Study guide
10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424)
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424)
Key Takeaways Explain This Topic AI
NEC 422.10(A): a fixed storage-type water heater is a continuous load — size the branch circuit and OCPD at 125% of nameplate
NEC 422.31: appliances rated 300 W or less need only a switch or cord-and-plug connection; appliances over 300 W need a lockable disconnect within sight
NEC 424.3(A): fixed electric space heating is a continuous load (125%); each unit requires a separate branch circuit
NEC 422.62: every appliance nameplate must show volts, amps, phases, and horsepower if motor-driven
A 4500 W/240 V water heater draws 18.75 A; at 125% = 23.44 A, requiring a 10 AWG Cu conductor with a 25 A or 30 A OCPD
Last updated: August 2026
Why This Matters for the TX Journeyman Exam
Article 422 (Appliances) , Article 424 (Fixed Electric Space Heating) , and water heaters appear in content outline areas 3, 6, and the Calculations part. The exam frequently tests the disconnecting-means rule (422.31) and the water-heater branch-circuit calculation. Expect one or two calculation items per exam from this material.
Branch-Circuit Rating (NEC 422.10)
NEC 422.10(A) requires that a branch circuit supplying an appliance be rated to carry the appliance load. If the appliance is a continuous load — expected to operate 3 hours or more — the branch-circuit conductor and OCPD must be sized at 125% of the nameplate rating. If non-continuous, size at 100% of the nameplate.
A fixed storage-type water heater is treated as a continuous load per NEC 422.10(A) and must be sized at 125% of nameplate. (If your AHJ accepts an unmarked heater as non-continuous, the non-continuous alternative appears in the worked example below.)
Overcurrent Protection (NEC 422.11)
NEC 422.11 requires each appliance to be protected against overcurrent. The OCPD rating must not exceed the appliance's marked rating. For motor-driven appliances, the OCPD follows the rules of Article 430 Part X (covered in Ch7). Cord-and-plug-connected appliances are protected by the receptacle rating (15 A or 20 A).
Special Branch Circuits (NEC 422.12)
NEC 422.12 requires a separate branch circuit for certain fixed appliances:
- Electric ranges (counter-mounted or wall-mounted)
- Clothes dryers
- Water heaters
- Space-heating equipment
A 20 A branch circuit serving laundry receptacles (NEC 210.11(C)(2), covered in Ch6) is separate from the dedicated dryer circuit.
Flexible Cords for Appliances (NEC 422.16)
NEC 422.16 permits cord-and-plug connection of specific appliances when the cord:
Is listed for the appliance type (422.16(A) general; 422.16(B) appliance-specific),
Has a length per the article (e.g., 422.16(B)(1) freestanding electric range: minimum 3 ft, maximum 4 ft; built-in range: maximum 6 ft), and
Terminates in a grounding-type attachment plug.
A range cord must be 4-wire (separate equipment grounding conductor, not bonded to the neutral) per NEC 250.140 — bonding details are in Ch7.
Support (NEC 422.18)
NEC 422.18 requires fixed appliances and luminaires used as heating appliances to be firmly supported independent of the attachment plug. A ceiling paddle fan must be supported by an outlet box listed for fan support (typically up to 70 lb; heavier fans require independent support).
Disconnecting Means (NEC 422.31)
NEC 422.31 sets the disconnecting means for appliances:
- Appliance Rating Required Disconnect
- 300 W or less A switch or cord-and-plug connection (the receptacle counts)
Over 300 W A lockable disconnect within sight of the appliance, OR a circuit breaker with a permanent lockout device if within sight
For a permanently connected appliance not in sight of its disconnect (e.g., attic HVAC), the breaker with a permanent lockout meets the requirement. The lockout device must be permanent — a clip-on accessory that can be removed without tools does not satisfy 422.31.
Water heater disconnect: A 4500 W water heater (over 300 W) requires a lockable disconnect within sight. A standard non-fusible safety switch rated at 30 A, 240 V is the conventional choice; a circuit breaker with a listed lockout accessory also satisfies the rule when within sight.
Nameplate (NEC 422.62)
NEC 422.62 requires every appliance to bear a nameplate showing volts, amps, and phases; motor-driven appliances must also show horsepower. The nameplate rating is the source of truth for branch-circuit and OCPD sizing.
Fixed Electric Space Heating (Article 424) and Water Heaters
Fixed electric space heating (Article 424): NEC 424.3(A) requires fixed electric space-heating equipment to be considered a continuous load — the 125% sizing rule applies. Each unit requires a separate branch circuit per 424.3(A).
Water heaters: A fixed storage-type water heater is continuous per NEC 422.10(A). Branch-circuit conductors and OCPD are sized at 125% of nameplate.
Worked Example — 4500 W, 240 V Electric Water Heater
A 4500 W, 240 V electric water heater is a common residential size. Convention used here: treat as continuous per NEC 422.10(A).
Step 1 — Full-load current:
I = P / V = 4500 W / 240 V = 18.75 A
Step 2 — Apply 125% for the continuous-load factor (NEC 422.10(A)):
18.75 A × 1.25 = 23.44 A
Step 3 — Conductor size (Table 310.16, 60°C column):
A 10 AWG Cu conductor is rated 30 A at 60°C. The 240.4(D) small-conductor rule caps 10 AWG Cu at 30 A — acceptable for a 23.44 A continuous load.
Step 4 — OCPD (NEC 240.6(A) standard ratings — 25 A and 30 A are both standard):
The next standard size up from 23.44 A is 25 A . A 25 A OCPD protects a 23.44 A continuous load. A 30 A OCPD is also commonly used when the next-standard-up allowance is applied for a continuous load.
Non-continuous alternative (if the AHJ accepts an unmarked heater as non-continuous):
18.75 A → 20 A OCPD with 12 AWG Cu (12 AWG capped at 20 A by 240.4(D)).
The arithmetic matches the brief's stated values; the continuous path is the NEC-consistent default.