13.3 True, Apparent & Reactive Power
CAAS SAR-66 AML Module 3 — Electrical Fundamentals Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 Knowledge Levels & Study Approach for Module 3
2 Electron Theory & Static Electricity
2.1 Electron Theory & Atomic Structure 2.2 Conductors, Semiconductors & Insulators 2.3 Static Electricity, Coulomb's Law & Conduction
3 Terminology & Generation of Electricity
3.1 Electrical Terminology 3.2 Generation of Electricity
4 DC Sources of Electricity
4.1 Primary & Secondary Cells 4.2 Lead-Acid & Nickel-Cadmium Batteries 4.3 Series/Parallel Cells, Internal Resistance, Thermocouples & Photocells
5 DC Circuits
5.1 Ohm's Law 5.2 Kirchhoff's Voltage & Current Laws 5.3 Series/Parallel Networks & Supply Internal Resistance
6 Resistance & Resistors
6.1 Resistivity & Factors Affecting Resistance 6.2 Resistor Colour Code, Tolerance & Preferred Values 6.3 Series/Parallel Resistors, Potentiometers & Rheostats 6.4 Wheatstone Bridge, Thermistors & Temperature Coefficient
7 Power, Work & Energy
7.1 Power, Work & Energy Concepts 7.2 Power Dissipation & Calculations
8 Capacitance & Capacitors
8.1 Capacitor Operation & Factors Affecting Capacitance 8.2 Series/Parallel Capacitors & Types 8.3 RC Time Constants, Energy Storage & Testing
9 Magnetism
9.1 Theory of Magnetism & Magnetic Materials 9.2 Electromagnets & Hand Rules 9.3 MMF, Flux Density, Permeability, Hysteresis & Eddy Currents
10 Inductance & Inductors
10.1 Faraday's Law & Induced Voltage 10.2 Self & Mutual Inductance, Lenz's Law 10.3 Back EMF, Saturation & Inductor Applications
11 DC Motor/Generator Theory
11.1 Basic Motor & Generator Theory 11.2 DC Generators — Construction & Operation 11.3 DC Motors — Series, Shunt, Compound & Starter-Generators
12 AC Theory
12.1 Sinusoidal Waveforms — Phase, Period, Frequency 12.2 Peak, Average, RMS Values & Calculations 12.3 Non-Sinusoidal Waves & Single/Three-Phase Principles
13 R, L & C Circuits
13.1 Phase Relationships in R, L, C Circuits 13.2 Impedance, Phase Angle & Power Factor 13.3 True, Apparent & Reactive Power
14 Transformers
14.1 Transformer Construction & Operation 14.2 Losses, Efficiency, Load/No-Load & Turns Ratio 14.3 Three-Phase Transformers & Autotransformers
15 Filters & AC Generators
15.1 Filters — Low Pass, High Pass, Band Pass, Band Stop 15.2 AC Generator Principles & Construction 15.3 Star/Delta Connections & Permanent Magnet Generators
16 AC Motors
16.1 Synchronous & Induction Motors 16.2 Speed Control, Direction & Rotating Field Methods
13.3 True, Apparent & Reactive Power
Key Takeaways Explain This Topic AI
True (real/active) power P = VI cos θ = I²R is measured in watts (W) and is the average power dissipated
Apparent power S = VI is measured in volt-amperes (VA); S² = P² + Q² on the power triangle
Reactive power Q = VI sin θ is measured in volt-amperes reactive (VAR); it represents energy shuttled by L and C
Ideal inductors and capacitors dissipate no average true power; resistance alone accounts for P in the ideal RLC model
- Power factor pf = P/S = cos θ links the power triangle to the impedance triangle (similar geometry)
- Last updated: July 2026
13.3 True, Apparent & Reactive Power
Quick Answer: True power P = VI cos θ (watts) — average energy converted per second, usually to heat in R. Apparent power S = VI (VA). Reactive power Q = VI sin θ (VAR). They form a power triangle with pf = P/S = cos θ . Ideal L and C exchange energy with the source but average P = 0 ; only R dissipates true power in the ideal model.
Impedance and power factor (§13.2) tell you the angle between V and I. Module 3 topic 3.14 finishes by naming the three power quantities that angle creates—and by stating clearly what dissipates energy in R, L, and C circuits.
Why Three “Powers”?
On DC, P = VI is unambiguous. On AC with phase shift, the product of RMS voltage and RMS current is not always the average heating power. Part of the VI product may represent energy that flows into magnetic or electric fields on one quarter-cycle and returns on the next. Module 3 therefore splits:
- Name Symbol Formula (RMS sine) Unit
- True / real / active power P P = VI cos θ = I²R = V²/R (resistive part) watt (W)
- Apparent power S S = VI volt-ampere (VA)
- Reactive power Q Q = VI sin θ volt-ampere reactive (VAR)
Also: P = S cos θ , Q = S sin θ , and pf = P / S .
True Power (P)
True power is the average power over a cycle—the rate at which electrical energy is converted irreversibly (heat in resistors, mechanical work in motors after accounting for losses, and so on).
For any linear sine circuit:
P = V_RMS × I_RMS × cos θ
In the series RLC idealisation, only the resistor dissipates average power:
P = I_RMS² × R
Worked example 1 — from V, I, pf. V = 115 V, I = 4.0 A, pf = 0.8 lagging.
P = 115 × 4.0 × 0.8 = 368 W .
Worked example 2 — from I and R. Series circuit, I = 2.5 A, R = 40 Ω.
P = (2.5)² × 40 = 6.25 × 40 = 250 W .
Frequency does not appear explicitly once I and R are known—but frequency shaped Z and therefore I.
Apparent Power (S)
Apparent power is the product of RMS voltage and RMS current as if you ignored phase:
S = V_RMS × I_RMS
Generators, transformers, and cable ratings are often stated in VA or kVA because heating in windings and wiring depends on current magnitude, and insulation stress depends on voltage, regardless of pf. A load drawing 10 A from 115 V needs 1150 VA of apparent capacity even if pf is only 0.5 and true power is 575 W.
Worked example 3 — S then P. V = 115 V, I = 2.5 A, θ such that pf = 0.6.
S = 115 × 2.5 = 287.5 VA .
P = 287.5 × 0.6 = 172.5 W .
Reactive Power (Q)
Reactive power quantifies the amplitude of the energy oscillation associated with inductance and capacitance:
Q = V_RMS × I_RMS × sin θ
- Sign convention (common) Meaning
- Q > 0 (inductive / lagging) Net magnetic energy storage behaviour
- Q < 0 (capacitive / leading) Net electric energy storage behaviour
- Q = 0 θ = 0 — no net reactive power
Worked example 4 — Q from S and θ. S = 287.5 VA, pf = 0.6 → cos θ = 0.6 → sin θ = 0.8 (because sin² + cos² = 1).
Q = 287.5 × 0.8 = 230 VAR (lagging if the load is inductive).
Worked example 5 — 400 Hz inductive branch. Pure inductor, V = 115 V, X_L = 46 Ω at 400 Hz.
I = 115 / 46 = 2.5 A; θ = 90°; cos θ = 0; sin θ = 1.
P = 0 W ; S = 115 × 2.5 = 287.5 VA ; Q = 287.5 VAR .
The Power Triangle
Draw P along the horizontal (in-phase) axis and Q along the vertical (quadrature) axis. The hypotenuse is S :
- S² = P² + Q²
- tan θ = Q / P
- cos θ = P / S
This triangle is similar to the impedance triangle (R, X, Z): multiply the impedance triangle by I² (or by I and use V drops) and you recover the power triangle.
- Impedance triangle Power triangle
- R P = I²R
- X Q = I²X (with sign)
- Z S = I²Z = VI
- θ same θ
Worked example 6 — close the triangle. P = 300 W, Q = 400 VAR.
S = √(300² + 400²) = √(90000 + 160000) = √250000 = 500 VA .
pf = 300 / 500 = 0.6 .
Worked example 7 — aircraft numeric. Series R = 30 Ω, X = 40 Ω, V = 115 V at 400 Hz (Z = 50 Ω from §13.2 pattern).
I = 115 / 50 = 2.3 A.
P = I²R = (2.3)² × 30 ≈ 5.29 × 30 ≈ 159 W .
Q = I²X ≈ 5.29 × 40 ≈ 212 VAR .
S = VI = 115 × 2.3 = 264.5 VA .
Check: √(159² + 212²) ≈ √(25281 + 44944) ≈ √70225 ≈ 265 VA ✓.
pf = 30/50 = 0.6 lagging .
Dissipation in R, L, and C Circuits
Module 3 expects a clear energy story—not only formulae.
Pure resistance
Current through R produces Joule heating I²R every instant (averaged over the cycle for AC). Energy leaves the electrical system as heat. P > 0 , Q = 0 , S = P , pf = 1 .
Pure inductance (ideal)
Energy is stored in the magnetic field as current rises and returned to the source as current falls. Over a full cycle the average energy transfer is zero: P = 0 , Q = S = VI , pf = 0 lagging . A real coil has winding resistance, so a small true power appears as copper (and core) loss—modelled by adding R in series with X_L.
Pure capacitance (ideal)
Energy is stored in the electric field as voltage rises and returned as voltage falls. Average P = 0 , Q = S (leading), pf = 0 leading . Real capacitors have small dielectric/ESR losses—again a small P.
Combined RLC
- Element Ideal average true power
- R P = I²R (all of the circuit’s true power in the ideal series model)
- L 0 (only Q contribution, magnetic)
- C 0 (only Q contribution, electric; opposite sign to L)
If X_L and X_C both exist, their reactive powers oppose; net Q = I²(X_L − X_C) in the series model. At resonance net Q → 0 and S → P.
Worked example 8 — where the watts go. Series RLC at 400 Hz: I = 3 A, R = 20 Ω, X_L = 50 Ω, X_C = 30 Ω.
P = 9 × 20 = 180 W (all in R).
Q_net = 9 × (50 − 30) = 180 VAR inductive.
S = √(180² + 180²) = 180√2 ≈ 255 VA .
Ideal L and C still contribute zero to the 180 W; they only shape the 180 VAR net.
Aircraft Maintenance Angle
Low power factor means large current (and large S) for a given true power—more I²R loss in feeders, larger generator loading in VA, hotter cables. Capacitive correction and load management appear in later systems topics; Module 3’s job is to compute P, S, Q and state that watts live in resistance , while L and C shuttle VARs .
Section Synthesis
- Symbol Name Unit Ideal role
- P True power W Dissipation / real work — from R
- S Apparent power VA VI product; equipment rating language
- Q Reactive power VAR L/C energy exchange
- Triangle S² = P² + Q² — Same θ as impedance triangle
Master P = VI cos θ, S = VI, Q = VI sin θ, the triangle check S² = P² + Q², and the dissipation rule (ideal L and C: P = 0). That closes syllabus 3.14 and prepares transformer loading language in topic 3.15 .