7.3 Power Factor, kW/HP, Overloads, and Machinery-Room Electrical Classification

RETA CIRO Certified Industrial Refrigeration Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Test-Day Tools, On-Screen References, and Calculators 1.3 CIRO vs CARO and the RETA Credential Path

2 IIAR and ASHRAE Standards

2.1 IIAR 2 and ASHRAE 15 Machinery-Room Design 2.2 IIAR 6 Inspection, Testing, and Maintenance 2.3 IIAR 7 Operating Procedures and IIAR 9 Existing Systems

3 OSHA Process Safety Management

3.1 PSM Applicability and the 14 Elements 3.2 Process Safety Information 3.3 Process Hazard Analysis 3.4 Operating Procedures, Training, Contractors, and PSSR

4 Integrity, Change, and Emergency Programs

4.1 Mechanical Integrity and Pressure-Relief Valves 4.2 Hot Work and Management of Change 4.3 Incident Investigation and Compliance Audits 4.4 Emergency Planning, EPA RMP, and the General Duty Clause

5 Ammonia Hazards and Machinery-Room Safety

5.1 Ammonia Properties, SDS, and Exposure Limits 5.2 Detection, Ventilation, and Emergency Shutdown 5.3 Eyewash, PPE, Materials Compatibility, and ASME B31.5 Piping

6 Three-Phase Motors and Starting

6.1 Three-Phase Motors, Nameplates, and FLA 6.2 Wye-Delta and Reduced-Voltage Starting 6.3 Voltage Unbalance 6.4 Single-Phasing, Rotation Checks, and Screw Compressors

7 Ladder Diagrams, VFDs, and Power

7.1 Ladder Diagrams, Seal-In Circuits, and Safety Interlocks 7.2 Variable-Frequency Drives in Refrigeration Plants 7.3 Power Factor, kW/HP, Overloads, and Machinery-Room Electrical Classification

8 Pressure-Enthalpy Diagrams and Properties

8.1 Reading the Ammonia P-h Diagram 8.2 Saturated Properties, psia vs psig, and Saturation Temperature 8.3 Superheat, Subcooling, and Flash Gas

9 Capacity, COP, and Efficiency

9.1 Enthalpy, Latent Heat, and Net Refrigerating Effect 9.2 COP, Tons of Refrigeration, and Heat Rejection Ratio 9.3 BHP/ton, Isentropic Efficiency, and Theoretical Discharge Temperature

10 Heat Transfer and Rejection

10.1 Q = UAΔT, LMTD, and Heat Exchangers 10.2 Condensers, Approach, and Wet-Bulb Limits 10.3 Specific Volume, Mass Flow, and Compression Ratio

11 System Screens and Performance KPIs

11.1 Using CIRO Operating Screens (normal vs abnormal) 11.2 kW/ton, BHP/ton, and KPI Dashboards 11.3 Power Cost, Demand Charges, and the Cost of Poor Operation

12 Approach, TD, and Oil-Cooling Diagnostics

12.1 Condenser Approach and Non-Condensables 12.2 Evaporator TD and Superheat Diagnostics 12.3 Thermosiphon Oil Coolers and Oil-Temperature Trends

13 Floating Head, Sequencing, and Slide Valves

13.1 Floating Head Pressure 13.2 Compressor Sequencing 13.3 Screw Slide-Valve Unloading and Feedback

14 Expansion Devices and DX Feed

14.1 Solenoid and TXV Pairs, Equalizers, and Hunting 14.2 Electronic Expansion Valves 14.3 Hand Expansion Valves and DX Coil Distribution

15 Pressure-Regulating and Pilot-Operated Valves

15.1 Back-Pressure Regulators 15.2 Crankcase Pressure Regulators and Gas-Pumped CPR Systems 15.3 Pilot-Operated Valves and High-to-Low Relief Regulators

16 Floats, Checks, Solenoid Failures, and Piping

16.1 High-Side Floats and High-Pressure Receivers 16.2 Check Valves, Discharge Checks, and Defrost Check Valves 16.3 Solenoid Failure Modes, Strainers, King Valves, and Ammonia Piping

17 Flooded and Liquid-Overfeed Basics

17.1 Flooded vs DX Advantages and Charge 17.2 Overfeed Ratios and Recirculation Rate 17.3 Surge Drums, Separators, and Wet Suction Returns

18 Pumps, Oil Management, and Level Control

18.1 Mechanical Liquid Pumps and NPSH 18.2 Oil Drain Pots, Rectifiers, and Thermosiphon Oil Management 18.3 Level Glasses, Float Switches, and High/Low Cutouts 18.4 Liquid-Line Sizing and High-/Low-Pressure Receivers

19 Two-Stage Compression and Intercoolers

19.1 Why Two-Stage: Compression Ratio and Discharge Temperature 19.2 Interstage Pressure Selection (Geometric Mean) 19.3 Open Flash Intercoolers 19.4 Closed Intercoolers and Two-Stage Troubleshooting

20 Cascade and Secondary Coolant Systems

20.1 NH3/CO2 Cascade Designs 20.2 Glycol and Brine Secondary Coolants (pH, freeze point, inhibitors) 20.3 Why Secondary Coolants and Glycol Testing/Maintenance

21 Evaporator Defrost

21.1 Hot-Gas Defrost Sequence 21.2 Defrost Drain Pressure-Relief Regulators and Soft Equalization 21.3 Time/Temperature Termination, Drain Pans, Water and Electric Defrost

7.3 Power Factor, kW/HP, Overloads, and Machinery-Room Electrical Classification

Key Takeaways Explain This Topic AI

Three-phase real power is kW = √3 × V × I × PF / 1000; shaft horsepower relates by HP = kW / 0.746, and motor input kW is shaft power divided by efficiency.

On a 480 V screen with PF 0.86, convert measured amps to kW demand first, then to $/hour as kW × $/kWh; do not treat nameplate HP as the electrical demand.

Lagging motors are corrected with capacitors so line current and kVA fall while real kW stays essentially the same; overloads protect against sustained heating, while fuses or breakers provide short-circuit and ground-fault protection.

ANSI/IIAR 2 designates a machinery room unclassified (ordinary) when emergency ventilation and ammonia detection are provided; without emergency ventilation the room is not less than Class I, Division 2, Group D — not an automatic Class I, Division 1 mandate — and emergency exhaust motors are typically totally enclosed, not explosion-proof.

Last updated: September 2026

Three-Phase Power on a CIRO Screen

Industrial refrigeration motors are three-phase . Real (working) power is: k W = 3 × V × I × P F 1000 \mathrm{kW} = \frac{\sqrt{3} \times V \times I \times \mathrm{PF}}{1000} kW = 1000 3 ​ × V × I × PF ​

Use line-to-line volts , line amps , and power factor as a decimal . 3 ≈ 1.732 \sqrt{3} \approx 1.732 3 ​ ≈ 1.732 . Power factor (PF) is k W / k V A \mathrm{kW}/\mathrm{kVA} kW / kVA , or cos ⁡ ϕ \cos\phi cos ϕ for a simple sine wave. Induction motors are lagging (current lags voltage) because they draw magnetizing vars.

Horsepower on the shaft: H P = k W s h a f t 0.746 and k W s h a f t = H P × 0.746 \mathrm{HP} = \frac{\mathrm{kW}_{\mathrm{shaft}}}{0.746} \quad \text{and} \quad \mathrm{kW}_{\mathrm{shaft}} = \mathrm{HP} \times 0.746 HP = 0.746 kW shaft ​ ​ and kW shaft ​ = HP × 0.746

Motor efficiency sits between shaft power and electrical input: k W i n p u t = H P × 0.746 η \mathrm{kW}_{\mathrm{input}} = \frac{\mathrm{HP} \times 0.746}{\eta} kW input ​ = η HP × 0.746 ​

CIRO-style screens often list a 300 HP class screw , 480 V , PF 0.86 , and 93% motor efficiency . Those numbers describe the machine , not a promise that the compressor is at 300 HP right now. Demand is whatever the ammeter (and PF) say.

Worked screen: amps → kW → dollars

A thermosiphon-oil-cooled screw shows 480 V , average current 312 A , PF 0.86 , motor efficiency 93% .

Electrical input: k W = 1.732 × 480 × 312 × 0.86 / 1000 \mathrm{kW} = 1.732 \times 480 \times 312 \times 0.86 / 1000 kW = 1.732 × 480 × 312 × 0.86/1000 . First, 1.732 × 480 = 831.4 1.732 \times 480 = 831.4 1.732 × 480 = 831.4 . Then 831.4 × 312 ≈ 259,400 831.4 \times 312 \approx 259{,}400 831.4 × 312 ≈ 259 , 400 . Then 259,400 × 0.86 ≈ 223,100 259{,}400 \times 0.86 \approx 223{,}100 259 , 400 × 0.86 ≈ 223 , 100 . Divide by 1000: about 223 kW .

Shaft load: H P = ( 223 × 0.93 ) / 0.746 ≈ 278 H P \mathrm{HP} = (223 \times 0.93) / 0.746 \approx 278\ \mathrm{HP} HP = ( 223 × 0.93 ) /0.746 ≈ 278 HP . That is a 300 HP class motor loaded hard, but not above nameplate shaft HP .

Energy cost: c o s t = k W × $ / k W h \mathrm{cost} = \mathrm{kW} \times \text{\textdollar}/\mathrm{kWh} cost = kW × $ / kWh . At 0.12 / k W h 0.12/\mathrm{kWh} 0.12/ kWh , 223 × 0.12 ≈ $ 26.80 223 \times 0.12 \approx \text{\textdollar}26.80 223 × 0.12 ≈ $ 26.80 per hour of run time at that load. Demand charges are extra and belong with KPI/cost chapters; do not ignore them in real plants, but the exam's first skill is kW × energy rate .

Full-load check from the nameplate (if the screen asked "what current at rated HP?"): k W i n , F L = 300 × 0.746 0.93 ≈ 241 k W \mathrm{kW}_{\mathrm{in, FL}} = \frac{300 \times 0.746}{0.93} \approx 241\ \mathrm{kW} kW in , FL ​ = 0.93 300 × 0.746 ​ ≈ 241 kW I F L = 241,000 1.732 × 480 × 0.86 ≈ 337 A I_{\mathrm{FL}} = \frac{241{,}000}{1.732 \times 480 \times 0.86} \approx 337\ \mathrm{A} I FL ​ = 1.732 × 480 × 0.86 241 , 000 ​ ≈ 337 A

312 A is therefore not full load. Trap: treating 300 HP × 0.746 = 224 kW as the electrical demand skips efficiency (input is higher than shaft) and skips the ammeter. Trap: dropping 3 \sqrt{3} 3 ​ and computing 480 × 312 × 0.86 / 1000 ≈ 129 k W 480 \times 312 \times 0.86 / 1000 \approx 129\ \mathrm{kW} 480 × 312 × 0.86/1000 ≈ 129 kW — that is a single-phase shape on a three-phase motor. Trap: dropping PF and reporting 259 kW (that is closer to kVA ). k V A = 3 × V × I 1000 , P F = k W k V A \mathrm{kVA} = \frac{\sqrt{3} \times V \times I}{1000}, \quad \mathrm{PF} = \frac{\mathrm{kW}}{\mathrm{kVA}} kVA = 1000 3 ​ × V × I ​ , PF = kVA kW ​

Power-Factor Correction

Lagging motors make the plant draw more amps than the kW require . Utilities may penalize low PF or bill on kVA. Capacitors supply vars locally . Real kW of the compressor hardly changes; line current and kVA fall as PF rises toward unity. Example: 223 kW at 0.86 PF is 259 kVA . Corrected to 0.95 PF , kVA falls to 223 / 0.95 ≈ 235 k V A 223 / 0.95 \approx 235\ \mathrm{kVA} 223/0.95 ≈ 235 kVA , and current falls in the same ratio ( 0.86 / 0.95 ≈ 0.91 0.86/0.95 \approx 0.91 0.86/0.95 ≈ 0.91 ).

Place and switch capacitors so you do not leave a large capacitor bank on a bus that has gone light — overvoltage and harmonic resonance with VFDs are real. Correction does not replace overloads or breakers, and it does not change the oil-pressure or high-pressure cutouts.

Overloads Versus Short-Circuit Protection

These are two different jobs :

Device What it protects against Time scale Typical location

Overload relay (thermal or electronic) Sustained current above FLA that heats the motor Seconds to minutes (inverse time) Heaters or CTs in the motor leads; N.C. aux in the control ladder

Fuse or circuit breaker (branch-circuit short-circuit and ground-fault protection) Bolted faults and ground faults that would melt conductors Cycles Line side of the starter or VFD

An overload can trip without the breaker opening. A short circuit should open the breaker or fuse long before an overload heater would. Sizing overloads to FLA and breakers to a higher short-circuit rating is normal — it is not a contradiction. Do not "fix" nuisances by installing oversized overload heaters; that burns motors. Do not assume a VFD's electronic thermal overload replaces a mechanical high-pressure cutout .

Machinery-Room Electrical Classification (IIAR 2 — Do Not Invent Division 1)

Anhydrous ammonia's flammable range is about 15–28% by volume (OSHA's commonly cited band). That is a high concentration compared with toxicity (ppm) limits. 25% of LFL is the order of 40,000 ppm when LFL is taken near 16% — the same neighborhood IIAR 2 uses for the upper-detection / compressor-pump shutdown logic. Flammability is real, but it is not "gasoline vapor at the floor under normal operation."

ANSI/IIAR 2 (2014 language Ordinary Location ; 2021 language Unclassified Location — treat them as the same exam idea) does not require a typical ventilated, detected machinery room to be Class I, Division 1 . The design path is:

Provide ammonia detection (IIAR 2 §6.13) and emergency ventilation (IIAR 2 §6.14.7).

Then the machinery room is designated unclassified / ordinary as described in the electrical code.

If emergency ventilation is not provided , the room shall be designated not less than Class I, Division 2, Group D , and electrical equipment must meet that classification.

Electrical design documents must state ordinary/unclassified versus hazardous, and if hazardous, the Class, Division, and Group .

NEC language used with ammonia machinery rooms matches the idea: rooms with adequate mechanical ventilation that runs continuously or starts from detection at not more than 150 ppm may be unclassified . That is how IIAR 2 keeps most machinery-room electrical from being treated as a continuously hazardous classified location . It is not a claim that ammonia cannot burn.

What IIAR 2 does not say: it does not impose a blanket Class I, Division 1 requirement on a code-compliant machinery room. Division 1 would mean ignitable concentrations are expected in normal operation. The ventilation-and-detection package is specifically there so that is not the design assumption.

Ignition control still exists in an unclassified room. IIAR 2 still restricts open flames and hot surfaces in the machinery room. Emergency exhaust fans that handle ammonia are specified with spark-resistant blades in current IIAR 2 ventilation language. Emergency exhaust fan motors in the airstream or in the room are to be totally enclosed (TEFC-type enclosure) and need not be explosion-proof when the room is unclassified because of detection and emergency ventilation. Totally enclosed is not the same listing as explosion-proof Class I equipment. Do not "upgrade" every motor to XP in your head and call it IIAR 2.

E-stop versus fans: refrigerant e-stop de-energizes compressors, refrigerant pumps, and N.C. automatic refrigerant valves. Emergency ventilation is powered so that it is not killed by that e-stop . Classifying the room correctly and keeping the fans running during a leak are the same safety story: dilute and exhaust , rather than pretending every starter is Division 1.

  • Condition Electrical designation (IIAR 2 path)
  • Detection and emergency ventilation provided Unclassified / ordinary
  • Emergency ventilation not provided Not less than Class I, Division 2, Group D
  • Operator assumption "must be Division 1 everywhere" Not an IIAR 2 mandate

Emergency exhaust motor in room/airstream Totally enclosed; not required to be explosion-proof solely because it runs in a leak

Open flames / hot surfaces Still restricted , even if the room is electrically unclassified