Study guide

10.4 Transformers (NEC Article 450)

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

10.4 Transformers (NEC Article 450)

Key Takeaways Explain This Topic AI

NEC 450.3(B) for transformers 1000V or less, primary current 9A or more: primary-only fuse = 125% of FLC (next size up); primary+secondary = primary 250% and secondary 125% (next size up on both sides)

NEC 450.21(A): a dry-type transformer rated 112.5 kVA or less may be installed without a vault; 450.21(C) waives combustible-clearance rules at 600V or less and 112.5 kVA or less

NEC 450.9: transformer ventilation must keep the ambient temperature at or below 40°C (or the transformer's marked ambient rating)

NEC 450.13(B): a dry-type transformer 600V or less and 50 kVA or less may be installed in hollow building spaces if accessible and ventilated

A 75 kVA 480V→208/120V three-phase transformer: primary FLC = 90.3 A → 125 A fuse; secondary FLC = 208 A → 300 A fuse

Last updated: August 2026

Why This Matters for the TX Journeyman Exam

Article 450 (Transformers) appears in content outline area 2 (Separately Derived Systems) and area 6 (Equipment & Devices). The exam tests the 450.3(B) overcurrent percentages, dry-type installation rules (450.21), and a primary/secondary OCPD calculation that lands in the Calculations part. The transformer calculation is a high-value item because the arithmetic is predictable and the table values are fixed.

Overcurrent Protection (NEC 450.3)

NEC 450.3 governs transformer OCPD. Table 450.3(B) applies to transformers 1000 V or less . For primary current of 9 A or more (the common exam range):

  • Protection Scheme Primary OCPD Secondary OCPD Next-Size-Up
  • Primary-only Fuse: 125% of FLC Not required Next standard size up permitted
  • Primary + secondary Fuse: 250% of FLC Fuse: 125% of FLC Next standard size up permitted on both sides

Where the next standard size up is used, the next standard ampere rating from NEC 240.6(A) is selected — recall that 25 A and 35 A are both standard ratings, so 125 A, 150 A, 200 A, 225 A, 250 A, and 300 A are all valid steps.

For primary current less than 9 A , Table 450.3(B) raises the percentages: primary-only fuse = 167% (next size up), and primary + secondary protection permits a primary fuse up to 250% with a 125% secondary fuse. Circuit-breaker percentages are higher still (up to 300% for the smallest primaries). These smaller-transformer rows appear less often on the exam but are worth a quick read of the table.

For transformers rated over 1000 V , Table 450.3(A) applies — separate percentages and different fuse/breaker columns. The Journeyman exam tests 450.3(B) far more often than 450.3(A).

Transformer Vaults and Secondary Grounding (NEC 450.4, 450.5)

NEC 450.4 requires a transformer vault for indoor installations of oil-insulated transformers above specific kVA/ratings, with construction per 450.42 through 450.47 (walls, doors, ventilation, drainage). Dry-type transformers are typically exempt — see 450.21 below.

NEC 450.5 requires the secondary of a separately derived system to be grounded per NEC 250.30 — bonding the neutral at the transformer or at the first disconnect. (Ch9 covers separately derived system grounding in detail.)

Dry-Type Transformer Installation (NEC 450.21)

NEC 450.21(A): a dry-type transformer rated 112.5 kVA or less may be installed without a vault and may be installed in the open. NEC 450.21(C): a dry-type transformer rated 600 V or less and 112.5 kVA or less is not required to maintain clearances from combustible material, but manufacturer-required clearances for ventilation must be maintained.

Ventilation (NEC 450.9)

NEC 450.9 requires transformer installations to provide ventilation so the ambient temperature around the transformer does not exceed 40°C (or the transformer's marked ambient rating). Louvers, grilles, or forced ventilation must direct air so heated air does not recirculate into the transformer intake.

Accessibility (NEC 450.13, 450.22)

NEC 450.13(A) requires transformer vault doors to be lockable and openable from inside without a key. NEC 450.13(B) permits dry-type transformers 600 V or less and 50 kVA or less to be installed in hollow building spaces (e.g., above a dropped ceiling) if accessible and ventilated.

NEC 450.22 requires transformers to be accessible for inspection and maintenance. "Accessible" does not mean "in sight" — access panels are acceptable if the unit can be reached for service.

Tap Rules for Transformer Secondaries (Brief)

Secondary conductors from a transformer to the first OCPD may follow the tap rules of NEC 240.21(C) — the 10-ft and 25-ft tap rules. Detailed tap-rule calculations are in Ch7; here, note only that transformer secondary taps are governed by 240.21(C) and not by 450.3.

Worked Example — 75 kVA, 480V → 208/120V, Three-Phase Transformer

A common commercial service transformer. All arithmetic uses the three-phase formula I = kVA × 1000 / (V × √3), where √3 = 1.732.

Step 1 — Primary full-load current:

I_pri = 75,000 VA / (480 V × 1.732) = 75,000 / 831.4 = 90.3 A

Step 2 — Primary OCPD (primary-only protection, fuse at 125%):

90.3 A × 1.25 = 112.9 A → next standard size up (NEC 240.6(A)) = 125 A

Step 3 — Secondary full-load current:

I_sec = 75,000 VA / (208 V × 1.732) = 75,000 / 360.3 = 208.2 A

Step 4 — Secondary OCPD (primary + secondary protection, fuse at 125%):

208.2 A × 1.25 = 260.3 A → next standard size up = 300 A

If primary + secondary protection is used, the primary fuse may be sized at 250% instead: 90.3 × 2.50 = 225.8 A → 250 A (next standard), while the secondary fuse remains 300 A.

Verify the arithmetic precisely:

  • 90.3 × 1.25 = 112.9 → next standard up = 125 A ✓
  • 208.2 × 1.25 = 260.3 → next standard up = 300 A ✓

Both figures match the brief's stated values. The 125 A primary fuse and 300 A secondary fuse are the conventional exam answers for this transformer.