Study guide

16.2 Energy Storage and EV Charging (Articles 706, 625)

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

16.2 Energy Storage and EV Charging (Articles 706, 625)

Key Takeaways Explain This Topic AI

ESS OCPDs must be rated at least 125% of the ESS nameplate current per 706.30(A), and output conductors sized at 125% of the ESS current rating per 706.31.

ESS disconnecting means per 706.15 must be readily accessible, marked ENERGY STORAGE SYSTEM DISCONNECT, and include emergency shutdown in one- and two-family dwellings.

EVSE requires an individual branch circuit (no other outlets) per 625.40 and is a continuous load per 625.42; apply the applicable continuous-load conductor and overcurrent sizing requirements separately.

A 40 A EVSE requires a 50 A OCPD (40 × 1.25 = 50 A) and a conductor with ampacity ≥ 50 A — 6 AWG copper at 75°C (65 A per Table 310.16) is a common selection.

Use 120.57 for the EVSE load calculation and distinguish known nameplate ratings from unknown-rating and permitted adjustable-setting provisions; conductor/OCPD sizing is a separate check.

Last updated: October 2026

Why Articles 706 and 625 Matter for the TX Journeyman Exam

Content-outline area 10 (Renewable Energy Technologies) extends beyond solar to include energy storage systems (ESS) and electric vehicle charging . The exam tests these primarily on the NEC Knowledge part — scope, disconnecting means, labeling, and continuous-load classification — with EVSE branch-circuit sizing also appearing on the Calculations part.

Use the 2026 edition for both equipment requirements and the separate Article 120 load calculation.

  • Energy Storage Systems — Article 706
  • Scope (706.1)

Article 706 applies to all ESS with a capacity greater than 1 kWh (3.6 MJ) that operate stand-alone or interactive with other power sources. This covers most modern battery systems (lithium-ion, flow batteries, etc.). Stationary battery installations that are not listed energy storage systems are addressed by Article 480.

Key Provisions

  • Section Topic Core Rule
  • 706.4 Nameplate Each ESS must be listed with nameplate data

706.7 Commissioning ESS must be commissioned upon installation (non-dwelling); written maintenance records kept

706.15 Disconnecting means Must disconnect ESS from all wiring systems; readily accessible; marked "ENERGY STORAGE SYSTEM DISCONNECT"

706.30(A) Circuit current / OCPD OCPD rated ≥ 125% of ESS nameplate current (exception: 100% if listed for continuous operation at 100%)

706.31 Conductor sizing Output circuit conductor ampacity ≥ 125% of ESS current rating or the OCPD rating

Article 250 Grounding & bonding ESS grounding and bonding per Article 250; equipment grounding conductors sized per Table 250.122

ESS Disconnecting Means — 706.15 Details

706.15(B) requires the disconnect to be readily accessible and comply with one of:

  • Located within the ESS
  • Within sight and within 10 ft of the ESS
  • If not within sight, capable of being locked in the open position per 110.25

706.15(B) Emergency Shutdown (one- and two-family dwellings): must include an emergency shutdown function to cease power export, with the initiation device located readily accessible outside the building .

706.15(C) marking: must plainly indicate open/closed position and be marked "ENERGY STORAGE SYSTEM DISCONNECT." For non-dwelling installations, marking must include nominal battery voltage, available fault current, arc-flash label, and date of calculation.

ESS Grounding

ESS grounding and bonding comply with Article 250 . Key applications:

  • Equipment grounding conductors sized per Table 250.122 based on the OCPD rating
  • Connection to the building's grounding electrode system
  • Bonding jumpers between metallic ESS enclosures, racking, and conduit
  • For DC battery systems with ungrounded (floating) circuits, a ground-fault detection device is essential
  • Electric Vehicle Supply Equipment — Article 625
  • Scope (625.1)

Article 625 covers the electric vehicle charging system: the EVSE (supply equipment), the connector, and the cable between them. It applies to wired-in (fixed) and cord-and-plug-connected equipment in residential, commercial, and public locations.

Core EVSE Rules

Section Rule

625.40 Individual branch circuit required for EVSE rated above 16 A or 120 V; no other outlets permitted on the circuit

  • 625.41 Overcurrent protection for EVSE branch circuits and feeders
  • 625.42 EV charging load and permitted load-management/adjustable-setting provisions

625.43 Disconnecting means required for EVSE/WPTE rated >60 A or >150 V to ground ; must be readily accessible and lockable in the open position per 110.25; if installed remote from the equipment, a plaque denoting the disconnect location is required

Worked Example — Size the Branch Circuit and OCPD for a 40 A EVSE

Given: A hardwired EVSE rated 40 A maximum continuous load, installed in a garage. Copper conductors, 75°C terminations, no more than 3 current-carrying conductors in the raceway.

Step 1 — Continuous-load adjusted current (625.41/625.42):

  • Formula: Required conductor/OCPD sizing current for this example = EVSE continuous current × 1.25
  • Substitution: 40 A × 1.25 = 50 A

Step 2 — OCPD selection:

The required OCPD sizing current is 50 A. Per 240.6(A) , standard ratings include 50 A. So the OCPD = 50 A .

Step 3 — Conductor selection (Table 310.16, 75°C column, copper):

The conductor ampacity must be ≥ 50 A (the continuous-load value the OCPD protects).

  • Conductor Size 75°C Ampacity (Cu)
  • 8 AWG 50 A
  • 6 AWG 65 A

8 AWG copper at 75°C gives exactly 50 A, which meets the requirement. In practice, many installers use 6 AWG (65 A) to provide margin and accommodate voltage drop on longer runs.

Trap: Do not forget that 625.40 requires an individual branch circuit. You cannot share this circuit with a receptacle, lighting, or any other load.

  • Load Calculation Cross-References — 120.57 and 240.6(A)
  • 120.57 — EVSE Load Calculation

For 2026 load calculations, use the EVSE nameplate rating under 120.57, including a rating modified in accordance with the permitted 625.42 provisions. If the rating is unknown, use the default load specified by 120.57 before proceeding. The old rule taking the larger of 7200 VA and every known equipment rating should not be carried into the 2026 calculation.

Keep this separate from branch-circuit sizing. A known 40 A, 240 V EVSE contributes 9600 VA to the load calculation. Its ordinary continuous-load branch-circuit example above still needs a 50 A sizing current and suitable conductor/OCPD. These numbers answer different questions.

EVSE does not qualify for the 120.53 fastened-in-place appliance reduction. Under the dwelling optional method, 120.82(D) adds EVSE at 100% of the 120.57 value separately from the general-load demand tiers.

240.6(A) — Standard Ampere Ratings

When selecting an OCPD, use a standard rating from 240.6(A) . The full run includes:

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000

Note: 25 A and 35 A are in the standard list. If your calculation yields 28 A, the next standard rating is 30 A. If it yields 36 A, use 40 A.

Comparing ESS and EVSE Requirements

  • Feature ESS (Art. 706) EVSE (Art. 625)
  • Continuous load? Not explicitly; sized via 706.30/706.31 Yes — 625.42
  • OCPD sizing ≥ 125% of nameplate current (706.30) Apply continuous-load sizing requirements (625.41/625.42)
  • Conductor sizing ≥ 125% of ESS current (706.31) Apply continuous-load sizing requirements (625.41/625.42)
  • Individual branch circuit? Not required by 706 specifically Required — 625.40

Disconnect marking "ENERGY STORAGE SYSTEM DISCONNECT" (706.15(C)) Not specified by 625.43 (must be lockable open per 110.25)

  • Grounding Article 250 Article 250
  • Key Takeaways

ESS: Remember the 125% multiplier for both OCPD (706.30) and conductors (706.31), and know the disconnect marking text.

EVSE: Three rules to memorize — individual branch circuit (625.40), continuous-load treatment (625.42), and the separate conductor/OCPD sizing checks.

120.57: Determine the equipment rating under the current rule. Keep load calculations separate from conductor/OCPD sizing.

240.6(A): Always round up to a standard rating; 25 A and 35 A are standard sizes candidates often forget.

Reference: Mike Holt’s 2026 code-change analysis, including the separate 100% EVSE optional-method load .