Study guide

GEK-2 — DC Circuit Relationships

Tennessee Limited Licensed Electrician LLE

Track your progress as you read

Finished sections get a check mark.

1 Electrical Theory and Calculations

GEK-1 — Electrical Quantities and Calculation Setup GEK-2 — DC Circuit Relationships GEK-3 — AC Systems and Power

2 NEC Navigation and Core Installation Rules

GEK-4 — NEC 2017 Structure, Definitions, and Lookup INS-1 — Approval, Listing, Labeling, and Instructions INS-2 — Working Space, Access, Guarding, and Enclosures

3 Safe Installations and Service Entrances

INS-3 — Workmanship, Protection, Identification, and OSHA Installation Safety SFB-1 — Load-Calculation Workflow SFB-2 — Service Conductors, Drops, Laterals, and Clearances

4 Service Equipment, Feeders, and Branch Circuits

SFB-3 — Service Equipment and Disconnecting Means SFB-4 — Feeder Sizing and Installation SFB-5 — Branch-Circuit Ratings, Conductors, and Loads

5 Dwelling Circuits, Personnel Protection, and Overcurrent Basics

SFB-6 — Dwelling-Unit Required Circuits and Outlet Placement SFB-7 — GFCI, AFCI, and Branch-Circuit Personnel Protection OCP-1 — Fuses, Circuit Breakers, Ratings, and Conductor Protection

6 Overcurrent Application and Bonding Foundations

OCP-2 — Overcurrent-Device Location and Application GND-1 — Grounding Versus Bonding and the Fault-Current Path GND-2 — Service Grounding and Bonding

7 Grounding Electrodes, Equipment Grounding, and Downstream Systems

GND-3 — Grounding Electrode Systems GND-4 — Equipment Grounding Conductors and Bonding Methods GND-5 — Feeders, Separate Buildings, Separately Derived Systems, and Special Bonding

8 Conductor Selection and Ampacity

CON-1 — Conductor Materials, Insulation, Markings, and Permitted Use CON-2 — Ampacity Tables and Terminal Temperature Limits CON-3 — Adjustment, Correction, and Special Ampacity Conditions

9 Cable Assemblies and Metal Raceway Systems

CON-4 — Cable Assemblies and Flexible Cords RBX-1 — Raceway Selection, Routing, Support, and Mechanical Protection RBX-2 — Metal Raceways

10 Nonmetallic Raceways, Fill, and Boxes

RBX-3 — Nonmetallic and Specialized Raceways RBX-4 — Raceway Fill, Conductor Fill, and Pulling Rules RBX-5 — Outlet, Device, Junction, and Pull Boxes

11 Hazardous Locations: Classification, Gases, Vapors, and Dusts

HAZ-1 — Classified-Location Framework HAZ-2 — Class I Flammable-Gas or Vapor Installations HAZ-3 — Class II Combustible-Dust Installations

12 Class III, Protection Techniques, and Signaling

HAZ-4 — Class III Fibers and Flyings HAZ-5 — Protection Techniques and Hazardous-Location Applications LVC-1 — Class 1/2/3, Alarm, and Signaling Circuits

13 Communications and Lighting Installations

LVC-2 — Communications Systems LGE-1 — Luminaires, Lampholders, and Lighting Outlets

14 Signs and General-Use Equipment

LGE-2 — Electric Signs and Outline Lighting LGE-3 — General-Use Equipment

GEK-2 — DC Circuit Relationships

Key Takeaways Explain This Topic AI

A series path has one current, additive resistances, and voltage drops that sum to source voltage.

Parallel branches share the same voltage, branch currents add, and equivalent resistance is less than the smallest branch resistance.

Kirchhoff's current and voltage checks expose setup errors in series, parallel, and combination circuits.

Open circuits interrupt a path, shorts bypass impedance, and conductor voltage-drop formulas require a clearly stated length and material assumption.

Last updated: July 2026

Start by drawing the current paths

A circuit calculation becomes easier when the diagram is reduced to nodes and paths. Mark the source voltage, each resistance, and the requested quantity. Assume ideal conductors and a steady DC source unless the problem supplies conductor resistance or another condition. Then decide whether components are in series, parallel, or a combination.

Components are in series only when the same current must pass through each component with no branching node between them. Components are in parallel when both ends connect to the same two nodes, so each branch has the same voltage. Physical appearance does not control; electrical connections do.

Series relationships

For series resistors:

Current is the same through every resistor.

Equivalent resistance is R_T = R₁ + R₂ + ... .

Individual voltage drops are V_n = I × R_n .

The sum of all voltage drops equals source voltage.

Consider an ideal 24 V DC source with 4 Ω and 8 Ω resistors in series. Total resistance is R_T = 4 Ω + 8 Ω = 12 Ω . Circuit current is I = V/R_T = 24 V ÷ 12 Ω = 2 A . The drops are V₁ = 2 A × 4 Ω = 8 V and V₂ = 2 A × 8 Ω = 16 V . Check: 8 V + 16 V = 24 V . The larger resistance receives the larger voltage drop because series current is common.

An open anywhere in this single path makes steady current zero throughout the circuit. With zero current, intact resistors have zero IR drop; the source voltage can appear across the open. A short circuit is an unintended path with very low impedance. A short placed across one resistor bypasses it, reducing total resistance and increasing source current. Real source, conductor, and protective-device impedance limits the current; “zero ohms” is an ideal model, not a safe field condition.

Parallel relationships

For parallel resistors:

Voltage is the same across every branch.

Branch current is I_n = V/R_n .

Total current is the sum of branch currents.

Equivalent resistance follows 1/R_T = 1/R₁ + 1/R₂ + ... .

For two resistors, the product-over-sum shortcut is R_T = (R₁R₂)/(R₁ + R₂) . For two equal resistors, R_T = R/2 . Parallel equivalent resistance must be less than the smallest branch resistance because another current path has been added.

Example: connect 30 Ω and 20 Ω branches across an ideal 120 V DC source. Branch currents are I₁ = 120 V ÷ 30 Ω = 4 A and I₂ = 120 V ÷ 20 Ω = 6 A . Total current is I_T = 4 A + 6 A = 10 A . Equivalent resistance is R_T = 120 V ÷ 10 A = 12 Ω . Check with product over sum: (30 Ω × 20 Ω) ÷ (30 Ω + 20 Ω) = 600 Ω² ÷ 50 Ω = 12 Ω . Total power is P = VI = 120 V × 10 A = 1,200 W ; branch powers of 480 W and 720 W also sum to 1,200 W.

An open branch stops current only in that branch if the other parallel paths remain intact. A short across the source is much more severe: it creates a low-impedance source path and can produce high fault current. Never treat a paper short-circuit exercise as permission to test a suspected short by energizing it. Follow applicable OSHA procedures and use properly rated test equipment.

Combination circuits

Reduce one clear group at a time. Suppose a 6 Ω resistor is in series with two 12 Ω resistors in parallel across an ideal 24 V DC source. First reduce the equal parallel pair: 12 Ω ÷ 2 = 6 Ω . Total resistance is then 6 Ω + 6 Ω = 12 Ω , and source current is 24 V ÷ 12 Ω = 2 A .

The series 6 Ω resistor drops 2 A × 6 Ω = 12 V , leaving 12 V across the parallel group. Each 12 Ω branch therefore carries 12 V ÷ 12 Ω = 1 A . The branch currents add to the 2 A entering the node. Do not apply the 2 A total current to each parallel resistor.

These checks are Kirchhoff's laws in practical form. Kirchhoff's current law says current entering a node equals current leaving it. Kirchhoff's voltage law says the algebraic sum of voltage rises and drops around a closed loop is zero.

Conductor voltage drop

A common two-wire DC or single-phase approximation is V_D = 2KID/CM , where K is conductor resistivity in ohm-cmil per foot, I is amperes, D is one-way length in feet, and CM is circular-mil area. The factor 2 accounts for outgoing and returning conductors.

Assume a 120 V, two-wire circuit carries 20 A over a one-way distance of 100 ft using 10 AWG copper with CM = 10,380 and K = 12.9 Ω-cmil/ft . Then V_D = (2 × 12.9 Ω-cmil/ft × 20 A × 100 ft) ÷ 10,380 cmil = 4.97 V . Percentage drop is (4.97 V ÷ 120 V) × 100 = 4.14% . This is an approximation because conductor temperature and connections affect actual resistance. State whether length is one-way; doubling an already round-trip length would double-count the path.

Before accepting any result, ask whether series drops add to the source, parallel branch currents add to total, and equivalent resistance falls on the correct side of the component values.

Diagnostic checkpoint

When a circuit answer seems wrong, return to the drawing before repeating arithmetic. Confirm which nodes are shared, mark the complete current paths, and decide whether the suspected condition is an open path, a bypassing short, or normal load resistance.