13.2 Appliance, Range, and Dryer Load
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
13.2 Appliance, Range, and Dryer Load
Key Takeaways Explain This Topic AI
NEC 120.53 permits a 75% demand factor on the nameplate load of four or more fastened-in-place appliances, excluding electric ranges, clothes dryers, space-heating equipment, air-conditioning, and EVSE.
NEC 120.54 sets the electric clothes dryer load at 5000 VA or the nameplate rating, whichever is larger, for each dryer served.
Table 120.55 Column C gives a maximum demand of 8 kW for a single household range rated 12 kW or less; for a range over 12 kW, Note 1 increases the Column C figure by 5% for each additional kW or major fraction above 12 kW.
NEC 120.51 sizes fixed electric space heating at 100% of the total connected nameplate load; NEC 120.50 sizes air-conditioning per Article 440.
NEC 120.60 permits only the larger of two noncoincident loads (e.g., heating vs. air-conditioning) to be used in the feeder or service calculation.
Last updated: October 2026
Why This Matters for the TX Journeyman Exam
After the general-lighting subtotal (Section 13.1), the exam's Calculations part tests whether you can correctly apply the individual appliance, range, and dryer articles. Each load category has its own NEC section, its own demand rules, and its own set of exclusions. Mixing them up — for example, applying the 120.53 fastened-in-place 75% factor to a clothes dryer — is one of the most common point-losing mistakes on the exam.
NEC 120.53 — Fastened-in-Place Appliance Load
NEC 120.53 permits a 75% demand factor on the combined nameplate load of four or more fastened-in-place appliances in a dwelling. To qualify, an appliance must be:
- Rated ¼ hp or greater, or 500 W or greater
- Fastened in place (permanently connected)
- Served by the same feeder or service
Exclusions — 120.53 Does NOT Apply To:
- Excluded equipment Calculated under
- Household electric ranges / cooking equipment 120.55
- Clothes dryers 120.54
- Space-heating equipment 120.51
- Air-conditioning equipment 120.50
- Electric vehicle supply equipment (EVSE) 120.57
Typical qualifying appliances include garbage disposers, dishwashers, trash compactors, water heaters, and built-in microwaves.
Rule of thumb: Count the qualifying appliances. If there are fewer than four , use 100% of the nameplate total. If there are four or more , apply 75%.
NEC 120.54 — Electric Clothes Dryers
NEC 120.54 sets the load for a household electric clothes dryer at 5000 VA or the nameplate rating, whichever is larger . For a single dryer in a one-family dwelling, this means:
- Nameplate ≤ 5000 VA → use 5000 VA
- Nameplate > 5000 VA → use the nameplate rating
Table 120.54 demand factors (for multiple dryers in multifamily dwellings) start at 100% for 1–2 dryers, then 80% for 3–5 dryers (see NFPA’s March 2026 Handbook erratum), and reach 25% for 43 or more dryers. For a single-family dwelling with one dryer, the demand factor is 100%, so the load is simply max(5000, nameplate).
NEC 120.55 and Table 120.55 — Electric Ranges and Cooking Equipment
NEC 120.55 and Table 120.55 provide demand factors for household electric ranges, wall ovens, counter-mounted cooktops, and other household cooking appliances. The most commonly tested column is Column C , which applies to ranges and cooking appliances rated not over 12 kW .
Table 120.55 — Column C (Excerpt)
- Number of appliances Maximum demand (kW)
- 1 8
- 2 11
- 3 14
- 4 17
- 5 20
For a single range rated 12 kW or less , the demand load is 8 kW — regardless of the actual nameplate (as long as it is ≤ 12 kW).
Note 1 — Ranges Over 12 kW
Table 120.55, Note 1 states: For ranges individually rated more than 12 kW but not more than 27 kW , the maximum demand in Column C shall be increased 5% for each additional kilowatt of rating or major fraction thereof by which the rating exceeds 12 kW.
"Major fraction thereof" means a fraction of 0.5 kW or more rounds up to the next whole kW. Fractions below 0.5 kW are dropped.
Formula for a single range over 12 kW:
- Demand (kW) = 8 × [1 + 0.05 × (kW over 12)]
- NEC 120.50 and 120.51 — HVAC and Space Heating
- 120.51 — Fixed Electric Space Heating
Fixed electric space heating loads are calculated at 100% of the total connected nameplate load . No demand factor is applied. The feeder or service load current rating shall not be less than the largest branch circuit supplied.
120.50 — Motors and Air-Conditioning Equipment
Air-conditioning and refrigeration equipment loads are determined per Part IV of Article 440 (hermetic refrigerant motor-compressors), using the rated-load current (RLA) or branch-circuit selection current (BCSC) from the nameplate.
120.60 — Noncoincident Loads
Where it is unlikely that two or more loads will be in use simultaneously, NEC 120.60 permits only the largest load to be used in the calculation. The classic dwelling application is heating vs. air-conditioning — a home with electric furnace heat and a central A/C unit will never run both at once, so only the larger load counts.
120.60 motor/AC exception: If a motor or air-conditioning load is part of the noncoincident load but is not the largest, 125% of either the motor load or the air-conditioning load — whichever is larger — shall be used in the calculation (and added to the largest noncoincident load). This ensures the 125% largest-motor factor is not lost when a motor or A/C is the smaller noncoincident load.
- Worked Examples
- (a) 10 kW Electric Range — Column C Direct
A 10 kW range is ≤ 12 kW, so use Table 120.55 Column C directly.
- Result: 8 kW (8000 VA)
- (b) 15 kW Electric Range — Note 1 Adjustment
Step 1 — Determine kW over 12:
15 − 12 = 3 kW over the threshold
Step 2 — Calculate the percentage increase:
3 × 5% = 15%
Step 3 — Apply to the Column C base of 8 kW:
8 kW × 1.15 = 9.2 kW (9200 VA)
- Step Calculation Result
- kW over 12 15 − 12 3 kW
- Increase 3 × 5% 15%
- Demand 8 × 1.15 9.2 kW
- (c) 5500 VA Electric Dryer — 120.54
Compare the nameplate to the 5000 VA minimum:
Nameplate (5500 VA) > 5000 VA → use the nameplate.
Result: 5500 VA
Reference: NFPA 2026 Handbook correction for Table 120.54 .