Study guide

12.1 General Disconnecting Means Principles

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

12.1 General Disconnecting Means Principles

Key Takeaways Explain This Topic AI

In sight means visible and not more than 50 ft apart; both conditions must be met.

For outside feeders and branch circuits, use 225.30 for the number of supplies, 225.31 for disconnecting means, and 225.32 for location.

An upstream breaker at another building does not by itself satisfy the disconnect requirement at the building served.

Article 404 covers switching equipment; Article 406, Part III covers general-use snap switches and dimmers.

For 2026 dwelling disconnect problems, distinguish the service requirements in 230.70 from the outside-supply requirements in Article 225.

Last updated: October 2026

Start with the Supply and Equipment Type

A disconnect question is first a classification problem. Determine whether the conductors are a utility service, an outside feeder to another building, a motor branch circuit, or an HVAC circuit. Then use the article for that installation. The presence of a switch somewhere upstream does not establish that its location, rating or function satisfies the equipment rule.

  • Installation Starting reference
  • Outside feeder or branch circuit to a building Article 225
  • Service disconnect Article 230, including 230.70
  • Motor disconnect Article 430
  • Air-conditioning equipment disconnect Article 440
  • General-use wall switches and dimmers Article 406, Part III
  • Other switching equipment Article 404
  • Visibility and Accessibility

In sight requires visibility and a distance of 50 ft or less . A disconnect 20 ft away around an opaque corner is not in sight. Conversely, visible equipment 80 ft away fails the distance condition. Do not confuse this test with readily accessible , which concerns reaching and operating equipment without obstacles or other prohibited actions.

The installation article determines when a lockable disconnect or another exception may be used. The definition of in sight does not create a general exception for every remote switch.

Outside Supplies to Another Building

For an ordinary outside feeder, locate the rules in this sequence:

225.30: determine whether the proposed number of supplies is permitted. Additional supplies need to meet a stated allowance.

225.31: identify the required disconnecting means at the building or structure served.

225.32: apply the location requirements and applicable exceptions.

Check the number, grouping, rating and suitability requirements in the rest of Article 225, including any dwelling-specific outdoor emergency-disconnect provisions.

Suppose a house panel supplies a detached garage. The breaker at the house protects and disconnects that feeder at its source. You must still evaluate the garage's required disconnect. A main-breaker panel at an appropriate garage location may perform that function when it meets the applicable requirements; a main-lug panel without a suitable disconnect is not automatically equivalent.

2026 change: Under 225.31, the emergency disconnect for an outside supply must be within sight of the building or structure. If that disconnect is installed away from the building, the Code also addresses a disconnect at the nearest point of conductor entrance. Read the complete conditions together with 225.32 and 225.41. For one- and two-family dwelling services, the outdoor service-disconnect requirements are in 230.70 ; do not use the older separate 230.85 rule as the current citation.

Switching Equipment and Wiring Devices

Article 404 continues to cover equipment such as disconnect switches. Snap switches and dimmers are now in Article 406, Part III. For a wall-device problem, start with 406.38 for accessibility/grouping and 406.46 for rating/use. For larger switching equipment, start with Article 404 and the equipment-specific article.

An enclosure rating does not establish that the enclosed switch can interrupt every load. Verify the device's voltage, current, load and interrupting characteristics. An isolating device must not be treated as a load-break disconnect unless it is rated and permitted for that duty.

Reference: Minnesota Board of Electricity’s review of the published 2026 NEC changes .