8.2 Conductor Insulations and Ampacity

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

8.2 Conductor Insulations and Ampacity

Key Takeaways Explain This Topic AI

NEC 110.14(C) limits the Table 310.16 column used for terminations: 60 °C for equipment rated 100 A or less (unless marked 75 °C), 75 °C for equipment over 100 A; the 90 °C column is used for derating only

Table 310.15(C)(1) ampacity adjustment factors: 4 to 6 current-carrying conductors = 80 percent, 7 to 9 = 70 percent, 10 to 20 = 50 percent, 21 to 30 = 45 percent

The -2 suffix on an insulation type (THWN-2, XHHW-2, RHW-2, USE-2) means 90 °C rating in both wet and dry locations

240.4(D) limits overcurrent protection to 15 A for #14, 20 A for #12, and 30 A for #10 copper regardless of the higher ampacity shown in the 75 °C or 90 °C columns

A neutral conductor on a 3-wire single-phase 120/240 V system is not counted as current-carrying; a neutral on a 4-wire 3-phase wye system is counted

Last updated: August 2026

Why Conductor Ampacity Matters on the TX Journeyman Exam

Conductor sizing and ampacity calculations appear in both exam parts. The NEC Knowledge part tests your recall of insulation types, temperature ratings, and 110.14(C) termination rules. The Calculations part expects you to apply Table 310.16, apply temperature correction from Table 310.15(B)(1), and apply ampacity adjustment for more than three current-carrying conductors from Table 310.15(C)(1). Getting derating right is often the difference between passing and failing the 26-question Calculations section.

  • Article 310 — Conductors for General Wiring
  • Insulation Types and Temperature Ratings

NEC Table 310.4(A) lists conductor applications and insulation ratings. The most common types on the Journeyman exam:

  • Insulation Max Temp Common Use
  • THHN 90 °C dry General wiring in conduit
  • THWN 75 °C wet General wiring, wet locations
  • THWN-2 90 °C wet and dry General wiring, all conditions
  • XHHW 90 °C dry / 75 °C wet General wiring, industrial
  • XHHW-2 90 °C wet and dry General wiring, all conditions
  • RHH 90 °C dry General wiring, higher temperature
  • RHW 75 °C wet and dry General wiring
  • RHW-2 90 °C wet and dry General wiring
  • USE-2 90 °C wet and dry Underground service entrance

Key distinctions:

The -2 suffix means the insulation is rated 90 °C in both wet and dry locations. Conductors without the -2 suffix typically drop to 75 °C in wet locations.

USE-2 is for underground service conductors. It is not permitted inside a building because it has no flame-retardant rating unless dual-listed (for example, RHH/RHW/USE-2).

THWN (without -2) is only 75 °C in wet locations — important when derating must start from the 75 °C column instead of 90 °C.

Table 310.16 — Allowable Ampacities (Copper, 60/75/90 °C)

This is the single most important table on the exam. Below are the copper values for common sizes:

  • Size (Cu) 60 °C (TW, UF) 75 °C (THW, THWN, XHHW, USE) 90 °C (THHN, THWN-2, XHHW-2, RHH, RHW-2, USE-2)
  • 14 AWG 15 A 20 A 25 A
  • 12 AWG 20 A 25 A 30 A
  • 10 AWG 30 A 35 A 40 A
  • 8 AWG 40 A 50 A 55 A
  • 6 AWG 55 A 65 A 75 A
  • 4 AWG 70 A 85 A 95 A
  • 3 AWG 85 A 100 A 110 A
  • 2 AWG 95 A 115 A 130 A
  • 1 AWG 110 A 130 A 150 A
  • 1/0 AWG 125 A 150 A 170 A
  • 2/0 AWG 145 A 175 A 195 A
  • 3/0 AWG 165 A 200 A 225 A
  • 4/0 AWG 195 A 230 A 260 A
  • 250 kcmil 215 A 255 A 290 A

Small-conductor rule (240.4(D)): The overcurrent protection for #14, #12, and #10 copper conductors is limited to 15 A, 20 A, and 30 A respectively, regardless of the higher ampacity in the 75 °C or 90 °C columns — unless specifically permitted otherwise (motor circuits per Article 430, for example).

110.14(C) — Electrical Connections: Temperature Limitations

This rule ties Table 310.16 to real equipment. You cannot use the 90 °C ampacity for conductor sizing unless the equipment terminations are rated for 90 °C.

  • Equipment Rating Applicable Column
  • 100 A or less , or marked for 14–1 AWG conductors 60 °C column (unless the equipment is marked 75 °C)
  • Over 100 A , or marked for 1/0 AWG and larger 75 °C column (unless marked 90 °C)
  • Marked 90 °C terminations 90 °C column (rare for standard equipment)

The 90 °C column is used for derating only. You start with the 90 °C ampacity to apply temperature correction and bundling adjustment, then verify the result does not exceed the termination-temperature limit (60 °C or 75 °C column).

310.15(B)(1) — Temperature Correction

When the ambient temperature is not 30 °C (86 °F) , correct the ampacity using Table 310.15(B)(1). Key correction factors:

  • Ambient 60 °C column 75 °C column 90 °C column
  • 21–25 °C 1.08 1.05 1.04
  • 26–30 °C 1.00 1.00 1.00
  • 31–35 °C 0.91 0.94 0.96
  • 36–40 °C 0.82 0.88 0.91
  • 41–45 °C 0.71 0.82 0.87
  • 46–50 °C 0.58 0.75 0.82
  • 310.15(C)(1) — Ampacity Adjustment for Number of Conductors

When more than three current-carrying conductors are in a raceway or cable, reduce the ampacity per Table 310.15(C)(1):

  • Number of Current-Carrying Conductors Adjustment Factor
  • 1–3 100%
  • 4–6 80%
  • 7–9 70%
  • 10–20 50%
  • 21–30 45%
  • 31–40 40%
  • 41 and above 35%

What counts as a current-carrying conductor?

Ungrounded (hot) conductors: always count.

Neutral conductor of a 3-wire single-phase 120/240 V circuit: does not count (balanced).

Neutral conductor of a 4-wire 3-phase wye circuit: counts (harmonics and unbalanced current).

Equipment grounding conductors: do not count .

3-way switch travelers: count (they carry current).

Worked Example — Derating Six #12 THHN at 40 °C

Problem: Six current-carrying #12 THHN copper conductors are installed in EMT in a 40 °C ambient. What is the maximum allowable ampacity?

Step 1 — Base ampacity: #12 THHN is 90 °C rated. Table 310.16, 90 °C column = 30 A .

Step 2 — Temperature correction: 40 °C ambient, 90 °C column factor = 0.91 .

30 A × 0.91 = 27.3 A.

Step 3 — Adjustment for 4–6 conductors: Factor = 0.80 .

27.3 A × 0.80 = 21.84 A .

Step 4 — Termination limit (110.14(C)): Equipment rated 100 A or less, not marked otherwise, uses the 60 °C column = 20 A .

Step 5 — Final ampacity: The lower of 21.84 A and 20 A = 20 A .

The derating does not reduce the conductor below the termination limit, so a standard 20 A breaker still protects this circuit. If the result had been below 20 A, you would either upsize the conductor or reduce the breaker rating.