4.3 Grounding Electrode Systems for Services

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

4.3 Grounding Electrode Systems for Services

Key Takeaways Explain This Topic AI

NEC 250.50 requires all grounding electrodes that are present at a building to be bonded together into a single grounding electrode system — you do not pick one electrode; you use all available ones.

A metal underground water pipe in direct contact with earth for at least 10 ft must be supplemented by an additional electrode (rod, pipe, plate, ring, or concrete-encased) per 250.53(D)(2).

Concrete-encased electrodes (Ufer grounds) of at least 20 ft of #4 AWG bare copper or bare steel rebar in the foundation are required in new construction under 250.52(A)(3) and 250.50.

The grounding electrode conductor (GEC) is sized from Table 250.66 based on the size of the largest ungrounded service-entrance conductor, not on the service ampacity.

The main bonding jumper at the service (250.24(C)) bonds the grounded (neutral) conductor to the equipment grounding bus and is sized from Table 250.102(C)(1) — formerly Table 250.66.

Last updated: October 2026

Why Grounding Electrodes Appear on the TX Exam

The Texas Journeyman exam's Knowledge part consistently tests electrode types, the 250.50 "all available electrodes" rule, GEC sizing from Table 250.66, and the supplemental electrode requirement for water pipes. Misreading "supplemental" (additional electrode required) versus "supplementary" (a different concept in 250.54) is a classic exam trap.

NEC 250.50 — The Bonded Electrode System Rule

NEC 250.50 states that all grounding electrodes that are present at a building or structure must be bonded together into one grounding electrode system. You do not choose between a water pipe and a ground rod — if both exist, both must be bonded. The electrodes that make up the system are listed in 250.52(A).

Exception : A concrete-encased electrode is not required to be added to an existing building unless the foundation is being replaced or newly poured, but if one is present it must be bonded.

250.52(A) — Permitted Electrode Types

  • Code Ref Electrode Type Key Requirement
  • 250.52(A)(1) Metal underground water pipe 10 ft in contact with earth; must be supplemented (250.53(D))

250.52(A)(2) Metal in-ground support structure (building steel) At least 10 ft in contact with earth, or bonded to rebar

250.52(A)(3) Concrete-encased electrode (Ufer) ≥ 20 ft of #4 AWG bare Cu OR ≥ 20 ft of bare steel rebar ≥ ½ in. diameter, in 2 in. of concrete

  • 250.52(A)(4) Ground ring ≥ 20 ft of #2 AWG bare Cu, ≥ 30 in. deep, encircling building
  • 250.52(A)(5) Rod & pipe electrodes ≥ 8 ft long, ≥ 5/8 in. diameter for rods; min 1.5 in. for pipes
  • 250.52(A)(6) Plate electrodes ≥ 2 sq ft of surface, ≥ ¼ in. ferrous or 0.06 in. nonferrous
  • 250.52(A)(7) Listed electrodes Listed and identified for grounding use
  • 250.52(B) — NOT Permitted as Electrodes
  • Aluminum electrodes
  • Metal underground gas piping systems (never bond gas pipe as an electrode)
  • Building steel that is not in earth contact and not bonded to a concrete-encased electrode
  • 250.53 — Installation Requirements
  • 250.53(A) — Rod, Pipe, and Plate Electrodes

Each rod/pipe must be supplemented by an additional electrode unless a single rod, pipe, or plate has a measured resistance to earth of 25 ohms or less (250.53(A)(2)(Exception)).

The supplemental electrode must be installed at least 6 ft away from the original (250.53(A)(3)).

Rods must be driven flush or below grade; if rock is encountered, the rod may be buried horizontally in a trench at least 30 in. deep (250.53(G)).

250.53(D) — Water Pipe Electrode Supplement

A metal underground water pipe must be supplemented by an additional electrode — rod, pipe, plate, ring, concrete-encased, or building steel. The supplemental electrode is required because water pipes can be replaced with nonmetallic pipe, leaving no electrode. The bond jumper between the water pipe and the supplemental electrode must be sized from Table 250.66.

250.53(E) — Bonding Jumper Between Electrodes

When multiple electrodes form the system, the bonding jumper connecting them must be sized from Table 250.66 and is not required to be larger than the largest ungrounded service-entrance conductor.

250.66 — Sizing the Grounding Electrode Conductor

Table 250.66 sizes the GEC based on the size of the largest ungrounded service-entrance conductor (copper or aluminum). The GEC connects the grounded (neutral) bus at the service to the grounding electrode system.

  • Largest Ungrounded SE Conductor (Cu) GEC Size (Cu)
  • 2 AWG or smaller 8 AWG
  • 1 or 1/0 AWG 6 AWG
  • 2/0 or 3/0 AWG 4 AWG
  • Over 3/0 to 350 kcmil 2 AWG
  • Over 350 to 600 kcmil 1/0 AWG
  • Over 600 to 1100 kcmil 2/0 AWG

Special rules :

For rod, pipe, or plate electrodes only: GEC need not be larger than 6 AWG copper (250.66(A)).

For a concrete-encased electrode or ground ring only: GEC need not be larger than 4 AWG copper (250.66(B) and (C)).

250.24(C) — Main Bonding Jumper at the Service

250.24(C) requires a main bonding jumper at the service equipment to connect the grounded (neutral) conductor to the equipment grounding conductor (EGC) bus. The main bonding jumper is:

Sized from Table 250.102(C)(1) (use this table for the bonding jumper; Table 250.66 is for grounding electrode conductors).

Required only at the service — never on the load side of the main disconnect (that would create parallel neutral return paths).

A screw, bus, wire, or listed strap supplied with listed panelboards.

Worked Example — GEC and Bonding Jumper Sizing

A service has 2/0 AWG copper service-entrance conductors. Size the GEC to a driven ground rod and to a concrete-encased electrode.

Table 250.66 lookup for 2/0 AWG Cu largest ungrounded conductor → 4 AWG Cu GEC .

250.66(A) cap for a rod-only electrode → GEC need not be larger than 6 AWG Cu, so the GEC to the rod is 6 AWG Cu (the smaller of 4 AWG and 6 AWG).

250.66(B) cap for a concrete-encased electrode → GEC need not be larger than 4 AWG Cu, so the GEC to the Ufer is 4 AWG Cu .

The main bonding jumper at the service is sized from Table 250.102(C)(1): for 2/0 AWG Cu largest ungrounded conductor → 4 AWG Cu (same value as the old Table 250.66).

Exam Pitfalls

"Supplemental" vs. "Supplementary" : 250.53(D) requires a supplemental (additional, required) electrode for water pipes. 250.54 supplementary bonding to grounding is optional and not an electrode requirement.

Gas pipe : Never used as an electrode (250.52(B)(1)).

Main bonding jumper location : Only at the service. A bonding jumper in a subpanel is a violation (creates objectionable neutral current on the EGC).