6.2 Receptacle Spacing and Required Outlets
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
6.2 Receptacle Spacing and Required Outlets
Key Takeaways Explain This Topic AI
NEC 210.52(A) requires a receptacle in every dwelling wall space 600 mm (2 ft) or wider, with receptacles spaced so no point along the floor line is more than 1.8 m (6 ft) from a receptacle — the "6 ft cord rule."
210.52(B) mandates at least two 20 A small-appliance branch circuits serving only kitchen, dining, breakfast, and pantry receptacles; no lighting, no garbage disposal, no dishwasher on these circuits.
Kitchen countertop receptacles (210.52(C)) must be installed so no point along the countertop is more than 600 mm (24 in) from a receptacle, with the first within 24 in of the sink edge.
210.52 assigns fixed required receptacles to bathrooms (D), outdoors (E), laundry (F), basements and garages (G), and hallways (H) — each a frequent exam target.
Required receptacles must be tamper-resistant (406.26), listed weather-resistant when outdoors (406.9), and GFCI-protected per 210.8.
Last updated: October 2026
The Backbone of Dwelling Receptacle Rules
Quick Answer: NEC Article 210 Part III (210.52 through 210.70) tells you exactly where a dwelling must have receptacles and lighting outlets. These rules are tested on the Knowledge part of the Texas Journeyman exam. Memorize the spacing numbers: 6 ft along general walls, 12 ft maximum between receptacles, 24 in along kitchen countertops, and 24 in from the sink edge to the first countertop receptacle. Miss these and you miss a guaranteed exam item.
General-Purpose Receptacles — NEC 210.52(A)
In every habitable room of a dwelling, 210.52(A)(1) requires receptacles so that no point along the floor line is more than 1.8 m (6 ft) from a receptacle outlet. The practical effect: receptacles are spaced no more than 3.6 m (12 ft) apart so a 6 ft cord plugged into either one can reach any point between them.
210.52(A)(2) requires a receptacle in every wall space 600 mm (2 ft) or wider . Wall space includes fixed glass panels in sliding doors but excludes the sliding panel itself. Bar tops and similar surfaces at least 600 mm wide also count.
210.52(A)(3) prohibits using a lighting outlet controlled by a wall switch as a required receptacle (a switch-controlled receptacle is allowed under 210.70(A)(2) Exception No. 1, but the receptacle itself still has to meet the spacing rule).
210.52(A)(4) counters the open-floor-plan trick: any fixed structural element that creates wall space ≥ 2 ft needs its own receptacle. A breakfast bar peninsula, a half-height partition, or an island with a seating overhang all count.
Small-Appliance Branch Circuits — NEC 210.52(B)
Kitchens, dining rooms, breakfast areas, and pantries are served by small-appliance branch circuits . The rules are strict:
210.52(B)(1) — at least two 20 A small-appliance branch circuits.
210.52(B)(2) — these circuits serve only receptacles in the kitchen, dining, breakfast, pantry, and similar rooms. No lighting. No garbage disposal. No dishwasher. No range hood. Refrigerator receptacle may be on a small-appliance circuit or a dedicated 15/20 A circuit.
210.52(B)(3) — the small-appliance circuits shall not serve receptacles outside those rooms.
The exam loves to ask whether a garbage disposal can share a kitchen small-appliance circuit. The answer is no .
Kitchen Countertop Receptacles — NEC 210.52(C)
210.52(C)(1) — receptacles shall be installed so no point along the countertop is more than 600 mm (24 in) from a receptacle. Translated: receptacles along the counter are spaced no more than 1200 mm (48 in) apart.
210.52(C)(2) — island and peninsula countertops need at least one receptacle; for the first 900 mm (36 in) of peninsular counter measured from the connecting edge, no receptacle is required. Islands with a long dimension ≥ 600 mm need at least one receptacle.
210.52(C)(3) — receptacles shall not be installed in a face-up position on countertops in a sink space (the area directly behind the sink). Receptacles must be above or below the countertop, not on the splash.
210.52(C)(5) — receptacles serving countertops shall be no more than 500 mm (20 in) above the countertop, or below the countertop if the side is accessible (no more than 12 in below the counter).
Worked Example — Counting Required Receptacles in a Sample Room
A dwelling bedroom measures 14 ft × 12 ft . The door is 3 ft wide on one 14 ft wall. There is a 4 ft wide fixed-glass picture window on the opposite 14 ft wall. How many receptacles are required?
Step 1 — Identify wall space. Each wall is ≥ 2 ft wide, so each qualifies. The picture window counts as wall space (fixed glass). The doorway opening does not count as wall space, but the wall segments on either side of the door do if they are ≥ 2 ft.
Step 2 — Apply the 6 ft rule per wall. Walk each wall and place a receptacle so no point is more than 6 ft from a receptacle.
Wall A (14 ft, no door): one receptacle is enough because the maximum reach from a centered receptacle is 7 ft — too far. Place two receptacles, spaced ≤ 12 ft apart, with each end within 6 ft of a receptacle. Two receptacles.
Wall B (12 ft): one centered receptacle leaves 6 ft to each end — exactly compliant. One receptacle.
Wall C (14 ft, contains 4 ft fixed window): the window is fixed glass and counts as wall space. Apply the 6 ft rule across the full 14 ft — two receptacles (same as Wall A).
Wall D (12 ft, contains 3 ft door): wall space = 12 − 3 = 9 ft of actual wall. One receptacle within 6 ft of both ends works if placed 4.5 ft from one end — that leaves 4.5 ft to the other end. One receptacle.
Total minimum: 2 + 1 + 2 + 1 = 6 receptacles (assuming no two walls share a corner receptacle — the corner receptacle typically counts toward only one wall unless it is within 6 ft of points on both walls).
- Wall Length Door/window Required receptacles
- A 14 ft — 2
- B 12 ft — 1
- C 14 ft 4 ft window (fixed) 2
- D 12 ft 3 ft door 1
- Total 6
- Other Required Receptacles — 210.52(D) through (H)
Section Location Rule
210.52(D) Bathroom At least one receptacle within 900 mm (36 in) of each basin; GFCI required per 210.8(A)(1). No receptacle over the tub or shower curb.
210.52(E) Outdoor At least one receptacle at the front and back of the dwelling, accessible at grade level; GFCI per 210.8(A)(3); listed weather-resistant in-use cover (406.9).
210.52(F) Laundry At least one receptacle for the laundry area; 20 A dedicated circuit per 210.11(C)(2).
210.52(G) Basement / Garage At least one receptacle in each unfinished basement and in each attached garage; GFCI per 210.8(A)(2) and (A)(5).
210.52(H) Hallways At least one receptacle in each hallway ≥ 3 m (10 ft) long.
Foyer Receptacles — 210.52(I)
A foyer with an area ≥ 5.6 m² (60 ft²) needs a receptacle at each entry door and one on a wall not containing an entry door, plus one additional receptacle per 3.7 m (12 ft) of wall space.
Common Exam Traps
Lighting on a small-appliance circuit — never allowed; the circuit serves only receptacles in the listed rooms.
Garbage disposal on a kitchen small-appliance circuit — never allowed; the disposal goes on a separate circuit.
Receptacle over a bathtub or shower — prohibited by 406.9(C) and 210.52(D) for the bathroom receptacle.
Forgetting the 12 ft spacing rule — the 6 ft cord rule means 12 ft maximum between receptacles, not 6 ft. Many candidates reverse them.
Fixed panels of sliding doors count as wall space; the sliding panel does not.
Tamper-Resistant and Weather-Resistant
406.26 requires tamper-resistant receptacles in all dwelling units specified by 210.52 (essentially every required dwelling receptacle). 406.9 requires listed weather-resistant receptacles outdoors, with in-use covers. GFCI protection is a separate requirement of 210.8, covered in Section 6.3.