LGE-2 — Electric Signs and Outline Lighting
Tennessee Limited Licensed Electrician LLE
Track your progress as you read
Finished sections get a check mark.
1 Electrical Theory and Calculations
GEK-1 — Electrical Quantities and Calculation Setup GEK-2 — DC Circuit Relationships GEK-3 — AC Systems and Power
2 NEC Navigation and Core Installation Rules
GEK-4 — NEC 2017 Structure, Definitions, and Lookup INS-1 — Approval, Listing, Labeling, and Instructions INS-2 — Working Space, Access, Guarding, and Enclosures
3 Safe Installations and Service Entrances
INS-3 — Workmanship, Protection, Identification, and OSHA Installation Safety SFB-1 — Load-Calculation Workflow SFB-2 — Service Conductors, Drops, Laterals, and Clearances
4 Service Equipment, Feeders, and Branch Circuits
SFB-3 — Service Equipment and Disconnecting Means SFB-4 — Feeder Sizing and Installation SFB-5 — Branch-Circuit Ratings, Conductors, and Loads
5 Dwelling Circuits, Personnel Protection, and Overcurrent Basics
SFB-6 — Dwelling-Unit Required Circuits and Outlet Placement SFB-7 — GFCI, AFCI, and Branch-Circuit Personnel Protection OCP-1 — Fuses, Circuit Breakers, Ratings, and Conductor Protection
6 Overcurrent Application and Bonding Foundations
OCP-2 — Overcurrent-Device Location and Application GND-1 — Grounding Versus Bonding and the Fault-Current Path GND-2 — Service Grounding and Bonding
7 Grounding Electrodes, Equipment Grounding, and Downstream Systems
GND-3 — Grounding Electrode Systems GND-4 — Equipment Grounding Conductors and Bonding Methods GND-5 — Feeders, Separate Buildings, Separately Derived Systems, and Special Bonding
8 Conductor Selection and Ampacity
CON-1 — Conductor Materials, Insulation, Markings, and Permitted Use CON-2 — Ampacity Tables and Terminal Temperature Limits CON-3 — Adjustment, Correction, and Special Ampacity Conditions
9 Cable Assemblies and Metal Raceway Systems
CON-4 — Cable Assemblies and Flexible Cords RBX-1 — Raceway Selection, Routing, Support, and Mechanical Protection RBX-2 — Metal Raceways
10 Nonmetallic Raceways, Fill, and Boxes
RBX-3 — Nonmetallic and Specialized Raceways RBX-4 — Raceway Fill, Conductor Fill, and Pulling Rules RBX-5 — Outlet, Device, Junction, and Pull Boxes
11 Hazardous Locations: Classification, Gases, Vapors, and Dusts
HAZ-1 — Classified-Location Framework HAZ-2 — Class I Flammable-Gas or Vapor Installations HAZ-3 — Class II Combustible-Dust Installations
12 Class III, Protection Techniques, and Signaling
HAZ-4 — Class III Fibers and Flyings HAZ-5 — Protection Techniques and Hazardous-Location Applications LVC-1 — Class 1/2/3, Alarm, and Signaling Circuits
13 Communications and Lighting Installations
LVC-2 — Communications Systems LGE-1 — Luminaires, Lampholders, and Lighting Outlets
14 Signs and General-Use Equipment
LGE-2 — Electric Signs and Outline Lighting LGE-3 — General-Use Equipment
LGE-2 — Electric Signs and Outline Lighting
Key Takeaways Explain This Topic AI
Article 600 adds sign-specific listing, marking, branch-circuit, disconnect, enclosure, grounding, and secondary-wiring rules to the generally applicable Chapter 1 through 4 requirements.
Each covered pedestrian-accessible commercial building or occupancy needs an accessible sign or outline-lighting outlet at each tenant entrance on a branch circuit rated at least 20 A that supplies no other load.
A sign disconnect opens all ungrounded conductors, controls no other load, and is within sight or is capable of being locked open where the 2017 rule permits a remote location; an operating control is not automatically a disconnect.
Preserve the sign listing in the field: use identified entries and wiring methods, close openings, bond metal parts, match wet-location markings, and apply the specialized high-voltage rules to neon secondary circuits.
Last updated: July 2026
Exam checkpoints
Checkpoint What to verify
1 Article 600 adds sign-specific listing, marking, branch-circuit, disconnect, enclosure, grounding, and secondary-wiring rules to the generally applicable Chapter 1 through 4 requirements.
2 Each covered pedestrian-accessible commercial building or occupancy needs an accessible sign or outline-lighting outlet at each tenant entrance on a branch circuit rated at least 20 A that supplies no other load.
3 A sign disconnect opens all ungrounded conductors, controls no other load, and is within sight or is capable of being locked open where the 2017 rule permits a remote location; an operating control is not automatically a disconnect.
Start with Article 600, then keep the general rules
Article 600 covers the installation of conductors and equipment for electric signs and outline lighting. A cabinet sign, channel letters, border tubing, an LED message center, and field-installed neon skeleton tubing may look like lighting equipment, but Article 600 is the starting point. Chapters 1 through 4 still govern such matters as conductor ampacity, wiring methods, boxes, environmental ratings, working space, overcurrent protection, and grounding unless Article 600 modifies them.
Section 600.3 requires electric signs and outline-lighting systems to be listed unless a stated rule covers the field-installed arrangement. Section 600.4 requires identification such as the manufacturer or installer and the electrical input rating. Read the complete nameplate: input voltage and current, frequency where applicable, wet-location marking, lamp or power-supply limitations, and any secondary-circuit information. A listed sign is evaluated as an assembly. Replacing its power supply, drilling new raceway entries, or adding field conductors does not permit the installer to defeat the listing instructions.
A sign installed outdoors is ordinarily in a wet location, even when it has a decorative top. Use equipment and fittings identified for that environment, arrange entries and drain or weep provisions as instructed, and prevent water from accumulating in wiring compartments. Close unused openings with listed closures and maintain access to components intended for service. The enclosure is not a general-purpose junction box for unrelated tenant loads.
Separate the required outlet from the installed sign load
Section 600.5(A) requires each commercial building and each commercial occupancy accessible to pedestrians to have at least one accessible outlet at each entrance to each tenant space for sign or outline-lighting use. That outlet is supplied by a branch circuit rated not less than 20 A and the circuit supplies no other load. Service hallways and service corridors not considered pedestrian entrances do not create the same requirement. The outlet is required even when the tenant has not yet selected a sign.
Do not reverse the wording. The required outlet circuit has a minimum rating of 20 A; that does not mean every sign may be placed on an arbitrarily large breaker. Section 600.5(B) limits ordinary sign and outline-lighting branch circuits to 20 A and permits up to 30 A for neon tubing installations, subject to its details and any stated provision for a larger sign. Apply the actual equipment nameplate, conductor ampacity, and overcurrent rules. Sign and outline-lighting loads are treated as continuous loads when sizing the branch circuit.
For service or feeder load calculations, 220.14(F) assigns at least 1,200 VA to each branch circuit required by 600.5(A), not 1,200 VA to every individual sign outlet placed on that same required circuit. Two required sign branch circuits contribute at least 2 × 1,200 = 2,400 VA before adding any larger known load that the calculation must recognize.
Provide a real disconnect
Under 600.6, each sign or outline-lighting system and the feeder or branch circuit supplying it is controlled by an externally operable switch or circuit breaker that opens all ungrounded conductors and controls no other load. The disconnect must be accessible and located within sight of the sign or outline-lighting system, or be capable of being locked in the open position where the 2017 rule permits it to be out of sight. A disconnect for a multiwire supply opens all ungrounded conductors as required; opening only one pole can leave part of a sign energized.
A time clock, photocell, contactor, dimmer, remote keypad, or software command may operate a sign without isolating its supply. Treat controller and disconnect as different functions unless the installed device is listed, rated, and arranged to perform both. A disconnect hidden behind a sign face is not externally operable merely because a technician can remove screws. Where a controller is remote, apply the controller-location provisions and ensure service personnel can identify and secure the disconnect.
Switches, flashers, and similar devices controlling transformers or electronic power supplies must be suitable for the inductive load or have the current rating specified by 600.6(B). An ordinary ampere rating does not automatically establish suitability for transformer inrush. Mark the controlled sign clearly where several tenant circuits or sign sections could be confused.
Bond the enclosure and protect field wiring
Section 600.7 requires grounding and bonding of metal sign parts and metal outline-lighting equipment, apart from equipment that qualifies for a stated exception such as listed double-insulated equipment. Run an equipment grounding conductor with the supply as required, bond cabinet sections, raceways, transformer or power-supply enclosures, and accessible metal that could become energized. The grounded circuit conductor is not the equipment grounding conductor, and mounting a cabinet on masonry is not a fault-current path.
Field-installed supply conductors use the applicable Chapter 3 wiring method and enter through fittings identified for the enclosure and location. Protect conductors from sharp sheet-metal edges, maintain bending space and conductor temperature ratings, place splices in approved accessible compartments, and keep primary and secondary wiring separated as the listing and Article 600 require. Do not run unrelated branch-circuit conductors through a sign simply because the cabinet is hollow.
LED modules supplied by a listed Class 2 power source remain subject to the power-source listing, output limitations, wiring method, support, polarity, and separation instructions. Class 2 status does not waive physical protection or permission for the space. A field alteration that is outside the evaluated instructions may require a field evaluation or a listed retrofit system rather than an improvised splice.
Recognize the neon secondary hazard
Field-installed skeleton tubing and neon secondary circuits can operate at thousands of volts. Use transformers or electronic power supplies, electrodes, receptacles, bushings, and secondary cable listed for sign use. Keep the high-voltage secondary separate from primary and unrelated wiring, protect it from physical damage, and make electrode connections within suitable housings. Required secondary-circuit ground-fault protection is part of the system; it is not a substitute for cabinet bonding.
Section 600.32 limits secondary-conductor length to control capacitive current and performance. For a solid copper secondary conductor between a transformer or power supply and the first neon tube, the general maximum is 20 ft ; other conductor constructions and installation conditions can have different limits. Locate and arrange the power supply according to Article 600 and its listing instead of extending secondary wiring for convenience. Before energizing, verify the branch rating, disconnect operation, bond continuity, enclosure closure, wet-location details, secondary routing, and all field-applied markings.