Study guide
5.2 CT Calculations & Disinfection Byproducts Compliance
South Carolina Water/Wastewater Operator Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: South Carolina Regulations & Licensing Framework
1.1 SC Environmental Certification Board & Chapter 51 Regulations 1.2 Certification Levels & Experience Requirements 1.3 Facility Classifications & Operator-in-Charge Duties 1.4 Exam Logistics, Scoring & Study Resources
2 Chapter 2: Source Water Characteristics
2.1 Raw Water Sources & Pretreatment 2.2 Groundwater Sources, Wells & GWUDI Determinations 2.3 Watershed Protection & Source Water Contaminants
3 Chapter 3: Water Treatment: Coagulation, Flocculation & Sedimentation
3.1 Coagulation & Flocculation Process Control 3.2 Sedimentation Basins & Clarification
4 Chapter 4: Water Treatment: Filtration
4.1 Granular Media & Membrane Filtration 4.2 Filter Operation, Backwash & Troubleshooting
5 Chapter 5: Water Treatment: Disinfection & Chemical Conditioning
5.1 Chlorination & Chemical Disinfection 5.2 CT Calculations & Disinfection Byproducts Compliance 5.3 Chloramines, Chlorine Dioxide, Ozone & UV 5.4 Corrosion Control & the Lead and Copper Rule 5.5 Fluoridation & Water Softening 5.6 Iron, Manganese, Taste & Odor Control
6 Chapter 6: Water Distribution Systems
6.1 Water Distribution Network Operations & Maintenance 6.2 Cross-Connection Control & Backflow Prevention 6.3 Distribution Hydraulics & Pressure Management 6.4 Pipes, Valves, Hydrants & Appurtenances 6.5 Storage Tanks & Reservoirs 6.6 Water Quality in Distribution: Flushing & Residual Management 6.7 Main Disinfection, Breaks & Repair
7 Chapter 7: Wastewater Collection & Preliminary Treatment
7.1 Wastewater Collection & Preliminary Operations 7.2 Sanitary Sewer Collection System Maintenance 7.3 Lift Station Pumps, Controls & Hydraulics
8 Chapter 8: Wastewater Treatment: Primary & Secondary
8.1 Wastewater Characteristics & Plant Loadings 8.2 Primary Sedimentation & Clarifier Operations 8.3 Activated Sludge Process Control & Operations 8.4 Activated Sludge Troubleshooting 8.5 Aeration Systems & Dissolved Oxygen Control 8.6 Fixed-Film & Lagoon Treatment Systems 8.7 Biological Nutrient Removal & Tertiary Treatment
9 Chapter 9: Wastewater Disinfection, Effluent & Industrial Treatment
9.1 Wastewater Disinfection & Dechlorination 9.2 Effluent Disposal, Reuse & Land Application 9.3 Physical/Chemical Industrial Wastewater Treatment 9.4 Industrial Pretreatment Programs
10 Chapter 10: Solids, Biosolids & Regulatory Permitting
10.1 Sludge Thickening, Digestion & Dewatering 10.2 Biosolids Stabilization & Part 503 Land Application 10.3 Clean Water Act & NPDES Permit Compliance 10.4 Safe Drinking Water Act Compliance & Public Notification
11 Chapter 11: Laboratory Analysis & Quality Control
11.1 Sampling, Preservation & Chain of Custody 11.2 Physical & Chemical Water Quality Analysis 11.3 Wastewater Process Testing & Analytical Methods 11.4 Microbiological Testing & Quality Assurance 11.5 Data Validation, Reporting & Laboratory Certification
12 Chapter 12: Equipment Operation & Maintenance
12.1 Pumps: Types, Curves & Cavitation 12.2 Motors, Drives & Electrical Fundamentals 12.3 Bearings, Seals, Couplings & Lubrication 12.4 Flow Measurement & Process Instrumentation 12.5 Chemical Feed Equipment & Calibration 12.6 SCADA, Controls & Preventive Maintenance Programs
13 Chapter 13: Safety, Security & Administrative Procedures
13.1 Confined Space Entry & Atmospheric Hazards 13.2 Chlorine Gas Safety & Emergency Response 13.3 Lockout/Tagout, PPE, Hazard Communication & Excavation 13.4 Security, Vulnerability Assessment & Emergency Response Planning 13.5 Recordkeeping, Reporting & Administrative Duties
14 Chapter 14: Process Calculations & Hydraulic Math
14.1 Basic Water & Wastewater Math Fundamentals 14.2 Chemical Feed Rate & Dosage Calculations 14.3 Detention Time & Volumetric Flow Calculations 14.4 Removal Efficiency & Process Loading Rates 14.5 Pump Hydraulics & Horsepower Calculations 14.6 Activated Sludge Process Control Math
5.2 CT Calculations & Disinfection Byproducts Compliance
Key Takeaways Explain This Topic AI
CT is calculated as the free disinfectant concentration (C in mg/L) multiplied by the effective contact time (T10 in minutes), where T10 = Theoretical Retention Time × Baffling Factor.
Under the Surface Water Treatment Rule (SWTR), conventional surface water plants must achieve a total of 3-log (99.9%) Giardia lamblia removal/inactivation and 4-log (99.99%) Virus removal/inactivation.
Baffling factors range from 0.1 for unbaffled/mixed basins to 0.7 for superior baffled basins and 1.0 for ideal plug-flow pipelines.
Total Trihalomethanes (TTHMs) have a Maximum Contaminant Level (MCL) of 0.080 mg/L (80 µg/L) and Haloacetic Acids (HAA5) have an MCL of 0.060 mg/L (60 µg/L).
The Stage 2 Disinfection Byproducts Rule enforces compliance based on Locational Running Annual Averages (LRAA) at each individual monitoring site rather than system-wide averages.
Last updated: August 2026
3.3 CT Calculations & Disinfection Byproducts Compliance
Primary disinfection efficacy is validated using the Concentration-Time ( C T CT CT ) concept established under the EPA Surface Water Treatment Rule (SWTR) and enforced by SC DES Regulation 61-58. Concurrently, utilities must balance primary pathogen inactivation against the formation of carcinogenic Disinfection Byproducts (DBPs) regulated under the Stage 1 and Stage 2 Disinfection Byproducts Rules.
The Concentration-Time ( C T CT CT ) Concept
The C T CT CT factor measures the total chemical disinfection dosage applied to water, defined as the product of the free disinfectant residual concentration ( C C C ) and the effective contact time ( T 10 T_{10} T 10 ): C T = C × T 10 CT = C \times T_{10} CT = C × T 10
Where:
C C C = Free disinfectant residual concentration measured at the outlet of the contact basin (mg/L).
T 10 T_{10} T 10 = The contact time (in minutes) required for 10% of the water volume to pass through the contact tank ( 90 % 90\% 90% of the water remains in the basin for at least T 10 T_{10} T 10 ).
Hydraulic Detention Time & Baffling Factors ( B F BF BF )
Theoretical hydraulic detention time ( T theoretical T_{\text{theoretical}} T theoretical ) assumes perfect mixing, calculated as: T theoretical = Basin Volume (gallons) Plant Peak Flow Rate (gpm) = V Q T_{\text{theoretical}} = \frac{\text{Basin Volume (gallons)}}{\text{Plant Peak Flow Rate (gpm)}} = \frac{V}{Q} T theoretical = Plant Peak Flow Rate (gpm) Basin Volume (gallons) = Q V
However, real-world tanks suffer from hydraulic short-circuiting and dead zones. To determine actual effective contact time ( T 10 T_{10} T 10 ), T theoretical T_{\text{theoretical}} T theoretical must be multiplied by an empirically determined Baffling Factor ( B F BF BF ) : T 10 = T theoretical × B F T_{10} = T_{\text{theoretical}} \times BF T 10 = T theoretical × BF
Baffling Classification Baffling Factor ( B F BF BF ) Basin Configuration & Internal Baffling Description
Unbaffled / Mixed 0.1 Single unbaffled inlet/outlet; high short-circuiting; mixed circular tanks.
Poor Baffling 0.3 Single inlet and outlet with minimal internal flow-directing walls.
Average Baffling 0.5 Baffled basin with several internal cross-walls or turning vanes.
Superior Baffling 0.7 Serpentine baffling with high length-to-width ratio; perforated distribution diffusers.
Perfect Plug Flow 1.0 Pipeline flow (unobstructed long pipelines without back-mixing).
SWTR Pathogen Log-Inactivation Requirements
Under the SWTR, surface water treatment plants must demonstrate cumulative reduction (removal plus inactivation) of target pathogens:
Giardia lamblia : 3-log (99.9%) reduction minimum.
Viruses : 4-log (99.99%) reduction minimum.
Cryptosporidium : 2-log to 3.5-log (99% to 99.97%) reduction under Long Term 2 Enhanced SWTR (LT2ESWTR) based on raw water source bin classification.
Credit Allocation between Filtration and Disinfection
Well-operated surface water treatment plants receive default log-reduction credits for physical filtration when meeting effluent turbidity standards:
Treatment Step Giardia Credit Virus Credit Cryptosporidium Credit
Conventional Filtration ( CFE ≤ 0.3 NTU \text{CFE} \le 0.3\text{ NTU} CFE ≤ 0.3 NTU ) 2.5-log (99.7%) 2.0-log (99.0%) 2.0-log (99.0%)
Direct Filtration ( CFE ≤ 0.3 NTU \text{CFE} \le 0.3\text{ NTU} CFE ≤ 0.3 NTU ) 2.0-log (99.0%) 1.0-log (90.0%) 2.0-log (99.0%)
- Required Chemical Disinfection 0.5-log (68.4%) 2.0-log (99.0%) Assigned by LT2 Bin / UV
- Step-by-Step Worked C T CT CT Calculation Example
Problem : A South Carolina water treatment plant treats a peak flow of 3 , 500 gpm 3,500\text{ gpm} 3 , 500 gpm ( Q Q Q ). The clearwell contact basin holds 210 , 000 gallons 210,000\text{ gallons} 210 , 000 gallons ( V V V ) and features superior serpentine baffling ( B F = 0.7 BF = 0.7 BF = 0.7 ). The free chlorine residual measured at the clearwell discharge is 1.6 mg/L 1.6\text{ mg/L} 1.6 mg/L at a water temperature of 15 ∘ C 15^\circ\text{C} 1 5 ∘ C and pH 7.5 7.5 7.5 . Determine whether the system satisfies the required 0.5-log Giardia inactivation credit, given that EPA tables state the required C T required CT_{\text{required}} C T required for 0.5-log Giardia at these conditions is 34 mg ⋅ min/L 34\text{ mg}\cdot\text{min/L} 34 mg ⋅ min/L .
Solution:
Calculate Theoretical Detention Time ( T theoretical T_{\text{theoretical}} T theoretical ) : T theoretical = V Q = 210 , 000 gal 3 , 500 gpm = 60.0 minutes T_{\text{theoretical}} = \frac{V}{Q} = \frac{210,000\text{ gal}}{3,500\text{ gpm}} = 60.0\text{ minutes} T theoretical = Q V = 3 , 500 gpm 210 , 000 gal = 60.0 minutes
Calculate Effective Contact Time ( T 10 T_{10} T 10 ) : T 10 = T theoretical × B F = 60.0 min × 0.7 = 42.0 minutes T_{10} = T_{\text{theoretical}} \times BF = 60.0\text{ min} \times 0.7 = 42.0\text{ minutes} T 10 = T theoretical × BF = 60.0 min × 0.7 = 42.0 minutes
Calculate Actual Achieved C T CT CT ( C T calculated CT_{\text{calculated}} C T calculated ) : C T calculated = C × T 10 = 1.6 mg/L × 42.0 min = 67.2 mg ⋅ min/L CT_{\text{calculated}} = C \times T_{10} = 1.6\text{ mg/L} \times 42.0\text{ min} = 67.2\text{ mg}\cdot\text{min/L} C T calculated = C × T 10 = 1.6 mg/L × 42.0 min = 67.2 mg ⋅ min/L
Calculate C T CT CT Compliance Ratio : Ratio = C T calculated C T required = 67.2 34.0 = 1.98 \text{Ratio} = \frac{CT_{\text{calculated}}}{CT_{\text{required}}} = \frac{67.2}{34.0} = 1.98 Ratio = C T required C T calculated = 34.0 67.2 = 1.98
Conclusion : Because the C T CT CT ratio is 1.98 ≥ 1.0 1.98 \ge 1.0 1.98 ≥ 1.0 , the plant comfortably satisfies DES and SWTR primary disinfection requirements for 0.5-log Giardia inactivation.
Disinfection Byproducts (DBPs) & Precursor Chemistry
When free chlorine or strong oxidants react with naturally occurring organic matter (NOM)—measured as Total Organic Carbon (TOC) —and bromide ions ( Br − \text{Br}^- Br − ) in raw water, chemical disinfectants form hazardous carcinogenic Disinfection Byproducts (DBPs) .
Regulated DBP Classes & Maximum Contaminant Levels (MCLs)
DBP Chemical Family Regulated Species Included Maximum Contaminant Level (MCL) Primary Health Risk
Total Trihalomethanes (TTHMs) Chloroform ( CHCl 3 \text{CHCl}_3 CHCl 3 ), Bromoform ( CHBr 3 \text{CHBr}_3 CHBr 3 ), Bromodichloromethane ( CHBrCl 2 \text{CHBrCl}_2 CHBrCl 2 ), Dibromochloromethane ( CHBr 2 Cl \text{CHBr}_2\text{Cl} CHBr 2 Cl ) 0.080 mg/L (80 µg/L) Bladder cancer, liver/kidney damage, central nervous system effects
Haloacetic Acids (HAA5) Monochloroacetic, Dichloroacetic, Trichloroacetic, Monobromoacetic, Dibromoacetic acids 0.060 mg/L (60 µg/L) Cancer risk, reproductive and developmental toxicity
Chlorite ( ClO 2 − \text{ClO}_2^- ClO 2 − ) Inorganic byproduct of Chlorine Dioxide ( ClO 2 \text{ClO}_2 ClO 2 ) use 1.0 mg/L Anemia, nervous system effects in infants
Bromate ( BrO 3 − \text{BrO}_3^- BrO 3 − ) Formed when Ozone ( O 3 \text{O}_3 O 3 ) reacts with bromide ( Br − \text{Br}^- Br − ) 0.010 mg/L (10 µg/L) High carcinogenic potential
Stage 1 vs. Stage 2 DBPR Compliance Rules
Stage 1 DBPR : Allowed utilities to determine compliance by averaging DBP concentrations across the entire distribution system using a System-Wide Running Annual Average (RAA) . This allowed low DBP levels in short-pipe areas to mask dangerous DBP spikes in dead-end mains.
Stage 2 DBPR : Replaced system-wide averaging with the Locational Running Annual Average (LRAA) . Compliance is calculated independently at each specific sampling location based on the average of the current quarter and the previous three quarters. Every individual site must maintain an LRAA ≤ MCL \text{LRAA} \le \text{MCL} LRAA ≤ MCL .
Operational Evaluation Levels (OEL)
To prevent Stage 2 LRAA violations, utilities monitor the Operational Evaluation Level (OEL) each quarter for TTHM and HAA5 at every sampling site: OEL = Q 1 + Q 2 + ( 2 × Q current ) 4 \text{OEL} = \frac{Q_1 + Q_2 + (2 \times Q_{\text{current}})}{4} OEL = 4 Q 1 + Q 2 + ( 2 × Q current )
Where Q 1 Q_1 Q 1 and Q 2 Q_2 Q 2 are the sample results from two quarters prior, and Q current Q_{\text{current}} Q current is the current quarter's result. If the calculated OEL \text{OEL} OEL exceeds 0.080 mg/L 0.080\text{ mg/L} 0.080 mg/L for TTHM or 0.060 mg/L 0.060\text{ mg/L} 0.060 mg/L for HAA5, the utility must conduct an operational evaluation study and submit a written report to SC DES within 90 days.
DBP Control & Mitigation Strategies
Enhanced Coagulation : Lowering raw water pH to 5.5–6.5 using acid or higher coagulant doses (alum/ferric) to precipitate TOC before chlorine application.
Alternative Disinfectants : Utilizing UV light or chlorine dioxide for primary disinfection, and switching from free chlorine to chloramines for secondary distribution protection.
Distribution System Management : Routine flushing of dead-end mains, installation of storage tank mixers, and tank aeration to strip volatile TTHMs.