14.3 Voltage Drop and Conductor Sizing
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
14.3 Voltage Drop and Conductor Sizing
Key Takeaways Explain This Topic AI
Voltage drop is an NEC Informational Note in 215.2(A)(3) and 210.19(A)(1), not a mandatory rule: the recommended maximum is 3% on any feeder or branch circuit and 5% combined.
Single-phase voltage drop: Vd = (2 × K × I × L) / CM; three-phase: Vd = (square root of 3 × K × I × L) / CM, where K = 12.9 for copper and 21.2 for aluminum.
Chapter 9 Table 8 circular mil areas: #12 = 6,530, #10 = 10,380, #8 = 16,510, #6 = 26,240, #4 = 41,740, #2 = 66,360, #1/0 = 105,600 CM.
NEC 110.14(C) requires the 75°C column of Table 310.16 for equipment rated over 100 A; the 90°C column is used only for derating and adjustment, not for final ampacity.
Voltage-drop upsizing is a design adjustment, not a 240.4(B) next-size-up application — 240.4(B) applies only to OCPD and conductor protection when ampacity does not match a standard rating.
Last updated: August 2026
Voltage Drop — Informational Notes, Not Mandatory
The NEC addresses voltage drop in Informational Notes — not enforceable code language. The key references are:
215.2(A)(3), Informational Note No. 2: Recommends a maximum 3% voltage drop on feeders.
210.19(A)(1), Informational Note No. 4: Recommends a maximum 3% voltage drop on branch circuits.
Combined recommendation: 5% total voltage drop (feeder + branch circuit).
While not mandatory, voltage drop is a practical design requirement and appears frequently on the exam Calculations part. Inspectors and engineers treat the 3%/5% thresholds as best practice.
The Voltage Drop Formulas
- System Formula
- Single-phase Vd = (2 × K × I × L) ÷ CM
- Three-phase Vd = (√3 × K × I × L) ÷ CM
Where:
- Vd = voltage drop in volts
- K = DC resistance constant (12.9 for copper, 21.2 for aluminum)
- I = load current in amperes (at 100%, not 125%)
- L = one-way length of the run in feet
- CM = circular mil area of the conductor (from Chapter 9, Table 8)
- √3 ≈ 1.732
The K values are derived from Chapter 9, Table 8: a 1,000 kcmil copper conductor has 0.0129 Ω per 1,000 ft, so K = 0.0129 × 1,000,000 = 12.9 . For aluminum, 0.0212 × 1,000,000 = 21.2 .
Chapter 9, Table 8 — Conductor Circular Mil Areas
- Size (AWG) Circular Mils
- #12 6,530
- #10 10,380
- #8 16,510
- #6 26,240
- #4 41,740
- #2 66,360
- #1/0 105,600
Circular mil area is the same for copper and aluminum of a given AWG size — only the resistance (and therefore K) differs by material.
- Percentage Voltage Drop
- %Vd = (Vd ÷ source voltage) × 100
For 240 V: 3% = 7.2 V. For 208 V: 3% = 6.24 V. For 120 V: 3% = 3.6 V.
110.14(C) — Termination Temperature Limitations
The termination temperature rating — not the conductor insulation rating — determines which ampacity column of Table 310.16 you may use for final conductor sizing .
- Equipment Rating Required Column Notes
- 100 A or less 60°C column Unless equipment is marked for 75°C
- 100 A or less, marked 60/75°C 75°C column Most modern equipment is marked this way
- Over 100 A 75°C column Equipment is typically not marked; 75°C is the default
- 90°C rated terminations 90°C column Rare; only if all terminations and connectors are rated 90°C
The 90°C column (for THHN, THWN-2, XHHW-2) is used only as a starting point for derating calculations — ambient temperature correction (Table 310.15(B)(1)(1)) and conductor bundling adjustment (Table 310.15(C)(1)). The final ampacity after derating cannot exceed the termination temperature limit from 110.14(C).
240.4(B) — Next Size Up
When a conductor's ampacity does not correspond to a standard OCPD rating in 240.6(A), the next higher standard rating is permitted, provided:
The conductors being protected are not part of a multioutlet branch circuit supplying receptacles.
The next higher rating does not exceed 800 A.
The conductor ampacity is adequate for the load.
Critical distinction: Voltage-drop upsizing is not a 240.4(B) application. Voltage drop drives you to a larger conductor for performance , not for OCPD alignment. You still select the OCPD based on the load current and the conductor's ampacity at the termination temperature column.
240.6(A) — Standard Ampere Ratings
Standard ratings for fuses and inverse time circuit breakers include: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 .
Note: Both 25 A and 35 A are standard ratings. Do not treat them as non-standard — this is a known exam trap. The 2023 NEC added 10 A as a standard rating for the first time.
Worked Example: 250 ft, 30 A, 240 V Single-Phase Feeder
Given: A 30 A load at 240 V, 250 ft (one-way) from the source, wired with #10 Cu.
- Step 1 — Identify Values
- K = 12.9 (copper)
- I = 30 A
- L = 250 ft
- CM = 10,380 (#10 Cu, Chapter 9 Table 8)
- Step 2 — Calculate Voltage Drop
- Vd = (2 × 12.9 × 30 × 250) ÷ 10,380
- Vd = 193,500 ÷ 10,380
- Vd = 18.6 V
- Step 3 — Check Against 3% Recommendation
- 3% of 240 V = 7.2 V
- 18.6 V > 7.2 V → exceeds the recommendation
- Step 4 — Find Required CM for 3% Vd
- CM = (2 × K × I × L) ÷ Vd_max
- CM = 193,500 ÷ 7.2 = 26,875 CM
- Step 5 — Select Larger Conductor
- #6 Cu = 26,240 CM → Vd = 193,500 ÷ 26,240 = 7.4 V (3.07%) — still just over 3%
- #4 Cu = 41,740 CM → Vd = 193,500 ÷ 41,740 = 4.6 V (1.93%) ✓
- Select: #4 Cu for voltage drop compliance
Note on ampacity: #10 Cu at 75°C is rated 35 A (Table 310.16), which is adequate for the 30 A load. The upsizing to #4 is driven entirely by voltage drop , not by ampacity. This is a design adjustment — 240.4(B) is not invoked.