Study guide

14.2 Losses, Efficiency, Load/No-Load & Turns Ratio

CAAS SAR-66 AML Module 3 — Electrical Fundamentals Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Knowledge Levels & Study Approach for Module 3

2 Electron Theory & Static Electricity

2.1 Electron Theory & Atomic Structure 2.2 Conductors, Semiconductors & Insulators 2.3 Static Electricity, Coulomb's Law & Conduction

3 Terminology & Generation of Electricity

3.1 Electrical Terminology 3.2 Generation of Electricity

4 DC Sources of Electricity

4.1 Primary & Secondary Cells 4.2 Lead-Acid & Nickel-Cadmium Batteries 4.3 Series/Parallel Cells, Internal Resistance, Thermocouples & Photocells

5 DC Circuits

5.1 Ohm's Law 5.2 Kirchhoff's Voltage & Current Laws 5.3 Series/Parallel Networks & Supply Internal Resistance

6 Resistance & Resistors

6.1 Resistivity & Factors Affecting Resistance 6.2 Resistor Colour Code, Tolerance & Preferred Values 6.3 Series/Parallel Resistors, Potentiometers & Rheostats 6.4 Wheatstone Bridge, Thermistors & Temperature Coefficient

7 Power, Work & Energy

7.1 Power, Work & Energy Concepts 7.2 Power Dissipation & Calculations

8 Capacitance & Capacitors

8.1 Capacitor Operation & Factors Affecting Capacitance 8.2 Series/Parallel Capacitors & Types 8.3 RC Time Constants, Energy Storage & Testing

9 Magnetism

9.1 Theory of Magnetism & Magnetic Materials 9.2 Electromagnets & Hand Rules 9.3 MMF, Flux Density, Permeability, Hysteresis & Eddy Currents

10 Inductance & Inductors

10.1 Faraday's Law & Induced Voltage 10.2 Self & Mutual Inductance, Lenz's Law 10.3 Back EMF, Saturation & Inductor Applications

11 DC Motor/Generator Theory

11.1 Basic Motor & Generator Theory 11.2 DC Generators — Construction & Operation 11.3 DC Motors — Series, Shunt, Compound & Starter-Generators

12 AC Theory

12.1 Sinusoidal Waveforms — Phase, Period, Frequency 12.2 Peak, Average, RMS Values & Calculations 12.3 Non-Sinusoidal Waves & Single/Three-Phase Principles

13 R, L & C Circuits

13.1 Phase Relationships in R, L, C Circuits 13.2 Impedance, Phase Angle & Power Factor 13.3 True, Apparent & Reactive Power

14 Transformers

14.1 Transformer Construction & Operation 14.2 Losses, Efficiency, Load/No-Load & Turns Ratio 14.3 Three-Phase Transformers & Autotransformers

15 Filters & AC Generators

15.1 Filters — Low Pass, High Pass, Band Pass, Band Stop 15.2 AC Generator Principles & Construction 15.3 Star/Delta Connections & Permanent Magnet Generators

16 AC Motors

16.1 Synchronous & Induction Motors 16.2 Speed Control, Direction & Rotating Field Methods

14.2 Losses, Efficiency, Load/No-Load & Turns Ratio

Key Takeaways Explain This Topic AI

Ideal turns-ratio law: Vp/Vs = Np/Ns = Is/Ip; for ideal power, Vp × Ip = Vs × Is

Copper (I²R) losses occur in windings and rise with load current; iron/core losses are hysteresis plus eddy currents and are essentially present whenever the core is energised

Eddy currents are reduced by laminated cores and higher-resistivity silicon steel; hysteresis is reduced by magnetically soft core material (narrow loop)

No-load primary current is mainly magnetising plus a small core-loss component; load current rises when the secondary delivers power

  • Efficiency η = Pout / Pin × 100% = Pout / (Pout + losses) × 100%
  • Last updated: July 2026

14.2 Losses, Efficiency, Load/No-Load & Turns Ratio

Quick Answer: Vp/Vs = Np/Ns = Is/Ip . Ideal power: Vp Ip = Vs Is . Copper losses = I²R in windings (load-dependent). Iron losses = hysteresis + eddy in the core (present when energised). η = Pout/(Pout+losses) .

Section 14.1 built the physical picture. Syllabus 3.15 expects fluent turns-ratio arithmetic , clear separation of copper vs iron losses , and the difference between no-load and loaded operation — all staples of CAAS Module 3 MCQs.

Turns Ratio — Voltage, Current, Power

Define:

  • Symbol Meaning
  • Vp, Vs Primary / secondary RMS voltages
  • Ip, Is Primary / secondary RMS currents
  • Np, Ns Primary / secondary turns
  • a = Np/Ns Turns ratio (primary to secondary)

Ideal transformer:

Vp / Vs = Np / Ns = Is / Ip

Equivalently:

Vs = Vp × (Ns / Np) and Ip = Is × (Ns / Np) or Is = Ip × (Np / Ns)

Voltage ratio equals turns ratio; current ratio is the inverse . Step-down voltage → step-up current (and vice versa) so that, ideally:

Pin = Pout → Vp × Ip = Vs × Is

(assuming unity power factor on both sides for the basic Module 3 model).

Worked example 1 — step-down voltage

Aircraft bus Vp = 115 V , turns Np : Ns = 5 : 1 .

Vs = 115 × (1/5) = 23 V .

Worked example 2 — primary current from secondary load

Same transformer; secondary load draws Is = 10 A (ideal).

Ip = Is × (Ns/Np) = 10 × (1/5) = 2 A .

Check power: Pin = 115 × 2 = 230 W; Pout = 23 × 10 = 230 W.

Worked example 3 — find turns

Instrument transformer: Vp = 115 V, Vs = 28 V, Np = 960 turns. Find Ns.

Ns = Np × (Vs/Vp) = 960 × (28/115) ≈ 233.7 → 234 turns (nearest whole turn).

Worked example 4 — step-up

Np = 200, Ns = 800, Vp = 28 V.

Vs = 28 × (800/200) = 112 V . If Is = 0.5 A, Ip = 0.5 × (800/200) = 2 A .

Impedance reflection (recognition-level)

Load Zs on the secondary appears at the primary approximately as:

Zp ≈ Zs × (Np/Ns)²

Module 3 may only require recognising that impedance scales with the square of the turns ratio — useful in coupling/matching discussions.

  • Load vs No-Load
  • No-load (secondary open)

Secondary current Is ≈ 0 (no load power).

Primary draws no-load current I0 : magnetising component (creates flux) + small core-loss component.

I0 is typically a few percent of full-load primary current on efficient units.

Core flux is set mainly by applied Vp and frequency (V/f roughly related to flux).

Iron losses continue whenever the primary is energised at rated voltage/frequency.

Copper losses in the secondary are zero; primary copper loss is small (I0² Rp).

On load

Secondary delivers Is to the load.

Secondary ampere-turns are opposed by additional primary ampere-turns → Ip rises .

Ideal relation Ip ≈ Is × (Ns/Np) plus the smaller magnetising component.

Copper losses in both windings increase roughly with the square of current.

Terminal voltage Vs may droop slightly on a real transformer because of winding resistance and leakage reactance (voltage regulation) — ideal maths ignore this unless the stem gives regulation data.

  • Condition Is Ip (approx.) Dominant notes
  • No-load ≈ 0 I0 (small) Iron loss present; little copper loss
  • Loaded Load value ≈ Is × Ns/Np (+ I0) Copper loss rises; iron loss still present
  • Transformer Losses

Real efficiency is less than 100%. Loss categories Module 3 emphasises:

1. Copper losses (winding / I²R losses)

Pcu = Ip² Rp + Is² Rs (or treated as a combined full-load copper-loss figure).

Cause: resistance of copper (or aluminium) windings. Mitigation: larger conductor cross-section, high-conductivity copper, shorter mean turn length. High-current (usually LV) windings need thicker wire.

Copper loss is load-dependent — approximately proportional to load current squared.

2. Iron / core losses

Present whenever the core is magnetised by rated AC voltage (approximately constant with load in the basic model if V and f stay fixed).

(a) Hysteresis loss — energy spent reorienting magnetic domains each cycle; area of the B–H loop each second. Worse at higher frequency and with “harder” magnetic materials. Mitigation: soft silicon steel with a narrow hysteresis loop (low coercivity).

(b) Eddy-current loss — circulating currents induced in the conducting core by alternating flux; heat as I²R inside the iron. Mitigation: thin insulated laminations parallel to flux; silicon to raise core resistivity. Solid cores are unacceptable for AC power transformers.

3. Flux leakage (coupling imperfection)

Some primary flux fails to link the secondary (and vice versa). Effects: leakage inductance, voltage drop under load, slightly less than ideal coupling. Mitigation: shell-type cores, interleaved/concentric windings, short leakage paths.

Overcoming / reducing losses — exam table

  • Loss Overcome / reduced by
  • Copper Thicker / better conductors; good cooling
  • Eddy Laminations + silicon steel resistivity
  • Hysteresis Soft magnetic core material, narrow loop
  • Leakage Shell-type / interleaved winding layout
  • Efficiency
  • η = (Pout / Pin) × 100%
  • Pin = Pout + Pcu + Piron (+ other small losses)

So:

η = Pout / (Pout + losses) × 100%

Aircraft transformers often exceed ~95% at sensible loads; Module 3 still expects you to compute from given loss watts.

Worked example 5 — efficiency

Rated output 2500 W (unity pf). Copper loss 45 W , iron loss 35 W .

Total losses = 80 W.

Pin = 2500 + 80 = 2580 W .

η = 2500/2580 × 100% ≈ 96.9% .

Worked example 6 — find Pout from η

Pin = 1200 W, η = 96%.

Pout = 0.96 × 1200 = 1152 W . Losses = 48 W.

Worked example 7 — ideal current then add losses (concept)

Ideal Vp=115 V, Vs=23 V, Is=10 A → Ip=2 A, Pout=230 W. If total losses at that load are 10 W, Pin=240 W, η=230/240≈ 95.8% . Do not use ideal Ip alone when a stem already gives Pin or losses.

Power Transfer Recap

Ideal: energy conserved magnetically — voltage up, current down (or reverse).

Real: a few percent becomes heat (copper + iron).

kVA rating is based on voltage × current capability (heating/insulation), not on a guaranteed wattage at any power factor.

Common Traps

Using Vp/Vs = Ip/Is (forgetting current is inverse).

Calling laminations a fix for hysteresis (they primarily cut eddy paths; soft steel fixes hysteresis).

Saying iron loss is zero at no-load (opposite: iron loss continues; copper is minimal).

Mixing peak and RMS in turns-ratio arithmetic — use consistent RMS nameplate values.

Drill Vp/Vs = Np/Ns = Is/Ip and the copper/iron mitigation table until both are automatic. Section 14.3 extends the same ideas to three-phase banks and autotransformers.