Study guide
10.2 Switches and Device Wiring (NEC Articles 404 & 400)
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
10.2 Switches and Device Wiring (NEC Articles 404 & 400)
Key Takeaways Explain This Topic AI
2026 NEC Article 406, Part III covers general-use snap switches, dimmers and electronic control switches; Article 404 covers other switching equipment.
Look up switch connections in 406.30, accessibility/grouping in 406.38, mounting in 406.42 and rating/use in 406.46.
A lighting-control neutral and an equipment grounding conductor serve different purposes. Follow the neutral rule and its stated exceptions; never use the EGC as a normal neutral.
Select a switch or dimmer by its voltage, current, load type and listing, including LED compatibility and any required derating.
Flexible cords are covered by Article 400: 400.10 lists permitted uses and 400.12 lists prohibited uses.
Last updated: October 2026
Find the Correct 2026 Article
A wall switch and a fused disconnect are both switches, but their installation rules now start in different places. Article 406, Part III covers general-use snap switches, dimmers and electronic control switches. Article 404 continues to cover other switching equipment. Starting with the device type prevents an old Article 404 citation from sending you to the wrong rule.
- Lookup 2026 section
- Switch connections 406.30
- Accessibility and grouping 406.38
- Switches, dimmers and control switches 406.40
- Mounting 406.42
- Rating and use 406.46
- Connections and Neutral Availability
A normal lighting switch interrupts the ungrounded conductor. Opening only the neutral can leave the load energized relative to ground even when the light is off. Multiway switching must preserve the correct ungrounded path through the travelers; a grounding conductor is never a traveler or neutral.
Use 406.30 to determine where a grounded conductor must be available for a lighting control. Read the stated exceptions and the conditions for multiple switch locations before concluding that every box needs a neutral. An electronic control may need a neutral to power its electronics; follow its listing and installation instructions. A bare or green equipment grounding conductor is a fault-current path, not a substitute operating-current return.
Ratings and Grounding
Match the device to the circuit voltage and the kind of load it controls. A dimmer's incandescent rating does not establish its LED or motor rating. Check the marked rating, lamp compatibility and any derating required when devices share a box. A product marked 600 W is not evidence of a universal NEC maximum for all dimmers.
Ground switches and conductive faceplates by the permitted equipment-grounding means. For an old box without an EGC, apply the actual replacement-device conditions in the Code; do not create a neutral-to-ground jumper at the switch. The ordinary switch grounding rules and the replacement exceptions must be evaluated separately.
Flexible Cords: Permitted Purpose Matters
400.10 covers permitted uses; 400.12 covers uses that are not permitted. A cord may serve suitable portable equipment or another expressly permitted application. It does not become permanent building wiring merely because its conductor ampacity is adequate.
For example, a listed pendant luminaire can use a suitable pendant cord. Running an extension cord through a hole in a finished wall to supply a permanently installed load is a different use and is prohibited as a substitute for fixed wiring. For a cord-connected appliance, also check its equipment article and listing: permission for one appliance does not authorize every stationary appliance to use a cord.
Choose the cord type for the environment and protect it from strain and physical damage. Table 400.4 is the starting point for cord types; 400.5 addresses ampacity. Wet-location suitability, oil resistance and temperature ratings are product characteristics to verify, not assumptions based on jacket appearance.
Study references: 2026 wiring-device migration, by NEC CMP-18 chair Robert Fahey and Mike Holt’s 2026 volume 1 contents .