15.5 Data Processing Rooms and Communications Systems
Texas Journeyman Electrician License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling
2 NEC Structure & Navigation
2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules
3 Electrical Theory & Fundamentals
3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor
4 Services & Service Equipment
4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations
5 Separately Derived Systems & Feeders
5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations
6 Branch Circuits & Receptacles
6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits
7 Overcurrent Protection
7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection
8 Wiring Methods, Conductors & Boxes
8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards
9 Equipment Grounding & Bonding
9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections
10 Equipment, Devices & Transformers
10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)
11 Motors & Generators
11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems
12 Control Devices & Disconnecting Means
12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs
13 Dwelling Load Calculations
13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing
14 Commercial & Advanced Calculations
14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone
15 Special Occupancies & Conditions
15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems
16 Renewable Energy Technologies
16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)
17 Exam Strategy & Final Review
17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice
15.5 Data Processing Rooms and Communications Systems
Key Takeaways Explain This Topic AI
Article 645 is optional: all six conditions of 645.4 must be met before any of its allowances, such as under-floor wiring methods, may be used.
NEC 645.10 requires a means to disconnect all electronic equipment and the dedicated HVAC serving the room, with the control readily accessible at the principal exit doors, and it must close required fire/smoke dampers.
NEC 645.5(A) sizes IT branch-circuit conductors at not less than 125 percent of the total connected load, and 645.5(B) limits IT equipment power-supply cords to 15 ft.
Communications cable substitution runs one way: plenum (CMP) may replace riser (CMR) and general-purpose (CM), but a general-purpose cable may never be installed in a plenum.
2026 NEC Chapter 8 no longer stands alone; use the applicable general requirements and the new limited-energy Articles 720–750.
Start indoor limited-energy wiring lookups in Articles 720–723, overvoltage protection in 742, and grounding/bonding in 750.
Last updated: October 2026
Why This Appears Twice on the Blueprint
The PSI content outline lists Data Processing and Communications Equipment under Special Occupancies, Equipment, and Conditions on the NEC Knowledge portion (6 items) and again under the same area on the Calculations portion (3 items). It is a small share of each, but it is the sub-topic candidates are least likely to have tabbed, because Article 645 sits alone in Chapter 6 and communications rules now span the Chapter 7 limited-energy articles and Chapter 8.
- Article 645 — Information Technology Equipment
- The article is optional
This is the fact the exam is really testing. Article 645 does not require anything of an IT room. It offers alternative rules — most importantly, permission to run branch-circuit wiring and interconnecting cable in the space under a raised floor — in exchange for meeting a set of preconditions. A data room wired entirely under Chapters 1 through 4 is perfectly legal and never touches Article 645.
645.4 — the six conditions
The allowances of Article 645 apply only where all of the following are met:
A disconnecting means complying with 645.10 is provided.
A dedicated HVAC system serves the IT equipment and is separated from other areas of the occupancy, or an HVAC system serving other areas is provided with fire/smoke dampers at the room boundary.
All IT and communications equipment installed in the room is listed .
The room is occupied by, and accessible only to, persons needed for the maintenance and functional operation of the IT equipment.
The room is separated from other occupancies by fire-resistant-rated walls, floors, and ceilings with protected openings.
Only electrical equipment and wiring associated with the operation of the IT room is installed in the room.
Miss any one and none of the article's relief is available.
645.10 — the disconnecting means
A means must be provided to disconnect power to all electronic equipment in the IT equipment room or designated zone, and a similar means must disconnect power to all dedicated HVAC systems serving the room and cause all required fire/smoke dampers to close . The controls must be grouped, identified, and readily accessible at the principal exit doors . A single means is permitted to disconnect both the electronic equipment and the HVAC.
In the field this is the mushroom-head emergency power off (EPO) button beside each exit, driving a shunt trip. Two points get tested:
The disconnect is not required to disconnect lighting or other non-electronic equipment in the room.
645.10(B) permits critical operations data systems to substitute an approved procedure with monitoring and an orderly shutdown rather than a hard EPO.
645.5 — supply circuits and cables
645.5(A) — branch-circuit conductors supplying one or more units of IT equipment must have an ampacity not less than 125 percent of the total connected load. This is the calculation item hiding inside this sub-topic.
645.5(B) — IT equipment may be connected by power-supply cords not exceeding 15 ft .
645.5(E) — where the 645.4 conditions are met, listed wiring methods are permitted under a raised floor , including RMC, IMC, EMT, ENT, PVC, metal and nonmetallic wireway, surface raceway, FMC, LFMC, LFNC, and Types MI, MC, AC, and TC power and control tray cable.
Abandoned cable under a raised floor must be removed unless it is tagged for future use.
645.18 requires surge protection for critical operations data systems, and 645.25 requires an available fault current field marking based on engineering supervision.
Plenum above the room
645.3(B) points to the plenum rules where the space above an IT room is used for environmental air: general wiring per 300.22(C), and only plenum-rated cable types — Class 2/3 plenum cable, plenum fire alarm cable, Types OFNP/OFCP optical fiber, Type CMP communications cable, and Type CATVP coaxial.
Limited-Energy and Communications Lookups in 2026
Chapter 8 no longer has its former independence. Do not answer a current exam question using the old shortcut that Chapters 1–7 apply only when Chapter 8 explicitly cites them. Read the applicable general requirements together with the limited-energy provisions and their specific permissions or exceptions.
- Topic 2026 starting point
- Limited-energy wiring methods and materials Articles 720–723
- Class-specific circuit requirements Applicable limited-energy system article
- Overvoltage protection Article 742
- Grounding and bonding Article 750
- Communications outside and entering buildings Chapter 8
Article 750 now concerns limited-energy grounding and bonding. Energy management systems, formerly in Article 750, are in Article 130. The identical article number in an old edition is therefore particularly misleading.
For a structured-cabling question, identify the circuit class, cable listing, route and environment before choosing an installation rule. A general-purpose cable marking is not permission to install the cable in an environmental-air space. A plenum route requires the appropriate listed cable or an expressly permitted wiring method. Likewise, check the applicable support, separation and bonding provisions; low operating voltage does not eliminate those requirements.
An exam may describe an entrance cable exposed to lightning, an indoor cable near power conductors, or a shield requiring bonding. These are different questions. Find the rule for the exposure or installation, then follow its cross-references. The new structure replaces several old 800-series installation lookups; do not carry an old section number forward solely because the cable type is unchanged.
Reference: 2026 NEC adoption review, including the Chapter 8 and limited-energy reorganization .