Study guide

14.4 Commercial Building Load Capstone

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

14.4 Commercial Building Load Capstone

Key Takeaways Explain This Topic AI

Separate the 2026 Article 120 load sum from conductor and overcurrent-device sizing.

For office receptacles, compare the demand-factored strap load with the 1 VA/ft² floor under 120.14(K).

Apply 120.60 only when the stated loads are noncoincident.

46,000 VA at balanced 208 V three-phase gives 127.7 A; the example’s separate sizing allowances produce 138.8 A.

The example uses 1/0 AWG copper at 75°C and a 150 A device after the separate sizing checks.

Last updated: October 2026

Capstone Problem: 10,000 sq ft Office Building

This capstone integrates every rule from Sections 14.1 through 14.3 into a single end-to-end calculation.

Given:

  • 10,000 sq ft office building
  • 40 receptacle outlets (one per strap/yoke)
  • Occupancy classification: office building , which triggers the 120.14(K) receptacle comparison
  • Continuous display lighting: 2,000 VA (separate from Table 120.42(A) general lighting)
  • Electric heating: 14,000 VA
  • Air conditioning: 11,000 VA
  • Commercial kitchen: range 4,000 VA + oven 3,000 VA (2 units)
  • System: 208 V, three-phase
  • Step 1 — General Lighting (Table 120.42(A))
  • Item Calculation Result
  • Floor area 10,000 ft² —
  • Unit load (office) Table 120.42(A) 1.3 VA/ft²
  • General lighting 10,000 × 1.3 13,000 VA
  • Demand factor Table 120.45, All Others 100%
  • Lighting demand 13,000 × 100% 13,000 VA

The 125% continuous load factor is already included in the Table 120.42(A) unit value — do not apply it again.

Step 2 — Receptacles (120.14(I), Table 120.47, and the 120.14(K) floor)

  • Item Calculation Result
  • Receptacle load 40 straps × 180 VA 7,200 VA
  • Demand factor Table 120.47 First 10 kVA @ 100%
  • (K)(1) result 7,200 ≤ 10,000 → 100% 7,200 VA
  • (K)(2) floor 10,000 ft² × 1 VA/ft² 10,000 VA
  • Receptacle load used Larger of (K)(1) and (K)(2) 10,000 VA

Two things are happening here. First, 7,200 VA is under the 10 kVA threshold, so no 50% reduction applies under Table 120.47. Second — and this is the step most candidates drop — 120.14(K) requires banks and office buildings to use the larger of the 120.14(I) result or 1 VA per square foot . At 10,000 ft² the floor is 10,000 VA, which beats the 7,200 VA strap count, so 10,000 VA is what moves forward. The two figures are never added.

Step 3 — Display Lighting Load

Include the known display lighting at 2000 VA in the Article 120 load sum. Under 120.5(E), the separate continuous-load sizing allowance is not added at this stage.

Step 4 — Noncoincident Loads (120.60)

Load VA Included?

  • Electric heating 14,000 Yes (larger)
  • Air conditioning 11,000 No (smaller)

Per 120.60, only the larger load is used. Per 120.51, fixed heating is calculated at 100% of connected load.

  • Heating demand = 14,000 VA
  • Step 5 — Commercial Kitchen (Table 120.56)
  • Item Calculation Result
  • Connected load 4,000 + 3,000 7,000 VA
  • Number of units 2 —
  • Demand factor Table 120.56, 2 units 100%
  • Kitchen demand 7,000 × 100% 7,000 VA
  • Floor check 4,000 + 3,000 = 7,000 7,000 ≤ 7,000 ✓
  • Step 6 — Article 120 Load Sum
  • Component VA
  • General lighting 13,000
  • Receptacles 10,000
  • Display lighting 2,000
  • Heating, larger noncoincident HVAC component 14,000
  • Kitchen equipment 7,000
  • Total calculated load 46,000

For a balanced 208 V three-phase supply:

I = 46,000 ÷ (208 × √3) = 127.7 A.

This is the load-calculation result. It is not yet a complete conductor or overcurrent-device selection. The display lighting is continuous, and fixed electric space heating has continuous-load sizing requirements. Apply the appropriate conductor/OCPD rules to those components, while avoiding double application of a factor already included in a table value. Check equipment nameplates, motor components and actual phase allocation before completing an installation design.

Step 7 — Separate Sizing Check

For this worked problem, assume the 14,000 VA heating component is fixed electric space heat, the separate 2000 VA display load is continuous, the table lighting already includes its applicable allowance, and the remaining demand components require no further continuous-load increase. The additional sizing allowance is 25% × (14,000 + 2000) = 4000 VA .

The sizing total is therefore 50,000 VA , giving 138.8 A at 208 V three-phase. With copper conductors, 75°C terminations, no adjustment or correction factors, and ordinary 80%-rated overcurrent equipment, 1/0 AWG copper at 150 A and a 150 A device satisfy this example. The 127.7 A load current and 138.8 A sizing current must not be confused.

What the Example Tests

The office receptacle floor wins over the sparse 40-strap load.

The smaller interlocked HVAC load is omitted; it is not added to heating.

The Article 120 sum uses the known display load without an extra continuous-load multiplier.

Conductor and OCPD selection then applies the separate sizing requirements.

Balanced three-phase VA converts to line current using voltage times the square root of three, not voltage alone.

A different phase allocation, conductor temperature rating, ambient temperature, number of current-carrying conductors or equipment rating can change the final selection. Use all conditions stated in the exam question.