13.3 Neutral Load and Service Sizing
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
13.3 Neutral Load and Service Sizing
Key Takeaways Explain This Topic AI
NEC 120.61 defines the feeder or service neutral load as the maximum unbalanced load — the load between the neutral and one ungrounded conductor.
NEC 120.61(B)(1) permits a 70% demand factor on the household range and dryer portion of the neutral load; 120.61(B)(2) permits a 70% demand factor on the portion of the unbalanced load exceeding 200 A.
The total computed service load combines the 120.45 demand-factored lighting load, the 120.53 appliance load, the 120.54 dryer load, the 120.55 range load, and the larger of heating or cooling per 120.60.
Table 310.12(A) sizes service-entrance conductors for single-family dwellings at 83% of the service rating: 175 A service requires 1/0 AWG copper or 3/0 AWG aluminum.
The service rating is selected from the 240.6(A) standard ampere ratings at or above the computed load current — a 154.9 A computed load requires a 175 A service.
Last updated: October 2026
Why This Matters for the TX Journeyman Exam
The final step of a dwelling service calculation ties together every load category from Sections 13.1 and 13.2, adds the neutral-load rules from NEC 120.61 , and lands on a service-entrance conductor size from Table 310.12(A) . The exam typically asks you to carry a full calculation through to the conductor size, so every arithmetic step must be right. This section references Chapter 4 for the service-disconnect rules (230.70–230.79) and Chapter 7 for OCPD selection (240.6(A)) — it does not re-teach them.
NEC 120.61 — Feeder or Service Neutral Load
NEC 120.61 defines the neutral load as the maximum unbalanced load : the greatest load between the neutral conductor and any one ungrounded conductor. On a 120/240 V single-phase, 3-wire service, 240 V loads (line-to-line) do not contribute to the neutral; only 120 V loads (line-to-neutral) do.
120.61(B) — Permitted Neutral Demand Factors
There is no separate "Table 120.61" in the 2026 NEC — the reductions are in 120.61(B) as text:
Provision Reduction permitted
120.61(B)(1) A 70% demand factor on the household electric range, wall oven, cooktop, and electric dryer portion of the neutral load (where calculated per Tables 120.55 and 120.54)
120.61(B)(2) A 70% demand factor on that portion of the unbalanced load exceeding 200 A , for 3-wire DC or single-phase AC, 4-wire 3-phase, 3-wire 2-phase, or 5-wire 2-phase systems
The practical result for a single-family dwelling: the first 200 A of unbalanced neutral load is taken at 100%, and the portion above 200 A is taken at 70%.
120.61(C) — Prohibited Reductions
No neutral reduction is permitted for:
Any portion of a 3-wire circuit consisting of 2 ungrounded conductors and the neutral of a 4-wire, 3-phase wye-connected system
That portion consisting of nonlinear loads on a 4-wire, wye-connected, 3-phase system (harmonic current concerns)
NEC 120.60 — Net Computed Load (Recap)
As covered in Section 13.2, where noncoincident loads (heating vs. air-conditioning) will not run simultaneously, 120.60 permits only the larger load to be included in the total. This applies to the total ungrounded-conductor load and indirectly to the neutral (since the 240 V heating or cooling load contributes little or nothing to the neutral).
Table 310.12(A) — Single-Phase Dwelling Service Conductors
Table 310.12(A) applies to service conductors supplying the entire load of a one-family dwelling on a single-phase, 120/240 V system rated 100–400 A. Conductors sized per this table must have an ampacity not less than 83% of the service or feeder rating, and the table may only be used where no adjustment or correction factors (310.15) apply.
Table 310.12(A) — Excerpt (Service-Entrance Conductors)
- Service Rating (A) Copper (AWG/kcmil) Aluminum or Copper-Clad Al
- 100 4 AWG 2 AWG
- 125 2 AWG 1/0 AWG
- 150 1 AWG 2/0 AWG
- 175 1/0 AWG 3/0 AWG
- 200 2/0 AWG 4/0 AWG
Per 310.12(D) , the neutral conductor may be smaller than the ungrounded conductors if the requirements of 120.61 (and 230.42(C) for services) are met.
Complete Worked Example — Single-Family Dwelling Service Load
Given: A 2000 sq ft single-family dwelling, 120/240 V single-phase service, with:
- 2 small-appliance branch circuits, 1 laundry branch circuit
- 10 kW electric range
- 5500 VA electric clothes dryer
- 4 fastened-in-place appliances with a combined nameplate of 9000 VA
- 12 kW electric furnace (no air-conditioning)
No appliance neutral components or line-to-neutral distribution specified; neutral sizing is a separate exercise
Step 1 — General-Lighting Demand Load (from 13.1)
- Component Calculation Load
- General lighting 2000 ft² × 2 VA/ft² 4000 VA
- Small-appliance (120.52(A)) 2 × 1500 VA 3000 VA
- Laundry (120.52(B)) 1 × 1500 VA 1500 VA
- Combined subtotal 8500 VA
Apply Table 120.45:
- First 3000 VA × 100% = 3000 VA
- Remaining 5500 VA × 35% = 1925 VA
- General-lighting demand load = 4925 VA
- Step 2 — Range Load (120.55, Table 120.55 Column C)
- 10 kW ≤ 12 kW → Column C direct = 8000 VA
- Step 3 — Dryer Load (120.54)
- max(5000 VA, 5500 VA) = 5500 VA
- Step 4 — Fastened-in-Place Appliances (120.53)
4 or more qualifying appliances → 75% demand factor:
- 9000 VA × 0.75 = 6750 VA
- Step 5 — HVAC (120.51, 120.60)
- Electric furnace: 12 kW × 100% = 12000 VA (120.51)
- Air-conditioning: none → 0 VA
- Per 120.60, use the larger: 12000 VA
- Step 6 — Total Computed Load (Ungrounded Conductors)
- Load category VA
- General-lighting demand 4925
- Range (120.55) 8000
- Dryer (120.54) 5500
- Fastened-in-place appliances (120.53) 6750
- Electric furnace (120.51/120.60) 12000
- Total computed load 37175 VA
- Step 7 — Service Current
- Formula: I = Total VA / V
- Substitution: 37175 VA / 240 V = 154.9 A
- Step 8 — Select the Service Rating
The computed load is 154.9 A. The service-disconnect rating must be selected from the 240.6(A) standard ampere ratings at or above this value. Standard ratings include 150 A and 175 A — 150 A is below 154.9 A, so the minimum standard service rating is 175 A .
Step 9 — Select Service-Entrance Conductors (Table 310.12(A))
For a 175 A single-family dwelling service, Table 310.12(A) gives:
- Copper: 1/0 AWG
- Aluminum or copper-clad aluminum: 3/0 AWG
- Step 10 — Neutral Load Requires a Separate Calculation
The total 37,175 VA includes line-to-line appliances and does not identify their neutral components or the maximum line-to-neutral loading. You cannot derive the neutral current by dividing the lighting subtotal by 240 V and ignoring every other 120 V load. Determine the maximum unbalanced load under 120.61 , apply only permitted reductions, and check the service grounded-conductor minimum under 250.24(D) and Table 250.102(C)(1) .
For a separate neutral-sizing exercise, suppose a completed load schedule gives 80 A of maximum unbalanced neutral load after permitted reductions . At 75°C, 4 AWG copper has an ampacity of 85 A in Table 310.16 , so it meets that 80 A load before any adjustment/correction and minimum-size checks. The 100 A service allowance in Table 310.12(A) is not a general-purpose 100 A ampacity rating for 4 AWG copper.
Summary of Results
- Result Value
- Total computed load 37175 VA
- Service current 154.9 A
- Minimum service rating (240.6(A)) 175 A
- Cu service-entrance conductor 1/0 AWG
- Al service-entrance conductor 3/0 AWG
- Neutral current Requires a line-to-neutral load schedule; not established by the total service VA
This is the natural endpoint of the load calculation. The service-disconnect rules (230.70–230.79), conductor ampacity adjustments, and OCPD selection are covered in Chapters 4 and 7.