Study guide

3.3 Three-Phase Systems and Power Factor

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

3.3 Three-Phase Systems and Power Factor

Key Takeaways Explain This Topic AI

In a wye system, line-to-line voltage equals line-to-neutral voltage multiplied by 1.732 (e.g., 208Y/120 and 480Y/277).

Three-phase real power: P = 1.732 × E × I × PF, where E is line-to-line voltage and I is line current.

Power factor is the ratio of real power to apparent power (PF = W ÷ VA = cos θ); a purely resistive load has PF = 1.0 and an inductive load has PF < 1.0.

Low power factor forces higher current for the same real power, requiring larger conductors, higher-rated breakers, and creating more voltage drop.

NEC Table 430.250 motor FLC values already account for typical motor power factor and efficiency; NEC 430.22 sizes motor conductors at 125% of that FLC.

Last updated: October 2026

Why This Matters for the Texas Journeyman Exam

The TDLR/PSI journeyman exam is built around commercial and industrial installations, and almost every commercial service in Texas is three-phase. The Calculations part tests three-phase power formulas directly (motor load calcs, feeder sizing, service demand calculations), and the Knowledge part expects you to recognize standard voltage configurations (208Y/120, 480Y/277) and understand how power factor affects conductor sizing. A candidate who cannot distinguish wye from delta, or who forgets the 1.732 factor, will lose points on a large cluster of questions.

  • Three-Phase System Configurations
  • Wye (Y) Systems

A wye (or "star") system has three phase windings connected at a common neutral point. Four wires are brought out: three ungrounded (phase) conductors and one grounded (neutral) conductor.

The defining relationship in a wye system is:

E_line-to-line = 1.732 × E_line-to-neutral

Common wye voltages on the exam:

  • System Designation Line-to-Line Line-to-Neutral Typical Use
  • 208Y/120 208 V 120 V Commercial lighting, receptacles, small motors
  • 480Y/277 480 V 277 V Industrial feeders, large motors, 277 V lighting

The "208Y/120" notation tells you both voltages at once: 208 V phase-to-phase, 120 V phase-to-neutral. Verify: 120 × 1.732 = 207.8 ≈ 208 V . Likewise 277 × 1.732 = 480.1 ≈ 480 V .

Delta (Δ) Systems

A delta system has three windings connected end-to-end in a closed loop. Only three wires are brought out (no neutral), and the line-to-line voltage equals the winding (phase) voltage:

E_line-to-line = E_phase

Common delta voltages: 240 V, 480 V, 600 V. Some deltas are corner-grounded or center-tapped (240/120 V high-leg delta, NEC 110.15), but the exam primarily treats delta as a 3-wire, no-neutral system.

Quick Comparison

  • Property Wye (Y) Delta (Δ)
  • Wires 4 (3 phase + neutral) 3 (phase only, unless derived)
  • E_LL vs E_LN E_LL = 1.732 × E_LN E_LL = E_phase (no single LN)
  • Neutral available Yes No (unless separately derived)
  • Common examples 208Y/120, 480Y/277 240 V, 480 V
  • The 1.732 Factor (√3)

The number 1.732 is the square root of 3. It appears in every three-phase formula because at any instant, a balanced three-phase load draws current through two conductors, and the vector sum of two phase currents 120° apart is √3 times one phase current. You will use 1.732 in:

  • Voltage relationships (wye): E_LL = 1.732 × E_LN
  • Power: P = 1.732 × E_LL × I_line × PF
  • Voltage drop: VD = 1.732 × I × R × L ÷ 1,000

Memorize 1.732 — you will use it dozens of times on the exam.

Three-Phase Power Formula

For a balanced three-phase load, the real power is:

P = 1.732 × E_LL × I_line × PF

Where:

  • P = real power in watts (W)
  • E_LL = line-to-line voltage in volts (V)
  • I_line = line current in amperes (A)
  • PF = power factor (decimal, 0 to 1)

If the load is purely resistive (PF = 1.0), this simplifies to P = 1.732 × E × I.

Worked Example 1 — Resistive Three-Phase Load

A 480 V three-phase electric heater (resistive, PF = 1.0) draws 60 A per phase. What is the power?

  • P = 1.732 × 480 × 60 × 1.0 = 49,882 W (≈ 49.9 kW)
  • Worked Example 2 — Inductive Load with Power Factor

A 208Y/120 V three-phase motor draws 30 A line current at a power factor of 0.85. What real power does it consume?

  • P = 1.732 × 208 × 30 × 0.85
  • P = 1.732 × 208 × 30 = 10,806 VA (apparent power)
  • P = 10,806 × 0.85 = 9,185 W (≈ 9.2 kW)

The apparent power is 10.8 kVA ; the real power is 9.2 kW . The difference is reactive power (VARs), which the motor uses to magnetize its windings but does not convert to mechanical work.

Power Factor (PF)

Power factor is the ratio of real power (watts) to apparent power (volt-amperes):

PF = W ÷ VA = cos θ

Where θ is the phase angle between voltage and current.

  • Load Type Typical PF Examples
  • Resistive 1.0 Heaters, incandescent lamps, electric ranges
  • Inductive 0.7 – 0.9 Motors, transformers, magnetic ballasts
  • Capacitive leading Power-factor correction capacitors (used to offset inductive loads)
  • Purely reactive 0 Ideal inductor or capacitor (no real power)
  • Why Power Factor Matters on the Exam

For the same real power , a lower power factor means more current:

I = P ÷ (1.732 × E × PF)

As PF drops, I rises. Higher current means:

  • Larger conductors (NEC 210.19, 215.2)
  • Larger overcurrent protection (NEC 240.4)
  • More voltage drop (Section 3.2 formulas)
  • Higher transformer kVA rating required
  • Worked Example 3 — Power Factor and Current

A 480 V three-phase load consumes 30 kW of real power.

  • At PF = 1.0: I = 30,000 ÷ (1.732 × 480 × 1.0) = 30,000 ÷ 831.4 = 36.1 A
  • At PF = 0.7: I = 30,000 ÷ (1.732 × 480 × 0.7) = 30,000 ÷ 582.0 = 51.5 A

The 0.7 PF load draws 43% more current for the same 30 kW. Every conductor, breaker, and feeder in that circuit must be sized for 51.5 A, not 36.1 A.

Worked Example 4 — Computing Power Factor

A load draws 40 A at 480 V three-phase. A wattmeter reads 25,000 W. What is the power factor?

  • Apparent power = 1.732 × 480 × 40 = 33,254 VA
  • PF = W ÷ VA = 25,000 ÷ 33,254 = 0.752 (≈ 0.75 lagging)
  • NEC Treatment of Power Factor

The NEC does not mandate a specific power factor for most installations, but it accounts for motor PF implicitly through its tables:

NEC Table 430.250 — Full-load currents for 3-phase AC motors. The table values already incorporate typical motor PF and efficiency. You do not compute motor current from P = 1.732 × E × I × PF using nameplate horsepower; you use the table value directly.

NEC 430.22 — Conductors serving a single continuous-duty motor must be sized at 125% of the FLC from Table 430.250 (or the nameplate FLC if higher).

NEC 120.18(A) — Branch-circuit motor loads are computed using the Table 430.250 current, not a calculated current from nameplate kW.

NEC Article 460 — Power-factor correction capacitors: rules for installation, discharge means, and conductor sizing. The exam may test the 460.12 rating requirement and the 460.28 discharge-circuit rules.

Worked Example 5 — Motor Conductor Sizing

A 50 hp, 460 V, 3-phase motor is supplied by a feeder. Size the conductor.

From NEC Table 430.250 : 50 hp at 460 V → 77 A FLC (this value embeds the motor's typical PF and efficiency — do not recompute).

From NEC 430.22 : Conductor ampacity = 125% × 77 A = 96.25 A .

From NEC Table 310.16 (75 °C Cu): #2 AWG Cu = 115 A — meets 96.25 A.

So the minimum conductor is #2 AWG copper (before any voltage-drop check). Note that we never used the power formula directly — the NEC table bypasses it. The formula matters when you are asked to verify nameplate data, compute power factor from wattmeter readings, or size a capacitor bank.

Practical Effects of Low Power Factor

  • Effect Consequence
  • Higher line current Larger conductors (NEC 210.19, 215.2)
  • Higher voltage drop Longer runs need upsizing
  • Larger breakers NEC 240.4 sizing moves up
  • Higher transformer kVA Apparent power, not real power, governs transformer rating
  • Utility penalties Commercial meters often include PF or demand charges

Correction is typically achieved by installing shunt capacitors (NEC Article 460) or synchronous condensers that supply leading reactive power to cancel the lagging reactive power of inductive loads. A corrected system approaches PF = 1.0, reducing line current and voltage drop.

Key Formulas for Three-Phase and Power Factor

  • Quantity Formula
  • Wye line-to-line voltage E_LL = 1.732 × E_LN
  • Three-phase apparent power VA = 1.732 × E_LL × I_line
  • Three-phase real power P = 1.732 × E_LL × I_line × PF
  • Power factor PF = W ÷ VA = cos θ
  • Current from real power (3φ) I = P ÷ (1.732 × E × PF)
  • Three-phase voltage drop VD = 1.732 × I × R × L ÷ 1,000