condensers, Approach, and Wet-Bulb Limits 10.3 Specific Volume, Mass Flow, and Compression Ratio
11 System Screens and Performance KPIs
11.1 Using CIRO Operating Screens (normal vs abnormal) 11.2 kW/ton, BHP/ton, and KPI Dashboards 11.3 Power Cost, Demand Charges, and the Cost of Poor Operation
12 Approach, TD, and Oil-Cooling Diagnostics
12.1 Condenser Approach and Non-Condensables 12.2 Evaporator TD and Superheat Diagnostics 12.3 Thermosiphon Oil Coolers and Oil-Temperature Trends
13 Floating Head, Sequencing, and Slide Valves
13.1 Floating Head Pressure 13.2 Compressor Sequencing 13.3 Screw Slide-Valve Unloading and Feedback
14 Expansion Devices and DX Feed
14.1 Solenoid and TXV Pairs, Equalizers, and Hunting 14.2 Electronic Expansion Valves 14.3 Hand Expansion Valves and DX Coil Distribution
15 Pressure-Regulating and Pilot-Operated Valves
15.1 Back-Pressure Regulators 15.2 Crankcase Pressure Regulators and Gas-Pumped CPR Systems 15.3 Pilot-Operated Valves and High-to-Low Relief Regulators
16 Floats, Checks, Solenoid Failures, and Piping
16.1 High-Side Floats and High-Pressure Receivers 16.2 Check Valves, Discharge Checks, and Defrost Check Valves 16.3 Solenoid Failure Modes, Strainers, King Valves, and Ammonia Piping
17 Flooded and Liquid-Overfeed Basics
17.1 Flooded vs DX Advantages and Charge 17.2 Overfeed Ratios and Recirculation Rate 17.3 Surge Drums, Separators, and Wet Suction Returns
18 Pumps, Oil Management, and Level Control
18.1 Mechanical Liquid Pumps and NPSH 18.2 Oil Drain Pots, Rectifiers, and Thermosiphon Oil Management 18.3 Level Glasses, Float Switches, and High/Low Cutouts 18.4 Liquid-Line Sizing and High-/Low-Pressure Receivers
19 Two-Stage Compression and Intercoolers
19.1 Why Two-Stage: Compression Ratio and Discharge Temperature 19.2 Interstage Pressure Selection (Geometric Mean) 19.3 Open Flash Intercoolers 19.4 Closed Intercoolers and Two-Stage Troubleshooting
20 Cascade and Secondary Coolant Systems
20.1 NH3/CO2 Cascade Designs 20.2 Glycol and Brine Secondary Coolants (pH, freeze point, inhibitors) 20.3 Why Secondary Coolants and Glycol Testing/Maintenance
21 Evaporator Defrost
21.1 Hot-Gas Defrost Sequence 21.2 Defrost Drain Pressure-Relief Regulators and Soft Equalization 21.3 Time/Temperature Termination, Drain Pans, Water and Electric Defrost
17.2 Overfeed Ratios and Recirculation Rate
Key Takeaways Explain This Topic AI
Overfeed ratio (recirculation rate) = mass circulated ÷ mass evaporated; typical industrial ammonia is 3:1 to 4:1.
A 4:1 feed means four pounds are pumped for each pound that boils; about three pounds of liquid return in the wet suction.
Too little overfeed causes dry-out, collapsed inside HTC, and high evaporator TD.
Too much overfeed burns pump power, wets the suction beyond design, and can overload the separator.
Ratio is mass, not gpm and not tons; evaporated mass follows load, so a fixed-speed pump runs a higher ratio at light load and a lower ratio at peak load.
Last updated: September 2026
17.2 Overfeed Ratios and Recirculation Rate
Liquid overfeed (also called liquid recirculation ) is flooded-coil operation with a pump — mechanical or gas-powered — that delivers more liquid mass than the coil evaporates . The extra liquid keeps every circuit wetted. Two-phase fluid leaves in a wet suction and the separator (surge drum / LPR / recirculator) splits vapor to the compressors from liquid back to the pumps.
This is the industrial answer to ammonia's small evaporated mass per ton . You do not try to meter exactly the boiled pounds the way a TXV does. You overfeed so quality in the tube stays well below 1.0 and the wall stays wet.
The ratio, in one line
Recirculation rate and overfeed ratio are the same idea on CIRO:
Overfeed ratio = mass circulated ÷ mass evaporated
A 4:1 overfeed means four pounds of liquid are pumped to the evaporators for every one pound that boils. Three pounds return as liquid. One pound returns as vapor (plus the vapor that formed in the coil). Typical industrial ammonia overfeed is 3:1 to 4:1 . That band is common industrial practice. If a stem or a manufacturer nameplate gives a different ratio for a specific coil, use the stem.
Say the numbers so you do not reverse them. Circulated mass is the numerator . Evaporated mass is the denominator . A ratio of 4 is not four tons of refrigeration per pound. It is a mass ratio .
If the feed entering the coil is essentially saturated liquid at evaporator pressure, outlet quality (vapor mass fraction) is about 1 / ratio . At 4:1, roughly 25% of the leaving mass is vapor and 75% is still liquid. At 3:1, quality is about 0.33 . At 1:1 you have evaporated everything — DX thinking — and dry-out is one maldistributed circuit away. That quality picture is why wet suction must be sized and pitched as two-phase, not as DX dry vapor.
Worked mass-flow clip
1 ton of refrigeration = 200 Btu/min. Ammonia's latent heat is large; look up h_fg on the on-screen P-h or saturation chart at the evaporating temperature , not at room temperature.
Example class (freezer, saturation near −20°F ). Suppose the chart shows h_fg ≈ 580 Btu/lb (order of magnitude; use the chart on exam day):
- Load on one penthouse: 40 tons
- Evaporated mass ṁ_evap = (40 × 200) / 580 ≈ 13.8 lb/min
- At 4:1 overfeed, ṁ_circ = 4 × 13.8 ≈ 55 lb/min
- Liquid returned (not evaporated) ≈ 41 lb/min
At 3:1 , ṁ_circ ≈ 41 lb/min . The coil still sees far more liquid than a DX coil that would feed only the 13.8 lb/min evaporated.
If you accidentally use volume (gpm) without converting density, you will mis-size the pump and lie to yourself about ratio. Overfeed is mass . Convert pump gpm to lb/min before you claim a ratio. Liquid ammonia specific gravity is often around 0.6–0.7 in the usual low-side range — look it up on the chart for the actual temperature. A teaching conversion is lb/min ≈ gpm × 8.33 × SG. A pump clocking 20 gpm is not automatically 4:1 on a 40-ton coil until you finish that conversion and divide by evaporated mass.
Field checks that actually support a ratio claim: a liquid flow meter on the pump discharge (best), a pump curve plus differential head (honest if the curve is for that ammonia and those orifices), or a crude amp draw trend that only tells you the pump is or is not on its usual operating point. Amps without a curve do not equal 3:1.
Why 3:1 to 4:1, not 1:1
At 1:1 you are trying to feed exactly the evaporated mass — that is DX thinking. Any maldistribution, any oil film, any frost-blocked circuit, and that circuit dries out . Quality reaches 1.0 before the outlet. Inside HTC falls. That circuit's TD rises : the space or product cannot get the capacity; frost dies out before the suction header; other circuits may still be wet. The room sees lost capacity and a high evaporator TD .
Extra liquid is a wetting insurance policy . It also helps oil move along the bottom of circuits toward the wet return instead of baking onto the tube wall. Ammonia overfeed coils are circuit-balanced with hand expansion / balancing valves on the liquid drops, not with TXVs. Those valves are opened to get design flow (and sometimes a minimum flow for oil), not to hold superheat. Closing them to save ammonia is how you create dry-out.
Too low
Symptoms of insufficient overfeed (ratio sagging toward 1–2, a failing pump, a throttled hand valve, a plugged strainer, a circuit valve cranked shut, or a gas pump that is not transferring):
- Dry-out at the top or outlet of some circuits
- High evaporator TD for the load
- Uneven frost: heavy at the inlet, bald toward the suction header
- Capacity missing while suction pressure is not correspondingly low (the coil is not using the surface)
- Warm leaving air or product with a coil that should be big enough
Do not first blame the compressor slide valve. Ask whether liquid is actually recirculating at the design multiple. A strainer in the pump suction or in a liquid drop will fake a low ratio with a pump that still sounds busy.
Too high
Overfeed is not more-is-always-better. Excessive recirculation (pump wide open, second pump started for no reason, ratio drifting toward 6:1 or 8:1 on a coil designed for 4:1):
Pump power rises. Recirculation pumps are often modest horsepower individually, but a plant with several pumps running off their curves is real kW. On a CIRO operating-cost screen, unexplained low-side pump kW is a recirculation story.
Wet suction carries more liquid. Return mains and the separator see a higher liquid fraction . Two-phase pressure drop goes up. The separator can overload : vapor velocity through the disengagement space rises with compressor load at the same time liquid rain increases, so droplets carry over.
High level in the LPR becomes more likely during defrost dumps and load swings because more liquid is in transit in the returns.
Coil internal pressure drop can rise, which hurts TD from the other direction.
The separator (Section 17.3) is sized for a design recirculation rate, not for an arbitrary flood.
Mechanical pump vs gas pump
Mechanical liquid pumps (typically canned-motor or sealless ammonia pumps) take liquid from the LPR and push it to the evaporator liquid header. Gas-pumped systems use high-pressure gas (often a transfer-vessel / CPR-style arrangement) to push liquid without a rotating pump. Chapter 18 owns NPSH , cavitation, and oil-pot details. Here you only need: both methods exist to produce overfeed ; the ratio definition does not change . If the exam shows a gas-pumped plant, you still compute circulated mass over evaporated mass.
Recirculation language you will see
- Phrase Meaning
- 4:1 overfeed ṁ_circ / ṁ_evap = 4
- Recirculation rate of 4 Same ratio
300% overfeed Sometimes used to mean 4:1 (100% evaporated + 300% extra). Ambiguous. Prefer 4:1 . If a stem says 300% extra, that is 4:1.
n-times circulation Same as n:1
CIRO-style trap: treating 4:1 as circulate 4 lb and evaporate 4 lb. Wrong. Evaporate 1, circulate 4.
Load changes evaporated mass, not pumped mass (unless you VFD the pump)
A fixed-speed pump delivers roughly a fixed gpm (curve versus head). Evaporated mass follows the load . At light load , ṁ_evap falls, so the ratio rises even if the pump does nothing. Light-load overfeed can become very wet returns — good for wetting, harder on the separator. At heavy load , ṁ_evap rises, ratio falls , and you approach dry-out if the pump cannot keep up. That is why pumps are selected for design load at 3:1 to 4:1 , with some margin, and why a plugged liquid line at peak pull-down is a dry-out event.
A VFD on a recirculation pump can track load and hold a more constant ratio. If the drive is in hand at minimum speed during a blast freeze, you have invented low overfeed. If it is locked at 60 Hz on a Sunday night with one room calling, you have invented extra pump kW and a wet separator.
Defrost makes the ratio dynamic. A coil off on hot-gas defrost evaporates little (it is condensing inside). Neighbors may still be at full load. Header flow can shift. After defrost, a cold coil can take a gulp of liquid. The surge drum exists so those gulps do not go to the compressor.
Exam traps
Ratio is mass , not tons, not gpm until converted.
Typical industrial ammonia: 3:1 to 4:1 .
Too low → dry-out, high TD . Too high → pump kW, wet suction, separator overload .
Overfeed is flooded-coil operation with extra liquid; it is not a DX TXV set a little rich.
Do not invent a RETA-official pump kW formula. Direction of the effect is what is tested.