Study guide
GEK-3 — AC Systems and Power
Tennessee Limited Licensed Electrician LLE
Track your progress as you read
Finished sections get a check mark.
1 Electrical Theory and Calculations
GEK-1 — Electrical Quantities and Calculation Setup GEK-2 — DC Circuit Relationships GEK-3 — AC Systems and Power
2 NEC Navigation and Core Installation Rules
GEK-4 — NEC 2017 Structure, Definitions, and Lookup INS-1 — Approval, Listing, Labeling, and Instructions INS-2 — Working Space, Access, Guarding, and Enclosures
3 Safe Installations and Service Entrances
INS-3 — Workmanship, Protection, Identification, and OSHA Installation Safety SFB-1 — Load-Calculation Workflow SFB-2 — Service Conductors, Drops, Laterals, and Clearances
4 Service Equipment, Feeders, and Branch Circuits
SFB-3 — Service Equipment and Disconnecting Means SFB-4 — Feeder Sizing and Installation SFB-5 — Branch-Circuit Ratings, Conductors, and Loads
5 Dwelling Circuits, Personnel Protection, and Overcurrent Basics
SFB-6 — Dwelling-Unit Required Circuits and Outlet Placement SFB-7 — GFCI, AFCI, and Branch-Circuit Personnel Protection OCP-1 — Fuses, Circuit Breakers, Ratings, and Conductor Protection
6 Overcurrent Application and Bonding Foundations
OCP-2 — Overcurrent-Device Location and Application GND-1 — Grounding Versus Bonding and the Fault-Current Path GND-2 — Service Grounding and Bonding
7 Grounding Electrodes, Equipment Grounding, and Downstream Systems
GND-3 — Grounding Electrode Systems GND-4 — Equipment Grounding Conductors and Bonding Methods GND-5 — Feeders, Separate Buildings, Separately Derived Systems, and Special Bonding
8 Conductor Selection and Ampacity
CON-1 — Conductor Materials, Insulation, Markings, and Permitted Use CON-2 — Ampacity Tables and Terminal Temperature Limits CON-3 — Adjustment, Correction, and Special Ampacity Conditions
9 Cable Assemblies and Metal Raceway Systems
CON-4 — Cable Assemblies and Flexible Cords RBX-1 — Raceway Selection, Routing, Support, and Mechanical Protection RBX-2 — Metal Raceways
10 Nonmetallic Raceways, Fill, and Boxes
RBX-3 — Nonmetallic and Specialized Raceways RBX-4 — Raceway Fill, Conductor Fill, and Pulling Rules RBX-5 — Outlet, Device, Junction, and Pull Boxes
11 Hazardous Locations: Classification, Gases, Vapors, and Dusts
HAZ-1 — Classified-Location Framework HAZ-2 — Class I Flammable-Gas or Vapor Installations HAZ-3 — Class II Combustible-Dust Installations
12 Class III, Protection Techniques, and Signaling
HAZ-4 — Class III Fibers and Flyings HAZ-5 — Protection Techniques and Hazardous-Location Applications LVC-1 — Class 1/2/3, Alarm, and Signaling Circuits
13 Communications and Lighting Installations
LVC-2 — Communications Systems LGE-1 — Luminaires, Lampholders, and Lighting Outlets
14 Signs and General-Use Equipment
LGE-2 — Electric Signs and Outline Lighting LGE-3 — General-Use Equipment
GEK-3 — AC Systems and Power
Key Takeaways Explain This Topic AI
Standard AC nameplate voltage and current values are RMS quantities; a 60 Hz waveform completes 60 cycles each second.
Resistance and reactance combine as impedance, and inductive or capacitive phase shift affects current and power factor.
Real power is measured in watts, apparent power in volt-amperes, and power factor is real power divided by apparent power.
Balanced three-phase calculations use the square-root-of-three factor with line-to-line voltage and line current; assumptions must be stated.
Last updated: July 2026
Read AC quantities correctly
Alternating current changes magnitude and direction periodically. A common power-system waveform is sinusoidal. Frequency (f) is cycles per second, measured in hertz (Hz). At 60 Hz, the period of one cycle is T = 1/f = 1 ÷ 60 s⁻¹ = 0.0167 s , or 16.7 ms.
Ordinary AC nameplate voltage and current values are root-mean-square (RMS) values. RMS lets AC heating effect be compared with DC: a 120 V RMS sine wave produces the same resistive heating as 120 V DC in the same resistance. Do not substitute peak voltage into a calculation that gives RMS voltage. For a sine wave, peak voltage is about √2 × V_RMS , but most LLE calculations use the stated RMS value directly.
Resistance, reactance, and impedance
Resistance dissipates real power. Inductors and capacitors also oppose AC, but their opposition depends on frequency and is called reactance , measured in ohms. Ideal inductive reactance is X_L = 2πfL , where L is henries. Ideal capacitive reactance is X_C = 1/(2πfC) , where C is farads.
At higher frequency, inductive reactance increases and capacitive reactance decreases. In an ideal inductor, current lags voltage; in an ideal capacitor, current leads voltage. A purely resistive load has voltage and current in phase. A memory aid is useful, but the physical distinction matters: magnetic fields store energy in inductors, electric fields store energy in capacitors, and the stored energy can return to the circuit.
Example: assume an ideal 0.100 H inductor connected to a 120 V RMS, 60 Hz source. X_L = 2π × 60 Hz × 0.100 H = 37.7 Ω . With winding resistance neglected, I = V/X_L = 120 V ÷ 37.7 Ω = 3.18 A RMS . A real coil also has resistance and losses, so its current and real power require impedance information.
Impedance (Z) is total opposition to AC and is measured in ohms. In a series resistance-inductance circuit, resistance and inductive reactance are perpendicular components, so magnitude is Z = √(R² + X_L²) , not simply R + X_L . For a series resistance-capacitance circuit, magnitude similarly uses √(R² + X_C²) .
Assume a series load has R = 30 Ω , X_L = 40 Ω , and is connected to 120 V RMS at the stated frequency. Z = √[(30 Ω)² + (40 Ω)²] = 50 Ω . Current is I = 120 V ÷ 50 Ω = 2.40 A . The impedance must be at least as large as either perpendicular component, so 50 Ω is reasonable.
Real, reactive, and apparent power
Real power (P) performs work or produces heat and is measured in watts. Apparent power (S) is the RMS volt-ampere product and is measured in volt-amperes: for single phase, S = VI . Reactive power (Q) represents energy exchanged with magnetic or electric fields and is measured in reactive volt-amperes (var).
Power factor (PF) is P/S . For single phase, P = VI × PF . Power factor ranges from 0 to 1 in magnitude. A purely resistive load has PF = 1.00; many motors have a lagging power factor below 1.00. Low power factor means more current is required to deliver the same real power at the same voltage.
For the 30 Ω and 40 Ω series RL example, apparent power is S = 120 V × 2.40 A = 288 VA . Real power is P = I²R = (2.40 A)² × 30 Ω = 172.8 W . Thus PF = 172.8 W ÷ 288 VA = 0.600 , which also equals R/Z = 30 Ω ÷ 50 Ω .
For a separate 240 V single-phase load drawing 30 A at PF = 0.80, assume RMS values and steady operation. Apparent power is S = 240 V × 30 A = 7,200 VA = 7.20 kVA . Real power is P = 7,200 VA × 0.80 = 5,760 W = 5.76 kW . Omitting power factor would incorrectly report apparent power as real power.
Balanced three-phase relationships
For a balanced three-phase load using line-to-line voltage V_L and line current I_L :
- S = √3 × V_L × I_L
- P = √3 × V_L × I_L × PF
Assume a balanced 480 V three-phase load draws 20 A at PF = 0.90. Apparent power is S = 1.732 × 480 V × 20 A = 16,627 VA , or 16.6 kVA. Real power is P = 16,627 VA × 0.90 = 14,964 W , or 15.0 kW after appropriate rounding. The square-root-of-three factor is used once.
Connection relationships help explain it. In a balanced wye system, V_L = √3 × V_phase and I_L = I_phase . In balanced delta, V_L = V_phase and I_L = √3 × I_phase . Do not apply a wye line-to-neutral relationship to a delta load without evidence.
Exam checks
Identify whether the question asks for watts, VA, current, or power factor. State single-phase or balanced three-phase assumptions. Use line-to-line voltage with the three-phase formula. At fixed real power and voltage, lowering power factor must increase current; a result showing the opposite is suspect. Finally, a theory result is not automatically an NEC ampacity or overcurrent selection. Later chapters apply continuous-load, conductor, terminal, motor, and equipment rules from the 2017 NEC.
Information checkpoint
When a problem omits power factor or phase configuration, do not silently invent either value. Identify whether the requested quantity can be calculated from the supplied data and state every assumption required by the selected formula.