Study guide
4.4 Service Load Calculations
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
4.4 Service Load Calculations
Key Takeaways Explain This Topic AI
NEC Article 120 governs service load calculations: general lighting uses 2 VA per sq ft for dwellings (120.41), with two 1,500 VA small-appliance branch circuits and one 1,500 VA laundry circuit added.
Table 120.45 demand factors for dwellings apply only to the general lighting + small-appliance + laundry total: first 3,000 VA at 100%, next 117,000 VA at 35%, and any remainder over 120,000 VA at 25%.
Table 120.55 demands a 12 kW range at 8 kW and ranges over 12 kW use Column C plus a note adjustment, while NEC 120.54 demands an electric clothes dryer at 5,000 VA or the nameplate rating, whichever is larger.
Section 120.61(B)(1) permits the specified range/dryer neutral demand reduction. There is no Table 120.61; check the maximum unbalanced load and service grounded-conductor minimum.
For a one-family dwelling service, Table 310.12(A) permits smaller conductors than Table 310.16 — 2 AWG copper covers a 125 A service.
Last updated: October 2026
Why Service Load Calculations Are Tested
The Texas Journeyman Calculations part (26 questions, 110 minutes) is weighted toward load computations, and a single-family dwelling service-load problem is the most common scenario. You will be asked to compute total VA, convert to amps at 240 V single-phase, and select the conductor from Table 310.16. Speed matters: you have roughly 4 minutes per calculation question, so memorize 120.41 (2 VA/sq ft for dwellings) and the three-tier Table 120.45 demand factors.
- Article 120 — Service Load
- Step 1 — General Lighting Load (120.41)
For a single-family dwelling, the general lighting load is computed at 2 VA per square foot under 2026 NEC 120.41. Floor area comes from the outside dimensions (120.5(C)) and excludes open porches and unfinished areas not adaptable for future use, so an attached garage counts.
- Formula : General Lighting VA = Floor Area (sq ft) × 2 VA/sq ft
- Step 2 — Small-Appliance and Laundry Branch Circuits (120.52)
210.11(C)(1) requires at least two 20-amp small-appliance branch circuits for kitchen/dining receptacles, each computed at 1,500 VA → 3,000 VA total.
210.11(C)(2) requires one 20-amp laundry branch circuit , computed at 1,500 VA .
These are added to the general lighting load before applying the Table 120.45 demand factors.
Step 3 — Apply Demand Factors (Table 120.45)
For dwelling units, demand factors apply only to the combined general lighting + small-appliance + laundry load:
- Tier Range Demand Factor
- 1 First 3,000 VA 100%
- 2 Next 117,000 VA (3,001–120,000) 35%
- 3 Remainder over 120,000 VA 25%
- Step 4 — Fixed Appliance Loads
Range (Table 120.55) : A 12 kW range is demanded at 8 kW (Column C, "Not over 12 kW"). For ranges over 12 kW, increase Column C by 5% for each additional kW or major fraction.
Dryer (120.54) : Demand the larger of 5,000 VA or the nameplate VA . A 5 kW dryer demands 5,000 VA; a 14 kW dryer demands 14,000 VA.
Water heater, dishwasher, disposal : add at nameplate VA (no demand factor).
Space heating (120.51) : add at nameplate; do not apply the 120.45 lighting demand.
Air conditioning (120.60) : compare A/C and heating loads and use the larger of the two (they are not simultaneous).
Step 5 — Neutral Load (120.61)
The neutral carries only the unbalanced load — the 120 V portion. For 240 V appliances (range, dryer, water heater), the 240 V portion does not contribute to the neutral.
120.61(B)(1) permits a 70% demand factor for the eligible household range and dryer load calculated under the referenced tables. It does not assert that 70% of the appliance physically operates at 120 V. Apply it only to the eligible neutral-load calculation.
- Step 6 — Total Service Load and Conductor Size
- Total VA ÷ 240 V = Service Amps
Select an adequate standard rating (including 100, 110, 125, 150, 175, 200, 225 and higher ratings), then size service-entrance conductors from Table 310.16 (75 °C column for service equipment rated 100 A or more).
Worked Example — 2,500 sq ft Single-Family Dwelling
A single-family dwelling has 2,500 sq ft of habitable floor area, a 12 kW electric range , a 14 kW electric dryer , two small-appliance branch circuits, and one laundry branch circuit. Compute the service load and size the service-entrance conductors (copper, 75 °C column).
- General Lighting + Small Appliance + Laundry General lighting: 2,500 sq ft × 2 VA = 5,000 VA
- Small-appliance (2 circuits): 2 × 1,500 = 3,000 VA
- Laundry (1 circuit): 1,500 VA
- Subtotal = 9,500 VA
- Apply Table 120.45 Demand First 3,000 VA × 100% = 3,000 VA
- Next 6,500 VA × 35% = 2,275 VA
- Demand load (lighting) = 5,275 VA
- (The 9,500 VA subtotal falls entirely in Tiers 1 and 2; Tier 3 at 25% does not begin until 120,000 VA.)
- Range and Dryer Range (Table 120.55, 12 kW): 8,000 VA
- Dryer (120.54, 14 kW nameplate): 14,000 VA
- Total Service Load 5,275 + 8,000 + 14,000 = 27,275 VA
- Service current = 27,275 ÷ 240 = 113.6 A
Round up to the next standard service rating → 125 A service .
Service-Entrance Conductor (Table 310.16, 75 °C Cu)
- Conductor Ampacity (75 °C Cu)
- 2 AWG 115 A
- 1 AWG 130 A
- 1/0 AWG 150 A
1 AWG Cu (130 A) exceeds the 125 A service rating → 1 AWG copper THWN-2 service-entrance conductors .
Cross-check with Table 310.12(A). Sizing straight from Table 310.16 as above is always defensible, but for a one-family dwelling service on a 120/240 V single-phase system, Table 310.12(A) permits a smaller conductor — it lists 2 AWG copper for a 125 A service (the 83% allowance). If an exam question names a one-family dwelling and a standard service rating, answer from Table 310.12(A); fall back to Table 310.16 when the dwelling allowance does not apply, such as when adjustment or correction factors are in play or the conductors do not carry the entire dwelling load. Section 13.3 works this table in full.
- Neutral Calculation (120.61) Lighting+SA+laundry demand (neutral) = 5,275 VA (all 120 V)
- Range 120 V load: 8,000 × 70% = 5,600 VA
- Dryer 120 V load: 14,000 × 70% = 9,800 VA
- Neutral load = 5,275 + 5,600 + 9,800 = 20,675 VA
- Neutral current = 20,675 ÷ 240 = 86.1 A
From Table 310.16, 75 °C Cu: a 3 AWG Cu conductor (100 A) carries the 86.1 A neutral load → 3 AWG copper neutral , subject also to 250.24(D) and the applicable minimum in Table 250.102(C)(1). The neutral may be smaller than the ungrounded conductors when the calculated neutral load is less.
Common Exam Errors
Forgetting the 1,500 VA laundry circuit — it is required even if the laundry receptacle is shared.
Applying Table 120.45 to appliances — demand factors apply only to lighting + small-appliance + laundry.
Using 100% on a range — Table 120.55 demands 12 kW at 8 kW, not 12 kW.
Forgetting the 25% tier — for very large dwellings, the remainder over 120,000 VA is at 25% , not 35%.
Using 90 °C column — service equipment terminations for 100 A+ are rated 75 °C per 110.14(C)(1)(b); use the 75 °C column.
Not rounding up to a standard service size — the conductor must meet the disconnect rating, not the raw calculated amps.
Standard Service Sizes and Typical Conductors
- Service Rating (A) Cu Conductor (75 °C) Table 310.16 Ampacity
- 100 3 AWG 100 A
- 125 1 AWG 130 A
- 150 1/0 AWG 150 A
- 200 2/0 AWG 175 A* → use 3/0 AWG (200 A)
- 225 4/0 AWG 230 A
- 400 600 kcmil 420 A
*When the exact conductor ampacity equals the service rating, the conductor is acceptable. When it is below, round up to the next size that meets the rating.
Exam Takeaways
2 VA/sq ft + 3,000 VA small-appliance + 1,500 VA laundry , then apply Table 120.45.
12 kW range → 8 kW demand. Dryer → larger of 5 kVA or nameplate.
Total VA ÷ 240 = amps , round up to standard service size.
Table 310.16, 75 °C column for service-entrance conductors on equipment rated 100 A or more.
Neutral uses 120.61 and the 70% range/dryer factor — the neutral conductor can be smaller than the ungrounded conductors.