10.1 Q = UAΔT, LMTD, and Heat Exchangers

RETA CIRO Certified Industrial Refrigeration Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Test-Day Tools, On-Screen References, and Calculators 1.3 CIRO vs CARO and the RETA Credential Path

2 IIAR and ASHRAE Standards

2.1 IIAR 2 and ASHRAE 15 Machinery-Room Design 2.2 IIAR 6 Inspection, Testing, and Maintenance 2.3 IIAR 7 Operating Procedures and IIAR 9 Existing Systems

3 OSHA Process Safety Management

3.1 PSM Applicability and the 14 Elements 3.2 Process Safety Information 3.3 Process Hazard Analysis 3.4 Operating Procedures, Training, Contractors, and PSSR

4 Integrity, Change, and Emergency Programs

4.1 Mechanical Integrity and Pressure-Relief Valves 4.2 Hot Work and Management of Change 4.3 Incident Investigation and Compliance Audits 4.4 Emergency Planning, EPA RMP, and the General Duty Clause

5 Ammonia Hazards and Machinery-Room Safety

5.1 Ammonia Properties, SDS, and Exposure Limits 5.2 Detection, Ventilation, and Emergency Shutdown 5.3 Eyewash, PPE, Materials Compatibility, and ASME B31.5 Piping

6 Three-Phase Motors and Starting

6.1 Three-Phase Motors, Nameplates, and FLA 6.2 Wye-Delta and Reduced-Voltage Starting 6.3 Voltage Unbalance 6.4 Single-Phasing, Rotation Checks, and Screw Compressors

7 Ladder Diagrams, VFDs, and Power

7.1 Ladder Diagrams, Seal-In Circuits, and Safety Interlocks 7.2 Variable-Frequency Drives in Refrigeration Plants 7.3 Power Factor, kW/HP, Overloads, and Machinery-Room Electrical Classification

8 Pressure-Enthalpy Diagrams and Properties

8.1 Reading the Ammonia P-h Diagram 8.2 Saturated Properties, psia vs psig, and Saturation Temperature 8.3 Superheat, Subcooling, and Flash Gas

9 Capacity, COP, and Efficiency

9.1 Enthalpy, Latent Heat, and Net Refrigerating Effect 9.2 COP, Tons of Refrigeration, and Heat Rejection Ratio 9.3 BHP/ton, Isentropic Efficiency, and Theoretical Discharge Temperature

10 Heat Transfer and Rejection

10.1 Q = UAΔT, LMTD, and Heat Exchangers 10.2 Condensers, Approach, and Wet-Bulb Limits 10.3 Specific Volume, Mass Flow, and Compression Ratio

11 System Screens and Performance KPIs

11.1 Using CIRO Operating Screens (normal vs abnormal) 11.2 kW/ton, BHP/ton, and KPI Dashboards 11.3 Power Cost, Demand Charges, and the Cost of Poor Operation

12 Approach, TD, and Oil-Cooling Diagnostics

12.1 Condenser Approach and Non-Condensables 12.2 Evaporator TD and Superheat Diagnostics 12.3 Thermosiphon Oil Coolers and Oil-Temperature Trends

13 Floating Head, Sequencing, and Slide Valves

13.1 Floating Head Pressure 13.2 Compressor Sequencing 13.3 Screw Slide-Valve Unloading and Feedback

14 Expansion Devices and DX Feed

14.1 Solenoid and TXV Pairs, Equalizers, and Hunting 14.2 Electronic Expansion Valves 14.3 Hand Expansion Valves and DX Coil Distribution

15 Pressure-Regulating and Pilot-Operated Valves

15.1 Back-Pressure Regulators 15.2 Crankcase Pressure Regulators and Gas-Pumped CPR Systems 15.3 Pilot-Operated Valves and High-to-Low Relief Regulators

16 Floats, Checks, Solenoid Failures, and Piping

16.1 High-Side Floats and High-Pressure Receivers 16.2 Check Valves, Discharge Checks, and Defrost Check Valves 16.3 Solenoid Failure Modes, Strainers, King Valves, and Ammonia Piping

17 Flooded and Liquid-Overfeed Basics

17.1 Flooded vs DX Advantages and Charge 17.2 Overfeed Ratios and Recirculation Rate 17.3 Surge Drums, Separators, and Wet Suction Returns

18 Pumps, Oil Management, and Level Control

18.1 Mechanical Liquid Pumps and NPSH 18.2 Oil Drain Pots, Rectifiers, and Thermosiphon Oil Management 18.3 Level Glasses, Float Switches, and High/Low Cutouts 18.4 Liquid-Line Sizing and High-/Low-Pressure Receivers

19 Two-Stage Compression and Intercoolers

19.1 Why Two-Stage: Compression Ratio and Discharge Temperature 19.2 Interstage Pressure Selection (Geometric Mean) 19.3 Open Flash Intercoolers 19.4 Closed Intercoolers and Two-Stage Troubleshooting

20 Cascade and Secondary Coolant Systems

20.1 NH3/CO2 Cascade Designs 20.2 Glycol and Brine Secondary Coolants (pH, freeze point, inhibitors) 20.3 Why Secondary Coolants and Glycol Testing/Maintenance

21 Evaporator Defrost

21.1 Hot-Gas Defrost Sequence 21.2 Defrost Drain Pressure-Relief Regulators and Soft Equalization 21.3 Time/Temperature Termination, Drain Pans, Water and Electric Defrost

10.1 Q = UAΔT, LMTD, and Heat Exchangers

Key Takeaways Explain This Topic AI

Heat rate is Q = UAΔT: U is the overall coefficient, A is surface area, and ΔT is the driving temperature difference

Fouling, oil film, scale, and ice add resistance in series, so U falls and the same load needs a larger ΔT (lower suction or higher condensing temperature)

When both end differences are known, use LMTD = (ΔT1 − ΔT2) / ln(ΔT1/ΔT2), not the arithmetic mean of the two ends

Operator evaporator TD is room (or process) temperature minus refrigerant saturation temperature; that shortcut is larger than coil LMTD when air or fluid temperature changes through the exchanger

Last updated: September 2026

10.1 Q = UAΔT, LMTD, and Heat Exchangers

Heat does not jump from a blast freezer to the evaporative condenser. It crosses metal , films , and whatever is stuck on those films. CIRO Heat Flow items treat that crossing as a rate equation, not a slogan. If you can name each symbol, you can predict what a dirty coil, a starved pump, or a tight approach will do to suction and discharge pressure.

  • The rate equation
  • Q = U A ΔT

Symbol Name Typical English units What it is on the plant

Q Heat-transfer rate Btu/h (or Btu/min) Load the surface must move: evaporator duty, condenser rejection, oil-cooler duty

U Overall heat-transfer coefficient Btu/h·ft²·°F Combined conductance of both films, the wall, and fouling

A Surface area ft² Tube, plate, or fin area the manufacturer rated — the area that is actually wet and clean enough to work

ΔT Driving temperature difference °F How much hotter the warm side is than the cold side, defined the way the surface is calculated

Rearranged, the same sentence is the operator's diagnostic:

ΔT = Q / (U A)

For a fixed load and a fixed area , anything that lowers U must raise ΔT . On an evaporator that means refrigerant saturation temperature is pulled down relative to the room or process. On a condenser it means saturation temperature is pushed up relative to leaving water or outdoor wet bulb. You feel those shifts as suction and discharge psig .

U is not a single film coefficient. Resistances add in series:

1/U = 1/h_warm + x/k_wall + R_fouling + 1/h_cold

You will not be asked to invent a metal conductivity. You will be asked what happens when R_fouling grows. Oil film on a flooded chiller, ice on a unit cooler, scale on condenser tubes, and a dry evaporative-condenser coil (no water) are all extra resistance. Metal thickness barely moves from year to year. Fouling does.

A is not the footprint of the penthouse. It is the heat-transfer surface that still participates. A plugged circuit, a frozen slab covering half the fins, or a condenser bay isolated for repair is lost area. Lost A is the same math as a lower U: required ΔT rises.

ΔT is the argument people mix up. Three different differences live in the engine room:

Local difference at one point along a tube (T_hot − T_cold at that station).

Logarithmic mean temperature difference (LMTD) — the correct average of the two end differences when the two fluids (or one fluid and a two-phase refrigerant) change temperature along the exchanger.

Operator TD — a plant shortcut such as room temperature minus evaporator saturation, or condensing saturation minus leaving water (approach).

CIRO will name which one it wants. Do not feed operator TD into Q = UAΔT when the stem just computed LMTD, and do not call LMTD the approach.

Worked example — fouling raises required ΔT

A 20-ton coil must move Q = 20 × 12,000 = 240,000 Btu/h . Fin-and-tube area A = 2,000 ft² . In a clean, wet, fully fed condition the coil's LMTD is 8°F .

U_clean = Q / (A × LMTD) = 240,000 / (2,000 × 8) = 15 Btu/h·ft²·°F

After a week of product ice and a light oil film, U falls to 12 Btu/h·ft²·°F (a 20% hit — directional teaching numbers, not a manufacturer rating).

To hold the same 20 tons:

LMTD_dirty = 240,000 / (12 × 2,000) = 10°F

If the room is still 0°F , a clean LMTD of 8°F might have meant a saturation temperature near −8°F . A dirty 10°F LMTD pulls saturation toward −10°F . The compressor now sees a lower suction pressure, higher specific volume, and less mass per cubic foot — the capacity problem of Section 10.3. Operators who only chase the TXV miss that U fell . The coil did not forget how to boil ammonia; the driving difference had to grow because the surface got worse.

If load falls (empty dock) while U stays dirty, ΔT can look 'normal' again. Judge U against Q , not against a single suction gauge in isolation.

LMTD, not the arithmetic mean

When a single-phase fluid changes temperature while the other stream is at a known temperature (two-phase ammonia is nearly isothermal at Tsat), the two end differences are:

  • ΔT1 = difference at one end of the exchanger
  • ΔT2 = difference at the other end
  • LMTD = (ΔT1 − ΔT2) / ln(ΔT1 / ΔT2)

The arithmetic mean (ΔT1 + ΔT2)/2 is always larger than LMTD when ΔT1 ≠ ΔT2. Using it overstates Q . The error is small when the two ends are close and ugly when they are not. If either end difference is zero , LMTD is zero: you have no driving force at that end, and the formula's logarithm blows up. That is the physics of trying to condense at the leaving-water temperature or at the wet bulb.

Counterflow versus parallel flow matters when both streams change temperature (glycol-to-glycol, oil cooler with sensible oil and a liquid thermosiphon that still has a temperature glide). Counterflow keeps a more uniform local ΔT and can allow the cold stream to leave hotter than the hot stream leaves. Parallel flow cannot. Two-phase evaporators and condensers with a flat Tsat have the same two end differences in either arrangement, so LMTD uses the same two numbers — but you still must not replace LMTD with (Tsat − T_fluid,avg).

Worked LMTD — water-cooled condenser

Ammonia condenses at a constant 95°F in a shell-and-tube unit. Cooling water enters at 75°F and leaves at 85°F .

  • Range (water temperature rise) = 85 − 75 = 10°F
  • Approach (condensing sat minus leaving water) = 95 − 85 = 10°F
  • End difference at the water inlet = 95 − 75 = 20°F
  • End difference at the water outlet = 95 − 85 = 10°F
  • LMTD = (20 − 10) / ln(20/10) = 10 / 0.693 = 14.4°F

Arithmetic mean = (20 + 10)/2 = 15.0°F — about 4% high. If U = 180 Btu/h·ft²·°F and A = 400 ft²:

Q_LMTD = 180 × 400 × 14.4 = 1,036,800 Btu/h ≈ 86.4 tons of rejection

Using 15°F would invent 1,080,000 Btu/h . The extra 43,200 Btu/h is not in the water; it is an arithmetic lie.

Wider spread, worse lie: ends of 30°F and 10°F give LMTD = 20 / ln(3) = 18.2°F versus arithmetic 20°F (~10% high).

Evaporator TD versus LMTD

Evaporator TD = room (or entering process) temperature − refrigerant saturation temperature.

A +34°F dock coil at 20°F saturated ammonia has TD = 14°F . A 0°F freezer with −10°F Tsat has TD = 10°F . A glycol chiller with 20°F entering glycol and 10°F Tsat has a process TD of 10°F . That is how operators and many coil selections talk.

It is not LMTD if the air or glycol leaves colder than it entered. The coil sees a smaller difference at the leaving end.

Worked air unit. Room 34°F , air off the coil 28°F , ammonia Tsat = 22°F .

  • Operator TD = 34 − 22 = 12°F
  • On-coil difference = 34 − 22 = 12°F
  • Off-coil difference = 28 − 22 = 6°F
  • LMTD = (12 − 6) / ln(12/6) = 6 / 0.693 = 8.7°F

If someone multiplies UA by 12°F instead of 8.7°F, they overstate coil capacity by about 38% . On a CIRO table item, that is the difference between a coil that holds the room and a coil you are about to starve or over-defrost.

Process evaporators use the same split: process TD from entering fluid (or setpoint) to Tsat; LMTD from both end differences if the stem gives in and out temperatures. Flooded vessels with tiny fluid ΔT have LMTD almost equal to TD. DX air coils with a large air drop do not.

Where the equation lives in the plant

Evaporators — air units, plate-and-frame, shell-and-tube chillers, jacketed tanks. Q is the refrigerating load. ΔT is LMTD or the stated TD to Tsat.

Condensers — evaporative, water-cooled, air-cooled. Q is heat of rejection (evaporator heat plus compressor work from Chapter 9), not evaporator tons alone.

Oil coolers — thermosiphon, water, or liquid injection as a heat exchanger between hot oil and a sink. Same UAΔT; a fouled thermosiphon is a U problem, not a personality trait of the screw.

Intercoolers and cascade evaporators — later chapters; the rate equation does not change.

Manufacturers often hide U and A inside a rated THR at a stated TD . You still think in Q = UAΔT: if the nameplate assumes 15°F wet-bulb approach and you only have 8°F to the day's wet bulb, the condenser cannot reject nameplate heat unless Tsat rises or load falls.

Exam traps

Treating operator TD as LMTD on a coil with a large air or fluid temperature change.

Using arithmetic mean of the end differences and calling it LMTD.

Raising ΔT in your head when U fell, then blaming the expansion valve for the suction drop.

Using condenser approach (one end) as if it were the LMTD for Q = UAΔT.

Forgetting that condenser Q is rejection, not evaporator tons.

Mixing °F TD with psig ; convert through the saturation table before you talk pressure.

Loading diagram... Heat crosses films, metal, and fouling — U is the overall result

Same 20-ton coil: dirty U needs more LMTD to hold Q