Study guide

6.2 Maximum Demand Calculation and Diversity Factors for ≤45 kVA

EMA Electrician Licence Written Assessment Study Guide Singapore

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Assessment Overview, Electricity Act and Regulations

1.1 Assessment Structure, Eligibility, Fees, and Application Process 1.2 Legislative Framework and Electricity Act Overview (Part 9) 1.3 Electrical Workers Regulations and LEW Classes 1.4 Scope of Work and Responsibilities of a Licensed Electrician 1.5 Electrical Installations Regulations and Compliance Requirements 1.6 Notification, Connection, Modification, and Inspection Duties 1.7 Offences, Penalties, Disciplinary Actions, and Licence Renewal

2 Chapter 2: Domestic Electrical Installations (SS 638)

2.1 Domestic Wiring Systems, Cables, and Conduits 2.2 Consumer Units and Distribution Board (DB) Layouts 2.3 Final Circuits: Lighting, Radial, and Ring Final Socket Circuits 2.4 Mandatory 30 mA RCD/RCCB Protection and Isolation 2.5 Cable Colour Coding, Identification, and Accessories

3 Chapter 3: Industrial Electrical Installations (SS 638)

3.1 Industrial Low-Voltage (LV) Distribution and Sub-Switchboards 3.2 Motor Control Circuits, Starters, and Overload Protection 3.3 Industrial Wiring Systems: Trunking, Tray, Ladder, and Armoured Cables 3.4 Industrial Load Segregation, Phase Balancing, and Emergency Stopping 3.5 Industrial Switchgear, Circuit Breakers (MCB, MCCB), and Fuses 3.6 Motor Troubleshooting, Sequential Starting, and Programmable Logic Controllers (PLC)

4 Chapter 4: Electrical Principles — AC/DC Supplies, Three-Phase Power, and Power Quality

4.1 AC and DC Supply Fundamentals: Circuit Laws, RMS Values, and Singapore Voltage Levels 4.2 Three-Phase Relationships and Real, Apparent, and Reactive Power 4.3 Power Factor Correction, Harmonics, and Power Quality

5 Chapter 5: Protection Against Electric Shock and Earthing

5.1 Fundamentals of Electric Shock: Basic Protection and Fault Protection 5.2 Earthing Systems in Singapore: TN-S and TT Arrangements 5.3 Touch Voltage, Protective Conductor Sizing, and Main Earthing Terminals 5.4 Residual Current Devices (RCD/RCCB), Earth Fault Protection, and Equipotential Bonding

6 Chapter 6: Installation Design, Single-Line Diagrams (SLD), and Cable Sizing

6.1 Single-Line Diagram (SLD) Preparation, Symbols, and Standard Layouts 6.2 Maximum Demand Calculation and Diversity Factors for ≤45 kVA 6.3 Cable Selection, Current-Carrying Capacity, and Correction Factors 6.4 Voltage Drop Calculations and Circuit Segregation Rules

7 Chapter 7: Testing and Commissioning

7.1 Inspection and Testing Sequence Overview and Visual Inspection 7.2 Continuity Testing of Protective and Equipotential Conductors 7.3 Insulation Resistance Testing and Polarity Verification 7.4 Earth Fault Loop Impedance (Zs), RCD Testing, and Post-Turn-On Checks

8 Chapter 8: Temporary Electrical Installations (SS 650)

8.1 SS 650 Part 1: Construction Site Temporary Electrical Supply 8.2 SS 650 Part 2: Festive Lighting, Trade Fairs, and Exhibition Supplies 8.3 Temporary Generators, Statement of Approval (SOA), and Safety Inspections

6.2 Maximum Demand Calculation and Diversity Factors for ≤45 kVA

Key Takeaways Explain This Topic AI

Connected Load is the total sum of continuous power ratings of all installed electrical appliances, whereas Maximum Demand is the actual peak load expected during normal operation.

Applying diversity factors per SS 638 Appendix 4 accounts for the non-simultaneous usage of connected appliances, preventing unnecessary over-sizing of supply cables and main switchgear.

In Singapore, single-phase supplies are generally restricted to 30A or 60A (up to ~14 kVA); loads exceeding 14 kVA require upgrade to a 3-phase 400V supply rated up to 45 kVA (~63A per phase).

The three-phase apparent power formula S = √3 × VL × IL (where VL = 400V) converts line current to kVA: S(kVA) = 0.6928 × IL.

Phase balancing across L1, L2, and L3 is critical in 3-phase installations to minimize neutral current and optimize transformer efficiency.

Last updated: August 2026

6.2 Maximum Demand Calculation and Diversity Factors for ≤45 kVA

Quick Summary: Maximum Demand (MD) is the maximum load current or power drawn by an electrical installation from the supply grid during any specified operational interval. Because not all electrical appliances, lights, or socket outlets operate simultaneously at full rated capacity, calculating maximum demand using Diversity Factors under SS 638 Appendix 4 allows engineers to determine the realistic peak load. Proper maximum demand calculation prevents costly over-design while ensuring incoming supply cables, main cut-out fuses, and circuit breakers do not trip under normal peak operating conditions.

1. Connected Load vs. Maximum Demand

Before sizing intake cables and protective switchgear, a clear distinction must be made between Connected Load and Maximum Demand :

Total Connected Load ( P c o n n P_{conn} P co nn ​ or S c o n n S_{conn} S co nn ​ ): The mathematical sum of the full-load power ratings of all installed electrical equipment, luminaires, socket outlets, motors, and appliances connected to the installation.

Maximum Demand ( I m d I_{md} I m d ​ or S m d S_{md} S m d ​ ): The maximum current or apparent power actually drawn by the installation at any one time under normal operating conditions. It is calculated by applying standardized diversity factors to individual sub-circuits.

Diversity Factor: The ratio of the sum of individual maximum demands of sub-circuits to the maximum demand of the complete installation. In practical design, diversity factors are expressed as derating percentages or fixed allowances applied to connected loads. Maximum Demand = ∑ ( Connected Sub-Circuit Load × Diversity Factor ) \text{Maximum Demand} = \sum \left( \text{Connected Sub-Circuit Load} \times \text{Diversity Factor} \right) Maximum Demand = ∑ ( Connected Sub-Circuit Load × Diversity Factor )

2. Supply Capacity Boundaries in Singapore (≤45 kVA Regime)

In Singapore, SP PowerGrid classifies low-voltage electricity supplies based on load capacity boundaries:

Single-Phase 230V Supply Limits

30A Single-Phase: Equivalent to 30 A × 230 V = 6.9 kVA 30\text{ A} \times 230\text{ V} = 6.9\text{ kVA} 30 A × 230 V = 6.9 kVA . Standard intake for small domestic apartments.

60A Single-Phase: Equivalent to 60 A × 230 V = 13.8 kVA ≈ 14 kVA 60\text{ A} \times 230\text{ V} = 13.8\text{ kVA} \approx 14\text{ kVA} 60 A × 230 V = 13.8 kVA ≈ 14 kVA . Maximum permissible single-phase supply allocation for residential or commercial units.

Threshold Rule: If the calculated maximum demand exceeds 60 A 60\text{ A} 60 A (or 14 kVA 14\text{ kVA} 14 kVA ) , SP PowerGrid mandates an upgrade to a Three-Phase 400V supply to prevent severe phase imbalance on the distribution network.

Three-Phase 400V Supply up to 45 kVA

45 kVA 3-Phase Rating: The maximum capacity boundary for standard small-commercial, food shop, office, or residential house installations operating on direct CT-less or standard 63A meter cut-outs.

Current per Phase Calculation: For a balanced 45 kVA 45\text{ kVA} 45 kVA 3-phase supply at 400 V 400\text{ V} 400 V line voltage: S = 3 × V L × I L S = \sqrt{3} \times V_L \times I_L S = 3 ​ × V L ​ × I L ​ 45 , 000 VA = 3 × 400 V × I L = 692.82 × I L 45,000\text{ VA} = \sqrt{3} \times 400\text{ V} \times I_L = 692.82 \times I_L 45 , 000 VA = 3 ​ × 400 V × I L ​ = 692.82 × I L ​ I L = 45 , 000 692.82 = 64.95 A ≈ 63 A per phase I_L = \frac{45,000}{692.82} = 64.95\text{ A} \approx 63\text{ A per phase} I L ​ = 692.82 45 , 000 ​ = 64.95 A ≈ 63 A per phase

Thus, a 45 kVA 45\text{ kVA} 45 kVA 3-phase supply corresponds to a standard 63 A 63\text{ A} 63 A 3-pole main isolator / MCCB per phase.

3. SS 638 Appendix 4 Diversity Factor Rules

Singapore Standard SS 638 Appendix 4 provides prescriptive rules for estimating maximum demand across domestic, commercial, and small industrial premises. The table below summarizes the mandatory diversity allowances:

Type of Load Circuit Domestic Premises Diversity Allowance Commercial / Office Premises Diversity Allowance Small Industrial Premises Diversity Allowance

Lighting Circuits 66% of total connected lighting load 90% of total connected lighting load 90% of total connected lighting load

13A Socket-Outlet Circuits 100% of largest circuit + 40% of remaining socket circuits 100% of largest circuit + 50% of remaining socket circuits 100% of largest circuit + 50% of remaining socket circuits

Cooking Appliances 10A + 30% of remaining full load + 5A for socket on switch unit 100% of largest appliance + 80% of 2nd + 60% of remaining 100% of largest appliance + 80% of 2nd + 60% of remaining

Instantaneous Water Heaters 100% of largest heater + 100% of 2nd heater + 25% of remaining 100% of largest heater + 100% of 2nd heater + 50% of remaining 100% of largest heater + 100% of 2nd heater + 50% of remaining

Thermal Storage Water Heaters 100% full load (No diversity allowed) 100% full load (No diversity allowed) 100% full load (No diversity allowed)

Air-Conditioning & Motors 100% of largest AC unit + 80% of 2nd unit + 60% of remaining 100% of largest motor/AC + 80% of 2nd motor + 60% of remaining 100% of largest motor + 80% of 2nd motor + 60% of remaining

4. Single-Phase and Three-Phase Power Formulas

To compute phase currents accurately from connected active power ( P P P in kW) or apparent power ( S S S in kVA), use the standard electrical power equations:

Single-Phase Calculations (230V AC) Active Power: P = V × I × cos ⁡ ϕ \text{Active Power: } P = V \times I \times \cos\phi Active Power: P = V × I × cos ϕ Design Current: I b = P V × cos ⁡ ϕ = P 230 × cos ⁡ ϕ \text{Design Current: } I_b = \frac{P}{V \times \cos\phi} = \frac{P}{230 \times \cos\phi} Design Current: I b ​ = V × cos ϕ P ​ = 230 × cos ϕ P ​ Apparent Power: S = V × I = 230 × I b \text{Apparent Power: } S = V \times I = 230 \times I_b Apparent Power: S = V × I = 230 × I b ​

Three-Phase Calculations (400V Line-to-Line / 230V Line-to-Neutral) Active Power: P = 3 × V L × I L × cos ⁡ ϕ \text{Active Power: } P = \sqrt{3} \times V_L \times I_L \times \cos\phi Active Power: P = 3 ​ × V L ​ × I L ​ × cos ϕ Line Current: I L = P 3 × V L × cos ⁡ ϕ = P 692.82 × cos ⁡ ϕ \text{Line Current: } I_L = \frac{P}{\sqrt{3} \times V_L \times \cos\phi} = \frac{P}{692.82 \times \cos\phi} Line Current: I L ​ = 3 ​ × V L ​ × cos ϕ P ​ = 692.82 × cos ϕ P ​ Apparent Power: S = 3 × V L × I L = 0.6928 × I L (kVA) \text{Apparent Power: } S = \sqrt{3} \times V_L \times I_L = 0.6928 \times I_L \text{ (kVA)} Apparent Power: S = 3 ​ × V L ​ × I L ​ = 0.6928 × I L ​ (kVA)

Phase Balancing and Neutral Current

In a 3-phase 4-wire installation, single-phase loads must be distributed evenly across Phase L1, Phase L2, and Phase L3. If the phase currents I 1 , I 2 , I 3 I_1, I_2, I_3 I 1 ​ , I 2 ​ , I 3 ​ are balanced ( I 1 = I 2 = I 3 I_1 = I_2 = I_3 I 1 ​ = I 2 ​ = I 3 ​ ), the neutral current I N = 0 A I_N = 0\text{ A} I N ​ = 0 A . For unbalanced loads, the resultant vector neutral current is calculated using: I N = I 1 2 + I 2 2 + I 3 2 − ( I 1 I 2 + I 2 I 3 + I 3 I 1 ) I_N = \sqrt{I_1^2 + I_2^2 + I_3^2 - (I_1 I_2 + I_2 I_3 + I_3 I_1)} I N ​ = I 1 2 ​ + I 2 2 ​ + I 3 2 ​ − ( I 1 ​ I 2 ​ + I 2 ​ I 3 ​ + I 3 ​ I 1 ​ ) ​

5. Comprehensive Step-by-Step Worked Maximum Demand Calculation

Example Scenario:

A small commercial office unit with a 3-phase 400V supply has the following connected loads:

Lighting: 40 × 2 × 18 W 40 \times 2 \times 18\text{W} 40 × 2 × 18 W LED panel fittings ( 0.95 0.95 0.95 power factor, total 1.52 kW 1.52\text{ kW} 1.52 kW ). Distributed equally: 0.507 kW 0.507\text{ kW} 0.507 kW per phase.

Socket Outlets: 6 separate 13 A 13\text{A} 13 A twin ring final circuits ( 32 A 32\text{A} 32 A protection each). 2 ring circuits connected to L1, 2 to L2, 2 to L3.

Water Heating: 2 × 3.5 kW 2 \times 3.5\text{ kW} 2 × 3.5 kW single-phase instantaneous water heaters ( 15.2 A 15.2\text{ A} 15.2 A each at 230 V 230\text{V} 230 V ). Heater 1 on L1, Heater 2 on L2.

Air-Conditioning: 3 × 3 HP 3 \times 3\text{HP} 3 × 3 HP 3-phase cassette air-conditioners ( 3 kW 3\text{ kW} 3 kW each, cos ⁡ ϕ = 0.85 \cos\phi = 0.85 cos ϕ = 0.85 , total 9 kW 9\text{ kW} 9 kW ). Line current per AC unit = 3000 3 × 400 × 0.85 = 5.1 A = \frac{3000}{\sqrt{3} \times 400 \times 0.85} = 5.1\text{ A} = 3 ​ × 400 × 0.85 3000 ​ = 5.1 A .

Step-by-Step Calculation Solution:

  • Step 1: Calculate Diversity for Lighting (Commercial: 90% allowance)
  • Total Connected Lighting Power = 1 , 520 W = 1,520\text{ W} = 1 , 520 W

Maximum Demand Power = 1 , 520 W × 0.90 = 1 , 368 W = 1,520\text{ W} \times 0.90 = 1,368\text{ W} = 1 , 520 W × 0.90 = 1 , 368 W

Total 3-Phase Current = 1368 3 × 400 × 0.95 = 2.08 A per phase = \frac{1368}{\sqrt{3} \times 400 \times 0.95} = 2.08\text{ A per phase} = 3 ​ × 400 × 0.95 1368 ​ = 2.08 A per phase

Step 2: Calculate Diversity for 13A Socket Outlets (Commercial: 100% largest + 50% remaining)

Each phase has 2 ring circuits rated at 32 A 32\text{A} 32 A capacity.

Per Phase Socket Maximum Demand = 100 % of Circuit 1 ( 32 A ) + 50 % of Circuit 2 ( 32 A × 0.50 = 16 A ) = 100\% \text{ of Circuit 1 } (32\text{A}) + 50\% \text{ of Circuit 2 } (32\text{A} \times 0.50 = 16\text{A}) = 100% of Circuit 1 ( 32 A ) + 50% of Circuit 2 ( 32 A × 0.50 = 16 A )

Per Phase Socket Maximum Demand = 32 A + 16 A = 48 A per phase = 32\text{A} + 16\text{A} = 48\text{A per phase} = 32 A + 16 A = 48 A per phase

  • Step 3: Calculate Diversity for Instantaneous Water Heaters (Commercial: 100% 1st + 100% 2nd)
  • Heater 1 on L1 = 15.2 A = 15.2\text{ A} = 15.2 A
  • Heater 2 on L2 = 15.2 A = 15.2\text{ A} = 15.2 A
  • L3 Water Heater Load = 0 A = 0\text{ A} = 0 A
  • Step 4: Calculate Diversity for Air-Conditioning Units (3-Phase Motors: 100% 1st + 80% 2nd + 60% 3rd)
  • Unit 1 (Largest) = 100 % × 5.1 A = 5.1 A = 100\% \times 5.1\text{ A} = 5.1\text{ A} = 100% × 5.1 A = 5.1 A
  • Unit 2 = 80 % × 5.1 A = 4.08 A = 80\% \times 5.1\text{ A} = 4.08\text{ A} = 80% × 5.1 A = 4.08 A
  • Unit 3 = 60 % × 5.1 A = 3.06 A = 60\% \times 5.1\text{ A} = 3.06\text{ A} = 60% × 5.1 A = 3.06 A

Total AC Maximum Demand per Phase = 5.1 + 4.08 + 3.06 = 12.24 A per phase = 5.1 + 4.08 + 3.06 = 12.24\text{ A per phase} = 5.1 + 4.08 + 3.06 = 12.24 A per phase

Step 5: Tabulate Maximum Demand per Phase (L1, L2, L3)

  • Load Category Phase L1 Current (A) Phase L2 Current (A) Phase L3 Current (A)
  • Lighting 2.08 A 2.08\text{ A} 2.08 A 2.08 A 2.08\text{ A} 2.08 A 2.08 A 2.08\text{ A} 2.08 A
  • 13A Sockets 48.00 A 48.00\text{ A} 48.00 A 48.00 A 48.00\text{ A} 48.00 A 48.00 A 48.00\text{ A} 48.00 A
  • Water Heaters 15.20 A 15.20\text{ A} 15.20 A 15.20 A 15.20\text{ A} 15.20 A 0.00 A 0.00\text{ A} 0.00 A
  • Air-Conditioning 12.24 A 12.24\text{ A} 12.24 A 12.24 A 12.24\text{ A} 12.24 A 12.24 A 12.24\text{ A} 12.24 A

Total Phase Demand 77.52 A 77.52\text{ A} 77.52 A 77.52 A 77.52\text{ A} 77.52 A 62.32 A 62.32\text{ A} 62.32 A

Step 6: Determine Overall Maximum Demand in kVA and Verify Supply Class

Peak Phase Line Current occurs on L1 / L2 at 77.52 A 77.52\text{ A} 77.52 A .

Overall 3-Phase Apparent Power Demand: S m d = 3 × V L × I m a x = 3 × 400 V × 77.52 A = 53 , 707 VA = 53.71 kVA S_{md} = \sqrt{3} \times V_L \times I_{max} = \sqrt{3} \times 400\text{ V} \times 77.52\text{ A} = 53,707\text{ VA} = 53.71\text{ kVA} S m d ​ = 3 ​ × V L ​ × I ma x ​ = 3 ​ × 400 V × 77.52 A = 53 , 707 VA = 53.71 kVA

Technical Conclusion & Design Verification:

Since the calculated Maximum Demand is 53.71 kVA 53.71\text{ kVA} 53.71 kVA ( 77.52 A per phase 77.52\text{ A per phase} 77.52 A per phase ) , this exceeds the standard 45 kVA 45\text{ kVA} 45 kVA / 63 A 63\text{ A} 63 A supply limit .

To bring this installation within the 45 kVA 45\text{ kVA} 45 kVA limit, the LEW must either:

Apply load management or re-group socket circuits (reducing socket demand to 32 A 32\text{A} 32 A per phase base), or

Upgrade the intake submission to SP PowerGrid for a 100 A 100\text{ A} 100 A 3-phase supply ( 69.3 kVA 69.3\text{ kVA} 69.3 kVA ) .

Loading diagram... Maximum Demand & Diversity Derating Flow