Study guide
12.1 Condenser Approach and Non-Condensables
RETA CIRO Certified Industrial Refrigeration Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 Test-Day Tools, On-Screen References, and Calculators 1.3 CIRO vs CARO and the RETA Credential Path
2 IIAR and ASHRAE Standards
2.1 IIAR 2 and ASHRAE 15 Machinery-Room Design 2.2 IIAR 6 Inspection, Testing, and Maintenance 2.3 IIAR 7 Operating Procedures and IIAR 9 Existing Systems
3 OSHA Process Safety Management
3.1 PSM Applicability and the 14 Elements 3.2 Process Safety Information 3.3 Process Hazard Analysis 3.4 Operating Procedures, Training, Contractors, and PSSR
4 Integrity, Change, and Emergency Programs
4.1 Mechanical Integrity and Pressure-Relief Valves 4.2 Hot Work and Management of Change 4.3 Incident Investigation and Compliance Audits 4.4 Emergency Planning, EPA RMP, and the General Duty Clause
5 Ammonia Hazards and Machinery-Room Safety
5.1 Ammonia Properties, SDS, and Exposure Limits 5.2 Detection, Ventilation, and Emergency Shutdown 5.3 Eyewash, PPE, Materials Compatibility, and ASME B31.5 Piping
6 Three-Phase Motors and Starting
6.1 Three-Phase Motors, Nameplates, and FLA 6.2 Wye-Delta and Reduced-Voltage Starting 6.3 Voltage Unbalance 6.4 Single-Phasing, Rotation Checks, and Screw Compressors
7 Ladder Diagrams, VFDs, and Power
7.1 Ladder Diagrams, Seal-In Circuits, and Safety Interlocks 7.2 Variable-Frequency Drives in Refrigeration Plants 7.3 Power Factor, kW/HP, Overloads, and Machinery-Room Electrical Classification
8 Pressure-Enthalpy Diagrams and Properties
8.1 Reading the Ammonia P-h Diagram 8.2 Saturated Properties, psia vs psig, and Saturation Temperature 8.3 Superheat, Subcooling, and Flash Gas
9 Capacity, COP, and Efficiency
9.1 Enthalpy, Latent Heat, and Net Refrigerating Effect 9.2 COP, Tons of Refrigeration, and Heat Rejection Ratio 9.3 BHP/ton, Isentropic Efficiency, and Theoretical Discharge Temperature
10 Heat Transfer and Rejection
10.1 Q = UAΔT, LMTD, and Heat Exchangers 10.2 Condensers, Approach, and Wet-Bulb Limits 10.3 Specific Volume, Mass Flow, and Compression Ratio
11 System Screens and Performance KPIs
11.1 Using CIRO Operating Screens (normal vs abnormal) 11.2 kW/ton, BHP/ton, and KPI Dashboards 11.3 Power Cost, Demand Charges, and the Cost of Poor Operation
12 Approach, TD, and Oil-Cooling Diagnostics
12.1 Condenser Approach and Non-Condensables 12.2 Evaporator TD and Superheat Diagnostics 12.3 Thermosiphon Oil Coolers and Oil-Temperature Trends
13 Floating Head, Sequencing, and Slide Valves
13.1 Floating Head Pressure 13.2 Compressor Sequencing 13.3 Screw Slide-Valve Unloading and Feedback
14 Expansion Devices and DX Feed
14.1 Solenoid and TXV Pairs, Equalizers, and Hunting 14.2 Electronic Expansion Valves 14.3 Hand Expansion Valves and DX Coil Distribution
15 Pressure-Regulating and Pilot-Operated Valves
15.1 Back-Pressure Regulators 15.2 Crankcase Pressure Regulators and Gas-Pumped CPR Systems 15.3 Pilot-Operated Valves and High-to-Low Relief Regulators
16 Floats, Checks, Solenoid Failures, and Piping
16.1 High-Side Floats and High-Pressure Receivers 16.2 Check Valves, Discharge Checks, and Defrost Check Valves 16.3 Solenoid Failure Modes, Strainers, King Valves, and Ammonia Piping
17 Flooded and Liquid-Overfeed Basics
17.1 Flooded vs DX Advantages and Charge 17.2 Overfeed Ratios and Recirculation Rate 17.3 Surge Drums, Separators, and Wet Suction Returns
18 Pumps, Oil Management, and Level Control
18.1 Mechanical Liquid Pumps and NPSH 18.2 Oil Drain Pots, Rectifiers, and Thermosiphon Oil Management 18.3 Level Glasses, Float Switches, and High/Low Cutouts 18.4 Liquid-Line Sizing and High-/Low-Pressure Receivers
19 Two-Stage Compression and Intercoolers
19.1 Why Two-Stage: Compression Ratio and Discharge Temperature 19.2 Interstage Pressure Selection (Geometric Mean) 19.3 Open Flash Intercoolers 19.4 Closed Intercoolers and Two-Stage Troubleshooting
20 Cascade and Secondary Coolant Systems
20.1 NH3/CO2 Cascade Designs 20.2 Glycol and Brine Secondary Coolants (pH, freeze point, inhibitors) 20.3 Why Secondary Coolants and Glycol Testing/Maintenance
21 Evaporator Defrost
21.1 Hot-Gas Defrost Sequence 21.2 Defrost Drain Pressure-Relief Regulators and Soft Equalization 21.3 Time/Temperature Termination, Drain Pans, Water and Electric Defrost
12.1 Condenser Approach and Non-Condensables
Key Takeaways Explain This Topic AI
Condenser approach is condensing saturation temperature from condenser pressure minus leaving water, or minus entering wet-bulb, depending on what the stem gives you.
Non-condensable penalty is actual condensing pressure minus saturation pressure at the real liquid or sump temperature, not a wet-bulb subtraction.
If liquid is 85°F (about 152–154 psig class) and condenser outlet is 181 psig (95°F class), the roughly 27 psi gap is non-condensable or a gauge/location error.
Purge from the high point at the top of the condenser or receiver vapor space; air collects where ammonia has already condensed and drained.
Chronic return of the same excess pressure on a vacuum-suction plant is air in-leakage through seals and packing, not a condenser that needs daily venting.
Last updated: September 2026
12.1 Condenser Approach and Non-Condensables
CIRO Monitoring System Performance items (about 15% of the sitting) expect you to read a plant screen the way a supervisor reads a log sheet: convert a pressure to a saturation temperature, subtract the right air- or water-side temperature, and decide whether the condenser is dirty, air-bound, weather-limited, or simply loaded. Approach is the first number. Non-condensables are the first trap. Heat-flow chapters already defined UA and wet-bulb limits; this section is the diagnostic use of those numbers on an ammonia industrial plant.
Two approach definitions — pick the one the stem gives you
Condensing saturation temperature (SCT) is not the discharge-gas thermometer. Convert condenser-outlet pressure (or a true condenser pressure tap) through the ammonia P/T chart. That saturation temperature is the refrigerant-side number in every approach formula.
Water-cooled shell-and-tube: Approach = SCT − leaving condenser water temperature. The water has already picked up the heat; the remaining gap to saturation is the exchanger's approach.
Evaporative condenser (the usual CIRO screen): Approach = SCT − entering wet-bulb temperature. Wet-bulb is the thermodynamic floor of an evaporative condenser. You cannot condense below wet-bulb, and you should not expect a 2°F approach to a 78°F wet-bulb on a loaded industrial unit.
If a question gives leaving water, subtract leaving water. If it gives wet-bulb on an evaporative condenser, subtract wet-bulb. Mixing those two subtractions is a common wrong answer.
Typical healthy evaporative approaches on ammonia sit in a rough 8–15°F band at design wet-bulb and load. 20°F+ is a problem, not a climate excuse, until you have proven otherwise. Water-cooled ammonia condensers often run 4–10°F to leaving water when clean and fully watered.
How to get SCT — and where the gauge lies
Discharge pressure at the compressor is not condenser pressure. Oil-separator drop, discharge-line loss, and a dirty coalescer all make compressor discharge higher than the condenser. Using discharge pressure as SCT overstates approach and can send you acid-washing a condenser that is not the problem.
Read condenser inlet/outlet or the condenser pressure transmitter the screen labels as head or condensing. Then look up saturation temperature on the on-screen P/T chart . RETA provides that chart in the exam session; do not treat a memorized wall card as more official than the reference in front of you.
Rounded R-717 saturation values in the high-side band (ASHRAE/NIST class, gauge pressure):
- Saturation temperature (°F) Approx. pressure (psig)
- 80 138
- 85 152 (plant charts often call this the 154 psig class )
- 90 166
- 95 181
- 100 197
Ammonia at 95°F saturates at 181.1 psig . That pair is the backbone of the non-condensable example below. 85°F liquid sits near 152 psig on NIST-style tables; many engine-room charts round the same point into the 154 psig class . On the exam, look up the chart you are given and then subtract. The diagnostic is the gap , not a fight over 2 psi of table rounding.
Non-condensables: pressure without matching liquid temperature
Air, nitrogen, and hydrogen do not condense at condenser conditions. They occupy volume, and by Dalton's law they add partial pressure on top of the ammonia vapor pressure. The liquid in the sump still tracks ammonia's saturation, not the total gauge reading.
Diagnostic: compare actual condensing pressure to saturation pressure at the actual liquid or sump temperature .
Worked screen (original numbers, same class as a typical CIRO high-side snapshot):
- Condenser liquid / sump = 85°F → sat ≈ 152–154 psig
- Condenser outlet = 181 psig → that is the 95°F class
Excess ≈ 181 − 154 ≈ 27 psi (about 29 psi if you use 152 psig). That gap is non-condensable penalty — or a gauge/location error you must rule out before you condemn the condenser.
Apparent SCT from 181 psig is 95°F . True liquid is 85°F . You are carrying about 10°F of phantom condensing temperature . If entering wet-bulb is 78°F , the screen approach is 95 − 78 = 17°F . An operator who only looks at approach will call for washdown. The liquid thermometer tells you to purge , not to tear the basin apart first.
Use sump or condenser-outlet liquid , not liquid after a dedicated subcooler. Extra subcooling makes liquid colder than condensing temperature and inflates the apparent air penalty.
Fouling vs non-condensables vs weather
Cause Liquid/sump T vs P-derived SCT What else you see
Scale, oil film, plugged spray nozzles Liquid climbs with SCT — both are hot High approach and hot liquid; wash/descale helps
Non-condensables Liquid lags SCT — liquid cooler than P implies Excess P vs sat-at-liquid; purge drops head without a weather change
High wet-bulb / hot cooling water SCT high, but P matches liquid T Approach to wet-bulb may still be normal
Fans off / low water flow / undersized condenser High SCT, liquid near SCT Heat-rejection hardware, not air in the vessel
Overcharged / liquid-logged condenser High SCT from lost surface High receiver level, possible liquid in condenser circuits
Exam trap: an undersized condenser shows high approach because UA is small. It does not produce a 27 psi gap between 85°F liquid and 181 psig. That mismatch is non-condensables (or the wrong gauge).
Purge — where, why, and what chronic means
Non-condensables collect in the vapor space at the top of the condenser, the last-pass coil header, or the high-pressure receiver. Ammonia condenses and drains; air stays gas. The purge point is the high point , never the sump drain.
Automatic refrigerated purgers take a gas mixture, condense the ammonia, and vent the residual non-condensable. That is the professional method.
Manual venting from a condenser can dump ammonia to atmosphere. CIRO is a supervisor exam: use the purger, follow the plant procedure, and treat the vent as a process emission, not a bleed-until-the-gauge-falls habit.
After construction, a pump-down, or opening the high side, a one-time air charge is expected. Purge until liquid temperature and pressure agree, then stop.
Chronic return of the same 20–30 psi penalty — especially on a vacuum-suction low-temperature system — means air in-leakage , not a mysterious condenser disease. Any suction below atmospheric (ammonia colder than about −28°F / 0 psig ) will pull air in through open-drive shaft seals, recip packing, recirculator and transfer-pump seals, unused evaporators with leaking solenoids, and loosely packed valve stems. Purge restores the screen for a shift. Finding the leak is mechanical integrity. If the only fix is a daily purge, the plant is feeding air on the vacuum side.
Gauge checklist before you purge
Same pressure transmitter the screen uses for SCT — not a mismatched compressor-discharge gauge.
Liquid temperature in the condenser sump or outlet liquid , not after a subcooler.
Steady wet-bulb and water flow; approach is a steady-state KPI.
If excess pressure vanishes when you move the gauge to a condenser tap, you had a location penalty, not air.
Treat approach as a heat-rejection health number and the P-versus-liquid-T gap as an air-in-the-high-side number. CIRO will hand you both. Separate them.