14.2 Continuous Loads and Equipment Demand

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

14.2 Continuous Loads and Equipment Demand

Key Takeaways Explain This Topic AI

NEC 215.2(A)(1) requires feeder conductors to be sized at 125% of the continuous load plus 100% of the noncontinuous load.

NEC 120.51 requires fixed electric space heating to be calculated at 100% of the total connected nameplate load.

NEC 120.60 permits using only the larger of two or more noncoincident loads, such as heating versus air conditioning, when they are unlikely to operate simultaneously.

Table 120.56 demand factors for commercial kitchen equipment range from 100% for 1 to 2 units down to 65% for 6 or more units, but the calculated load can never be less than the sum of the largest two individual equipment loads.

Last updated: October 2026

The 125% Continuous Load Rule

The NEC defines a continuous load as one where the maximum current is expected to continue for 3 hours or more . Commercial lighting, refrigeration, and some process loads are typically continuous. Two parallel rules govern conductor sizing:

215.2(A)(1) — Feeders: Feeder conductors shall have an ampacity not less than 125% of the continuous load plus 100% of the noncontinuous load .

210.19(A)(1) — Branch circuits: Branch-circuit conductors shall have an ampacity not less than 125% of the continuous load plus 100% of the noncontinuous load .

The formula is straightforward:

Conductor ampacity ≥ (1.25 × continuous load) + (1.00 × noncontinuous load)

Important interaction with Table 120.42(A): The general lighting unit values in Table 120.42(A) already include the 125% continuous load factor. When you use those table values for the load calculation, you do not apply 125% again. However, for other continuous loads not calculated from Table 120.42(A) — such as actual continuous lighting or process loads — you must apply the 125% factor per 215.2(A)(1) or 210.19(A)(1).

Fixed Electric Space Heating — 120.51

NEC 120.51 requires fixed electric space-heating loads to be calculated at 100% of the total connected load (nameplate rating). No demand factor is applied to the heating load itself. The feeder or service load current rating cannot be less than the rating of the largest branch circuit supplied.

Exception: Where reduced loading results from duty cycling, intermittent operation, or units not operating simultaneously, the AHJ may permit smaller conductors — but only if the conductors have adequate ampacity for the actual load.

Noncoincident Loads — 120.60

Where two or more loads are unlikely to be operating simultaneously , NEC 120.60 permits using only the larger load in the calculation. The classic exam application is electric heating versus air conditioning — a building will not run both at full capacity at the same time.

Special rule: If a motor or air-conditioning load is part of the noncoincident pair but is not the largest, you must include 125% of the motor or AC load (per 120.60, referencing 120.50) in the total, not just the larger load alone.

Motors and Air-Conditioning — 120.50

NEC 120.50 governs how motor and air-conditioning equipment loads are included in feeder and service calculations. Motor loads are generally taken at nameplate full-load current, with the largest motor added at 125% per 430.62 for feeder OCPD sizing. Motor conductor sizing (430.22 for a single motor, 430.24 for multiple motors) is covered in Chapter 11 — this chapter references it but does not re-teach it.

Table 120.56 — Commercial Kitchen Equipment Demand Factors

For commercial electric cooking equipment, dishwasher boosters, water heaters, and other kitchen equipment (other than dwelling units), NEC 120.56 permits demand factors from Table 120.56:

  • Number of Units Demand Factor
  • 1 100%
  • 2 100%
  • 3 90%
  • 4 80%
  • 5 70%
  • 6 and over 65%

Floor rule: In no case shall the feeder or service calculated load be less than the sum of the largest two kitchen equipment loads .

These demand factors apply only to equipment with thermostatic control or intermittent use as kitchen equipment. They do not apply to space heating, ventilating, or air-conditioning equipment in the kitchen.

  • Example: 4 kitchen units
  • Range: 8,000 VA, Oven: 6,000 VA, Fryer: 4,000 VA, Griddle: 3,000 VA
  • Total connected = 21,000 VA
  • 4 units → 80% demand factor
  • Demand = 21,000 × 0.80 = 16,800 VA
  • Floor check: 8,000 + 6,000 = 14,000 VA
  • 16,800 ≥ 14,000 → use 16,800 VA

If the calculated demand had been less than 14,000 VA, you would use 14,000 VA instead.

Worked Example: Load Sum and Feeder Sizing

Given: A 240 V single-phase feeder supplies:

  • Continuous lighting load: 10,000 VA (not from Table 120.42(A))
  • Noncontinuous receptacle load: 5,000 VA

Interlocked noncontinuous process loads: 15,000 VA and 12,000 VA (neither includes a motor or fixed space-heating load)

  • Step 1 — Noncoincident Loads (120.60)
  • Interlocked process load A (15,000 VA) vs. load B (12,000 VA) → use larger = 15,000 VA

The 12,000 VA process load is dropped from the calculation.

The Article 120 load sum is 10,000 + 5,000 + 15,000 = 30,000 VA , or 125 A at 240 V . Under 120.5(E), keep this separate from the following conductor/OCPD sizing step.

  • Step 2 — Apply Continuous Load Factor for Sizing (215.2(A)(1))
  • Continuous: 10,000 × 1.25 = 12,500 VA
  • Noncontinuous: 5,000 + 15,000 = 20,000 VA
  • Total = 12,500 + 20,000 = 32,500 VA
  • Step 3 — Required Sizing Current
  • I = 32,500 VA ÷ 240 V = 135.4 A
  • Step 4 — Conductor Selection (Table 310.16, 75°C column per 110.14(C))
  • #1/0 Cu = 150 A ≥ 135.4 A ✓
  • Select: 1/0 AWg Cu THWN
  • Step 5 — OCPD Selection (240.6(A))
  • Next standard rating ≥ 135.4 A = 150 A
  • 150 A (conductor) ≥ 150 A (OCPD) ✓
  • Select: 150 A breaker

This example shows three rules working together: 120.60 eliminates the smaller noncoincident load, 215.2(A)(1) applies the 125% continuous factor to the continuous lighting only, and the conductor and OCPD are selected from the verified tables.