Study guide

14.3 Three-Phase Transformers & Autotransformers

CAAS SAR-66 AML Module 3 — Electrical Fundamentals Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Knowledge Levels & Study Approach for Module 3

2 Electron Theory & Static Electricity

2.1 Electron Theory & Atomic Structure 2.2 Conductors, Semiconductors & Insulators 2.3 Static Electricity, Coulomb's Law & Conduction

3 Terminology & Generation of Electricity

3.1 Electrical Terminology 3.2 Generation of Electricity

4 DC Sources of Electricity

4.1 Primary & Secondary Cells 4.2 Lead-Acid & Nickel-Cadmium Batteries 4.3 Series/Parallel Cells, Internal Resistance, Thermocouples & Photocells

5 DC Circuits

5.1 Ohm's Law 5.2 Kirchhoff's Voltage & Current Laws 5.3 Series/Parallel Networks & Supply Internal Resistance

6 Resistance & Resistors

6.1 Resistivity & Factors Affecting Resistance 6.2 Resistor Colour Code, Tolerance & Preferred Values 6.3 Series/Parallel Resistors, Potentiometers & Rheostats 6.4 Wheatstone Bridge, Thermistors & Temperature Coefficient

7 Power, Work & Energy

7.1 Power, Work & Energy Concepts 7.2 Power Dissipation & Calculations

8 Capacitance & Capacitors

8.1 Capacitor Operation & Factors Affecting Capacitance 8.2 Series/Parallel Capacitors & Types 8.3 RC Time Constants, Energy Storage & Testing

9 Magnetism

9.1 Theory of Magnetism & Magnetic Materials 9.2 Electromagnets & Hand Rules 9.3 MMF, Flux Density, Permeability, Hysteresis & Eddy Currents

10 Inductance & Inductors

10.1 Faraday's Law & Induced Voltage 10.2 Self & Mutual Inductance, Lenz's Law 10.3 Back EMF, Saturation & Inductor Applications

11 DC Motor/Generator Theory

11.1 Basic Motor & Generator Theory 11.2 DC Generators — Construction & Operation 11.3 DC Motors — Series, Shunt, Compound & Starter-Generators

12 AC Theory

12.1 Sinusoidal Waveforms — Phase, Period, Frequency 12.2 Peak, Average, RMS Values & Calculations 12.3 Non-Sinusoidal Waves & Single/Three-Phase Principles

13 R, L & C Circuits

13.1 Phase Relationships in R, L, C Circuits 13.2 Impedance, Phase Angle & Power Factor 13.3 True, Apparent & Reactive Power

14 Transformers

14.1 Transformer Construction & Operation 14.2 Losses, Efficiency, Load/No-Load & Turns Ratio 14.3 Three-Phase Transformers & Autotransformers

15 Filters & AC Generators

15.1 Filters — Low Pass, High Pass, Band Pass, Band Stop 15.2 AC Generator Principles & Construction 15.3 Star/Delta Connections & Permanent Magnet Generators

16 AC Motors

16.1 Synchronous & Induction Motors 16.2 Speed Control, Direction & Rotating Field Methods

14.3 Three-Phase Transformers & Autotransformers

Key Takeaways Explain This Topic AI

Three-phase transformers (or three single-phase units) transform balanced three-phase systems; line and phase voltages/currents depend on star (wye) vs delta connection

In star: VL = √3 Vph and IL = Iph; in delta: VL = Vph and IL = √3 Iph

Three-phase true power for balanced unity-pf loads: P = √3 VL IL (or 3 Vph Iph)

An autotransformer uses one tapped winding shared by primary and secondary — lighter and often more efficient, but without galvanic isolation

Autotransformer failure modes can impress full primary voltage on the secondary; isolation transformers remain preferred where separation is required

Last updated: July 2026

14.3 Three-Phase Transformers & Autotransformers

Quick Answer: Three-phase banks use star or delta connections — remember √3 factors for line vs phase. Balanced power P = √3 VL IL (unity pf). An autotransformer shares one winding (weight save, no isolation).

Sections 14.1–14.2 treated the single-phase two-winding unit. Syllabus 3.15 also requires three-phase transformer relationships and the special case of the autotransformer — both appear in aircraft and ground support equipment.

Three-Phase Transformer Arrangements

A three-phase transformer may be:

Three separate single-phase transformers connected in a three-phase bank, or

A three-limb (or five-limb) three-phase core with three primary and three secondary windings on a common magnetic structure.

Primary and secondary sides are each connected in star (wye, Y) or delta (Δ) . Combinations include Y–Y, Δ–Δ, Y–Δ, Δ–Y. Each combination sets the relationship between line quantities (measured between lines) and phase quantities (across one winding).

Star (wye) connection — per side

  • Relation Formula
  • Line voltage vs phase voltage VL = √3 Vph
  • Line current vs phase current IL = Iph

Each winding sees phase voltage ; line-to-line is higher by √3. Neutral may be available at the star point for line-to-neutral loads (e.g., 115 V from 200 V line-to-line class systems — exact aircraft figures follow the specific system).

Delta connection — per side

  • Relation Formula
  • Line voltage vs phase voltage VL = Vph
  • Line current vs phase current IL = √3 Iph

Each winding sees full line voltage ; line current is √3 times winding (phase) current because line current is the phasor combination of two winding currents.

Memory aid

Star: voltage gets the √3 (line > phase); currents equal.

Delta: current gets the √3 (line > phase); voltages equal.

Worked example 1 — star secondary. Balanced star secondary with Vph = 115 V. Line voltage VL = 115 × √3 ≈ 199 V (often called ~200 V class). If each phase winding current Iph = 10 A, then IL = 10 A .

Worked example 2 — delta secondary. Same Vph = 115 V in delta → VL = 115 V . If Iph = 10 A, IL = 10 × √3 ≈ 17.3 A .

Three-Phase Power

For a balanced three-phase load at unity power factor:

P = √3 × VL × IL

Also:

P = 3 × Vph × Iph

(with Vph, Iph the phase values of that side). At power factor cos φ:

P = √3 VL IL cos φ

Module 3 often uses unity pf unless stated.

Worked example 3 — power. VL = 200 V, IL = 10 A, unity pf.

P = √3 × 200 × 10 ≈ 3464 W ≈ 3.46 kW .

Worked example 4 — from phase. Three windings each 115 V, 10 A, unity pf (star or delta internal accounting).

P = 3 × 115 × 10 = 3450 W (matches √3 VL IL within rounding when VL/IL are consistent with the connection).

Ideal three-phase transformer banks still obey per-phase turns-ratio ideas: each phase pair transforms voltage by Np/Ns; total power balances primary↔secondary aside from losses.

Why Three-Phase on Aircraft / GSE

Large aircraft electrical systems commonly use three-phase 400 Hz generation and distribution for smoother power delivery and efficient high-power machines. Ground power units and hangar supplies may present three-phase as well. Transformers (or autotransformers) match voltage levels between ground and aircraft or between buses. Single-phase transformers remain ubiquitous for avionics and lighting secondaries derived from one phase or from dedicated windings.

Autotransformers — Construction

An autotransformer has one continuous winding on a laminated core, with one or more taps . Part of the winding is common to both “primary” and “secondary” circuits.

  • Feature Two-winding transformer Autotransformer
  • Windings Separate primary & secondary Single tapped winding
  • Isolation Galvanic isolation yes No galvanic isolation
  • Copper / weight More copper for same VA Less copper — lighter
  • Efficiency High Often slightly higher (less winding loss)
  • Variable output Usually fixed ratios Often used as variable tap / Variac-style
  • Voltage relationship

If the full winding has Nfull turns across the supply Vp, and the tap uses Ntap turns for Vs (or vice versa depending on step-up/step-down tap):

Vs / Vp = Ntap / Nfull (for the usual proportional tap from a common end)

Part of the power is transformed electromagnetically; part is conducted directly through the shared winding segment. That conductive path is why less copper is needed for a given throughput when the voltage ratio is close to 1:1 — a major weight win.

Worked example 5 — autotransformer tap. Full winding 115 V across 460 turns. Tap at 112 turns from common end.

Vs = 115 × (112/460) ≈ 28 V .

Worked example 6 — current idea (ideal, step-down). Vs = 28 V, Is = 20 A, Vp = 115 V. Ideal Pin ≈ Pout → Ip ≈ (28×20)/115 ≈ 4.9 A . The common winding carries the difference of the larger and smaller currents (Is − Ip in the usual step-down auto case), which is why conductor rating of the common section differs from a fully isolated design — recognise the idea even if a stem only asks isolation or weight.

Advantages of Autotransformers

Weight and size — less copper and often smaller core for the same throughput when ratio is not extreme.

Cost — fewer materials.

Efficiency — lower winding resistance losses for comparable duty.

Smooth variable ratio — continuously variable autotransformers (Variacs) useful in shops and test benches.

Disadvantages — Critical for Safety

No electrical isolation — primary and secondary share conductors. A fault or open in the common portion can place full primary voltage on the secondary load.

Not for isolation-required loads — sensitive avionics, personnel-safety isolation, and many certification contexts need a true two-winding isolating transformer.

Fault propagation — primary-side disturbances couple more directly to the secondary.

Limited use on aircraft for critical low-voltage supplies — Module 3 / training texts emphasise restriction to applications where isolation is unnecessary and weight saving matters.

Exam contrast: Laminations still apply (eddy currents). Turns-ratio thinking still applies on the tapped turns. The unique autotransformer penalty is loss of isolation , not “higher eddy loss by definition.”

Three-Phase Autotransformer Banks

Three autotransformers can form a three-phase bank (e.g., for modest voltage buck/boost between buses). Line/phase √3 rules still describe the system voltages and currents; each phase unit remains a single-winding tapped device without isolation. Ground-power and industrial buck-boost applications are common; treat aircraft use with the same isolation caution.

Practical Selection Snapshot

  • Need Prefer
  • Isolation between circuits Two-winding transformer
  • Small buck/boost, minimum weight Autotransformer
  • 115 V ↔ 28 V with isolation Two-winding step-down
  • Three-phase 200 V class ↔ phase utilisation Star/delta bank as required
  • Shop variable AC for testing Variable autotransformer (with awareness of no isolation)
  • Closing Syllabus Map for 3.15
  • Section Focus
  • 14.1 Construction, mutual induction, polarity
  • 14.2 Turns ratio, losses, load/no-load, efficiency
  • 14.3 Three-phase V/I/P, autotransformers

Know √3 line/phase rules cold, compute balanced three-phase power, and state without hesitation that autotransformers do not isolate . That trio, plus the turns-ratio chain from 14.2, covers the Module 3 transformer exam surface.