Study guide
7.3 Motor Overcurrent and Short-Circuit Protection
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
7.3 Motor Overcurrent and Short-Circuit Protection
Key Takeaways Explain This Topic AI
Motor branch-circuit short-circuit and ground-fault protection is sized from Table 430.250 FLC (not the nameplate) using the percentages in Table 430.52.
Table 430.52 percentages: inverse-time breaker 250%, instantaneous-trip breaker 800%, dual-element time-delay fuse 175%, non-time-delay fuse 300% for standard AC motors.
Motor overload protection under 430.32 is sized from the motor NAMEPLATE FLC, typically 115% or 125% per Table 430.32.
Short-circuit/ground-fault protection (430.52) and overload protection (430.32) are two separate functions and are never satisfied by the same device on a motor circuit.
When a Table 430.52 result is not a standard rating, 430.52(C)(1) Exception 1 allows the next higher standard size (≤ 600 A).
Last updated: August 2026
Why Motor Overcurrent Matters for the TX Journeyman Exam
Motors are Content Outline area (7) — Motors & Generators — and they generate a disproportionate number of Calculations questions because the sizing rules are multi-step. The Texas exam expects you to know that motor overcurrent is two separate protections , sized from two different FLC sources , using two different sets of percentages . Mixing them up is the most common reason candidates miss motor questions.
The Two Motor Protections
Protection NEC Article Sized From Device Where Installed
Branch-circuit short-circuit and ground-fault 430.52 (Part III) Table 430.250 FLC Fuse or circuit breaker at the line side of the motor disconnect In the motor branch-circuit OCPD
Motor overload 430.32 (Part XIII) Motor nameplate FLC Overload relay (heater) or integral thermal protector At the motor controller or inside the motor
The short-circuit/ground-fault device must be capable of clearing a bolted fault at the motor terminals. The overload device must protect the motor from sustained overcurrent (stall, single-phasing, excessive load). A single device can rarely perform both functions at the currents a motor needs, so Article 430 splits them.
NEC 430.52 and Table 430.52 — Short-Circuit and Ground-Fault Protection
430.52 requires the branch-circuit short-circuit and ground-fault protective device to be sized from the motor full-load current listed in Table 430.250 (for three-phase AC motors) — not from the motor nameplate . The nameplate is used for overload protection only.
Table 430.250 is organized by horsepower and voltage. For example, a 5 hp, 230 V three-phase motor has a Table 430.250 FLC of 15.2 A .
Table 430.52 — Maximum Rating or Setting as a Percentage of FLC
Type of Motor Inverse-time circuit breaker Instantaneous-trip breaker Dual-element (time-delay) fuse Non-time-delay fuse
- Single-phase; polyphase (not wound-rotor); DC 250% 800% 175% 300%
- Wound-rotor 150% 800% 150% 200%
- Direct-current constant-voltage 150% 250% 150% 200%
The percentages are the maximum rating or setting. Where the calculated value does not match a standard 240.6(A) rating, 430.52(C)(1) Exception 1 permits the next higher standard size (up to 600 A). Above 600 A, the next lower standard size is used. Where the maximum still will not carry the starting current, Exception 2 allows further increases for specific device types — for example, an inverse-time breaker rated 800 A or less may be raised up to 400% for high-inrush loads.
NEC 430.58 — Motor Controllers
NEC 430.58 requires the motor controller to have a horsepower rating not less than that of the motor, and to be capable of carrying the motor's full-load current and interrupting stalled-rotor current. A controller rated in horsepower is tested for the duty; a general-purpose switch or breaker is not automatically a motor controller. For the exam, remember that the controller (contactor) is sized in horsepower , while the short-circuit device is sized from Table 430.250 FLC.
NEC 430.32 — Overload Protection
430.32 requires overload protection for each motor based on the motor nameplate full-load current (not Table 430.250). The maximum overload is set by Table 430.32 :
- Motor characteristic Max overload as % of nameplate FLC
- Service factor 1.15 or more , or temp rise 40 °C or less 125%
- All other motors 115%
For motors with a 1.0 service factor and 50 °C rise, the overload is set at 115% of nameplate FLC. For a 1.15 SF motor, 125% is permitted. Where the overload setting is not standard, the next lower size is used for overload relays (the opposite of the 430.52 next-size-up).
A separate overload device is not required where the motor has integral thermal protection approved for the application, or where the motor is part of listed equipment with its own overload protection.
Worked Example — 5 hp, 230 V Three-Phase Motor
Size the inverse-time circuit breaker (short-circuit/ground-fault) and the overload for a 5 hp, 230 V three-phase motor with a 1.15 service factor. The motor nameplate FLC is 15.0 A.
Short-Circuit and Ground-Fault Protection (430.52)
Step 1 — Get the FLC from Table 430.250. A 5 hp, 230 V three-phase motor = 15.2 A (Table 430.250, not the 15.0 A nameplate).
Step 2 — Apply Table 430.52. For an inverse-time circuit breaker on a standard polyphase motor, the percentage is 250% .
15.2 A × 2.50 = 38.0 A
Step 3 — Round to a standard rating (430.52(C)(1) Exception 1). 38.0 A is not a standard 240.6(A) rating. The next higher standard rating above 38 A is 40 A .
Result — short-circuit/ground-fault device: 40 A inverse-time circuit breaker.
Overload Protection (430.32)
Step 1 — Use the motor NAMEPLATE FLC. Nameplate = 15.0 A (not the 15.2 A Table value).
Step 2 — Apply Table 430.32. The motor has a 1.15 service factor, so the maximum overload is 125% of nameplate FLC.
15.0 A × 1.25 = 18.75 A
For a motor with a 1.0 service factor, the 115% value would be:
15.0 A × 1.15 = 17.25 A
Result — overload setting: 18.75 A (1.15 SF motor) or 17.25 A (1.0 SF motor). The next lower standard overload relay rating is selected.
Arithmetic Check
15.2 × 2.50 = 38.0 → next standard up is 40 A. Correct.
15.0 × 1.25 = 18.75 A. Correct.
15.0 × 1.15 = 17.25 A. Correct.
Note that the short-circuit calculation used the Table 430.250 value (15.2 A), and the overload calculation used the nameplate value (15.0 A). The exam will give you both numbers and try to bait you into using the wrong one for each calculation.
Common Exam Traps
Using the nameplate for 430.52 sizing. Wrong. Use Table 430.250.
Using Table 430.250 for 430.32 overload sizing. Wrong. Use the nameplate.
Forgetting the 430.52(C)(1) next-higher-standard-size exception. 38 A is not a standard rating; the answer is 40 A, not 35 A.
Applying 240.4(D) to motor branch circuits. 240.4(D) does not apply — Article 430 controls.
Combining the two protections into one device. A standard inverse-time breaker sized at 250% of FLC is not the overload; a separate overload relay is required at 115%/125% of nameplate FLC.