9.1 Equipment Grounding Conductors

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

9.1 Equipment Grounding Conductors

Key Takeaways Explain This Topic AI

Table 250.122 sizes the wire-type equipment grounding conductor by the rating of the overcurrent protective device ahead of the conductors: 15 A → 14 AWG, 20 A → 12 AWG, 60 A → 10 AWG, 100 A → 8 AWG, 200 A → 6 AWG, 400 A → 3 AWG, 600 A → 2 AWG (copper).

250.122(B) requires the EGC to be increased in size proportionally when ungrounded conductors are increased for voltage drop — not to the next Table 250.122 entry, but by the same ratio as the ungrounded conductors.

250.118 lists permitted EGC types: wire type, rigid metal conduit (RMC), intermediate metal conduit (IMC), electrical metallic tubing (EMT), and listed cable armor; flexible metal conduit (FMC) and liquidtight FMC (LFMC) may serve only where 250.118(5)/(6) conditions are met, and most installations require a separate wire EGC.

250.119 requires the insulated wire EGC to be green or green with one or more yellow stripes; #6 AWG and larger may be re-identified at ends and at every point where the conductor is accessible.

Last updated: October 2026

Why the EGC Matters on the TX Journeyman Exam

Equipment grounding is a Knowledge -part staple. PSI draws items straight from NEC 250 Parts V and VI — type recognition, identification, and Table 250.122 lookups. A common trap is confusing the equipment grounding conductor (the EGC, sized from Table 250.122) with the grounding electrode conductor (GEC, sized from Table 250.66, covered in Chapter 4). They are two different conductors with two different tables and two different jobs. The EGC does not connect to the earth; it connects the faulted metal back to the system neutral at the service or source so the breaker trips.

Performance Requirements — NEC 250.4(A)(2) and (A)(3)

Article 250.4 states what grounding and bonding must accomplish , not just how to do it. For grounded systems:

250.4(A)(2) — Conductive materials enclosing electrical conductors or components, or that are likely to become energized, shall be grounded and bonded in a manner that creates an effective path for fault current.

250.4(A)(3) — Bonding of electrically conductive materials and other equipment shall be sufficient to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed.

250.4(A)(5) — The impedance of the effective ground-fault current path shall be low enough to allow operation of the overcurrent protective device. This is the performance test — if the breaker will not trip, the path is not code-compliant, regardless of wire size.

Types of Equipment Grounding Conductors — NEC 250.118

NEC 250.118 lists the conductors and raceways permitted to serve as an EGC. The most-tested entries:

  • Item Type Key limitation
  • (1) Copper, aluminum, or copper-clad aluminum wire type Most common; insulated or bare
  • (2) Rigid metal conduit (RMC) Threaded, full-path
  • (3) Intermediate metal conduit (IMC) Threaded
  • (4) Electrical metallic tubing (EMT) Setscrew couplings — verify listing

(5) Listed flexible metal conduit (FMC) Only where length ≤ 1.8 m (6 ft), not as sole EGC for over 20 A circuits, and the contained conductors are protected by a 20 A or less OCPD

(6) Listed liquidtight flexible metal conduit (LFMC) Similar trade-size and length limits; 3/8 in. limited to 6 ft and 20 A

  • (7) Armored cable (Type AC) Bonding strip in the cable
  • (8) Metal-clad cable (Type MC) Listed grounding path in the cable

Exam trap: FMC, LFMC, and reduced-size flexible conduits are not a reliable EGC for most installations. A separate wire-type EGC must be pulled inside them. The 6 ft / 20 A exception is narrow and tested.

Identification — NEC 250.119

An insulated wire-type EGC must have a continuous green finish or green with one or more yellow stripes . The exceptions that show up on the exam:

#6 AWG and larger — may be re-identified at each end and at every point where the conductor is accessible by stripping the insulation, or by colored tape, cable ties, or paint. The re-identification must encircle the conductor.

Multiconductor varnished-cloth-insulated cables (legacy) — a green identifying marker is permitted at termination.

A conductor with insulation that is green may not be used as a grounded (neutral) conductor, and a conductor that is white, gray, or has three continuous white stripes may not be used as an EGC.

Sizing the Wire-Type EGC — NEC 250.122 and Table 250.122

NEC 250.122(A) requires the EGC to be sized by Table 250.122 using the rating of the overcurrent protective device ahead of the conductors — not the ungrounded conductor ampacity. The EGC is never required to be larger than the ungrounded conductors.

NEC Table 250.122 (copper, the common range):

  • OCPD rating Copper EGC (AWG)
  • 15 A 14
  • 20 A 12
  • 30 A 10
  • 40 A 10
  • 60 A 10
  • 100 A 8
  • 200 A 6
  • 300 A 4
  • 400 A 3
  • 500 A 3
  • 600 A 2
  • 800 A 1/0
  • 1000 A 2/0
  • 1200 A 3/0

For aluminum or copper-clad aluminum EGCs, Table 250.122 lists a separate (larger) column — use it when the question says aluminum.

Voltage Drop Adjustment — NEC 250.122(B)

When ungrounded conductors are increased in size for voltage drop, the EGC must be increased in size proportionally . The formula:

EGC size = Table 250.122 size × (adjusted ungrounded conductor area / Table-ampacity ungrounded conductor area)

Example: a 100 A feeder is wired in 2 AWG copper instead of the minimum 4 AWG copper to control voltage drop. From Table 250.122, the EGC is 8 AWG . From Chapter 9, Table 8 (conductor areas, stranded):

  • 4 AWG stranded ≈ 41,740 cmil
  • 2 AWG stranded ≈ 66,360 cmil

Ratio = 66,360 / 41,740 = 1.59. New EGC area = 8 AWG area (16,510 cmil) × 1.59 = 26,250 cmil → round up to 6 AWG (26,240 cmil). The EGC moves up one size.

Worked Examples

Example 1 — 60 A feeder. A 60 A feeder supplies a panelboard. Size the wire-type copper EGC.

Step 1: Identify the OCPD rating = 60 A.

Step 2: Table 250.122, copper column, 60 A row → 10 AWG copper .

The ungrounded conductors could be 6 AWG copper (THHN, 75 °C column = 65 A), but the EGC is driven by the OCPD rating, not the conductor size — still 10 AWG.

Example 2 — 200 A service. A 200 A service-entrance panel has a 200 A main breaker. Size the wire-type copper EGC run with the service-entrance conductors.

Step 1: OCPD rating = 200 A.

Step 2: Table 250.122, copper column, 200 A row → 6 AWG copper .

Note this is the equipment grounding conductor, not the grounding electrode conductor (GEC). The GEC for a 2/0 copper service-entrance conductor would be sized from Table 250.66 — 8 AWG copper — a separate calculation covered in Chapter 4. Mixing the two tables is the most common miss on this exam area.