Study guide
4.2 Service Disconnecting Means
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
4.2 Service Disconnecting Means
Key Takeaways Explain This Topic AI
NEC 230.71 permits a maximum of six service disconnecting means per service — the famous 'six-disconnect rule' or 'six-handle rule' — in a single enclosure or a group of separate enclosures.
The service disconnect must be rated at least 100 amperes for a one- or two-family dwelling per 230.79(C), with a 60-amp minimum for a single circuit and 30 amps for limited-load installations.
230.72 requires all service disconnects to be grouped in the same location unless a generator, fire pump, or multiple-occupancy exception applies.
230.70 requires the disconnect to be readily accessible, located outside the building or nearest the point of entrance of the service conductors, and clearly marked as the service disconnect.
230.66 requires service equipment to be marked with a short-circuit current rating sufficient for the available fault current at the service point.
Last updated: August 2026
Why the Service Disconnect Appears on the Exam
The service disconnecting means is the single most-tested device in Area 2. The Knowledge part will quiz the six-disconnect rule, the minimum rating, the location requirement, and the marking of service equipment. The Calculations part occasionally tests the rating of the disconnect as the result of a service-load computation. Mastering 230.70 through 230.79 is mandatory.
- Article 230 Part VI — Service Disconnecting Means
- 230.71 — Maximum Number of Disconnects (the Six-Handle Rule)
Each service is permitted a maximum of six service disconnecting means per 230.71(A). These six can be in:
A single enclosure (e.g., a six-position main lug load center with no main breaker), or
A group of separate enclosures grouped at one location.
Each disconnect must be capable of being opened independently. The rule is also called the "six movements of the hand" rule — it must take no more than six hand operations to disconnect all service conductors.
Key exception (230.71(A) Exception) : A single disconnect with multiple handles (e.g., a 2-pole main breaker) counts as one disconnecting means, not two.
230.72 — Grouping of Disconnects
230.72(A) requires the two to six disconnects to be grouped in the same location. The only exceptions are:
A separate disconnect for a fire pump (must be located to minimize fire hazard, per 695.5).
A separate disconnect for an emergency system or standby generator (700.x, 702.x).
Multiple-occupancy buildings where each occupant has access to their own service disconnect.
230.79 — Rating of Service Disconnect
The minimum rating depends on the occupancy type:
- Occupancy Minimum Rating NEC Ref
- Single circuit (limited load) 30 A 230.79(A)
- Two circuits (limited load) 60 A 230.79(B)
- One- or two-family dwelling 100 A 230.79(C)
- All other installations 60 A (with calculated load) 230.79(D)
The 100-amp dwelling minimum in 230.79(C) is the most-tested value. Note that 230.79(D) for other installations sets a 60-amp floor, but the actual rating must always carry the calculated load.
230.70 — Location and Accessibility
230.70(A)(1): The service disconnect must be readily accessible — defined in Article 100 as capable of being reached quickly without obstacles, climbing, or portable ladders.
230.70(A)(2): It must be located outside the building or structure, or nearest the point of entrance of the service conductors if inside. This "outside or nearest the point of entry" rule prevents long unprotected runs of service-entrance conductors inside a building. Inside conductors are limited by 230.6 and 230.7 to essentially the minimum practical run.
230.70(B): Each disconnect must be legibly marked with a purpose (e.g., "Main," "Service Disconnect," or "House Panel — Service Entrance"). The marking must be sufficient to identify the disconnect from its purpose and location , and must be on the front of the enclosure or on the inside door.
230.66 — Service Equipment Short-Circuit Current Rating
230.66 requires all service equipment to be marked with its short-circuit current rating (SCCR), and the rating must be equal to or greater than the available fault current at the line terminals of the equipment. Available fault current is determined by the utility transformer impedance, conductor length, and conductor size (Annex D calculation or engineering analysis).
Worked Example
A single-family dwelling has a calculated service load of 92 amperes. What is the minimum service disconnect rating, and what size copper service-entrance conductor (75 °C column) is required?
Minimum disconnect rating : Per 230.79(C), a one-family dwelling requires a minimum 100 A disconnect. The calculated load of 92 A is below 100 A, but the 100 A floor governs.
Standard service size : Round up to the next standard rating (100 A).
Conductor ampacity (230.42) : Must equal or exceed the disconnect rating. 100 A → Table 310.16, 75 °C column, copper:
3 AWG Cu = 100 A — acceptable (equal to rating).
Result : 100 A service disconnect, 3 AWG copper THWN-2 service-entrance conductors in a raceway.
If the same dwelling had a 135 A calculated load:
Disconnect rating = 150 A (next standard size above 135 A).
Conductor = 1/0 AWG Cu (150 A at 75 °C).
Common Exam Pitfalls
Counting handles : A 2-pole breaker counts as ONE disconnect, not two.
"Six enclosures" : The rule is six DISCONNECTS, not six enclosures. One enclosure can hold six disconnects, or six enclosures can hold one each.
Interior location : "Nearest the point of entry" does NOT mean anywhere inside; the conductors must take the shortest practical route.
Mobile home panel : A mobile home's panel inside the unit is NOT the service disconnect — the service disconnect for a mobile home park pedestal is outside per 550.23.