Study guide

8.3 Conduit and Raceway Fill

Texas Journeyman Electrician License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the Texas Journeyman Electrician Exam 1.2 The Two-Part Exam Format (Knowledge + Calculations) 1.3 Eligibility, Application & Scheduling

2 NEC Structure & Navigation

2.1 Key NEC Definitions (Article 100) 2.2 How the NEC is Organized 2.3 NEC Index and Quick Lookup Strategies 2.4 Reading Electrical Plans, Symbols, and Schedules

3 Electrical Theory & Fundamentals

3.1 Ohm's Law, Power, and Series/Parallel Circuits 3.2 Conductors, Resistance, and Voltage Drop 3.3 Three-Phase Systems and Power Factor

4 Services & Service Equipment

4.1 Service Entrance Conductors and Service Point 4.2 Service Disconnecting Means 4.3 Grounding Electrode Systems for Services 4.4 Service Load Calculations

5 Separately Derived Systems & Feeders

5.1 Separately Derived Systems 5.2 Feeder Sizing, Ampacity, and Tap Rules 5.3 Feeder Load Calculations

6 Branch Circuits & Receptacles

6.1 Branch Circuit Sizing and Conductor Selection 6.2 Receptacle Spacing and Required Outlets 6.3 GFCI and AFCI Requirements 6.4 Lighting Outlets and Switch-Controlled Circuits

7 Overcurrent Protection

7.1 Overcurrent Principles and OCPD Types 7.2 Small-Conductor and Continuous-Load Rules 7.3 Motor Overcurrent and Short-Circuit Protection

8 Wiring Methods, Conductors & Boxes

8.1 Wiring Methods and Raceways 8.2 Conductor Insulations and Ampacity 8.3 Conduit and Raceway Fill 8.4 Boxes and Box Fill 8.5 Cable Trays and Underground Wiring 8.6 Cabinets, Cutout Boxes, and Panelboards

9 Equipment Grounding & Bonding

9.1 Equipment Grounding Conductors 9.2 Bonding & the Effective Ground-Fault Current Path 9.3 Equipment and Box Grounding Connections

10 Equipment, Devices & Transformers

10.1 Luminaires and Lighting (NEC Article 410) 10.2 Switches and Device Wiring (NEC Articles 404 & 400) 10.3 Appliances and Utilization Equipment (NEC Articles 422 & 424) 10.4 Transformers (NEC Article 450) 10.5 Working Space and Equipment Access (NEC 110.26)

11 Motors & Generators

11.1 Motor Branch Circuits & Conductors 11.2 Motor Disconnects, Controllers & Starters 11.3 Generators & Emergency Systems

12 Control Devices & Disconnecting Means

12.1 General Disconnecting Means Principles 12.2 HVAC and Refrigeration Disconnects 12.3 Motor Control Circuits and VFDs

13 Dwelling Load Calculations

13.1 General Lighting and Receptacle Load 13.2 Appliance, Range, and Dryer Load 13.3 Neutral Load and Service Sizing

14 Commercial & Advanced Calculations

14.1 Commercial Lighting and Receptacle Load 14.2 Continuous Loads and Equipment Demand 14.3 Voltage Drop and Conductor Sizing 14.4 Commercial Building Load Capstone

15 Special Occupancies & Conditions

15.1 Hazardous (Classified) Locations — NEC Articles 500–506 15.2 Health Care Facilities — NEC Article 517 15.3 Pools, Spas, and Fountains — NEC Article 680 (Beyond GFCI) 15.4 Other Specific Occupancies — A Survey 15.5 Data Processing Rooms and Communications Systems

16 Renewable Energy Technologies

16.1 Solar PV Systems (Article 690) 16.2 Energy Storage and EV Charging (Articles 706, 625)

17 Exam Strategy & Final Review

17.1 Time Management and NEC Lookup Speed 17.2 Test Day and Final Practice

8.3 Conduit and Raceway Fill

Key Takeaways Explain This Topic AI

NEC Chapter 9 Table 1 fill percentages: 1 conductor = 53 percent, 2 conductors = 31 percent, 3 or more conductors = 40 percent (wire-type)

Common THHN stranded copper areas from Table 5: #14 = 0.0097 in², #12 = 0.0133 in², #10 = 0.0211 in², #8 = 0.0366 in², #6 = 0.0507 in²

Chapter 9 Note 2 requires rounding up to the next larger standard trade size whenever the calculated minimum falls between standard sizes

For 3 or more conductors, compare total conductor area directly to the 40 percent fill column in Table 4 — the percentage is already applied

Annex C lists pre-calculated maximum conductor counts for common raceway and conductor combinations and should match your manual Chapter 9 calculation

Last updated: August 2026

Why Conduit Fill Matters on the TX Journeyman Exam

Conduit fill calculations are a Calculations-part staple. The exam gives you a number and type of conductors plus a raceway type, then asks for the minimum trade size — or the maximum number of conductors that fit in a given raceway. The method is mechanical (look up areas, divide, compare), but you must know which NEC table to use, how to apply the fill percentages, and when to round.

NEC Chapter 9 — Tables for Raceway Fill

Chapter 9 of the NEC provides the tables used for raceway fill calculations. They are separate from the conduit body articles (342 through 362) and apply universally.

Table 1 — Percent of Cross Section

The fill percentage depends on the number of conductors , not the type of raceway:

  • Number of Conductors All Wire Types
  • 1 53%
  • 2 31%
  • 3 40%
  • 4 or more 40%

The 40 percent rule for three or more conductors is the most common scenario on the exam. Use Table 5A for compact-strand conductors (slightly smaller areas).

Note 2 to Chapter 9 Table 1 — Rounding

Where the computation of the minimum size of the raceway results in a decimal less than the next larger standard size, the next larger standard size shall be used.

You always round up to the next standard trade size. You never round down. If your calculation requires 0.316 in² of total area and the next standard size offers 0.346 in² in the 40 percent column, that is the minimum.

Table 5 — Conductor Cross-Sectional Areas (Wire Types)

Table 5 gives the area of individual conductors in square inches . Common THHN/THWN-2 (stranded copper) values:

  • Size THHN/THWN-2 Area (in²)
  • 14 AWG 0.0097
  • 12 AWG 0.0133
  • 10 AWG 0.0211
  • 8 AWG 0.0366
  • 6 AWG 0.0507
  • 4 AWG 0.0835
  • 2 AWG 0.1162
  • Table 4 — Raceway Cross-Sectional Areas

Table 4 gives the total internal area of each raceway type at 100 percent, plus the pre-calculated fill areas at 53 percent, 31 percent, and 40 percent. For EMT (Article 358), common values:

  • Trade Size Metric Total Area (in²) 40% Fill (in²)
  • 1/2 in. 16 0.304 0.122
  • 3/4 in. 21 0.533 0.213
  • 1 in. 27 0.864 0.346
  • 1-1/4 in. 35 1.496 0.598
  • 1-1/2 in. 41 2.036 0.814
  • 2 in. 53 3.376 1.350

When calculating fill for three or more wires , compare the total conductor area directly to the 40 percent column — the NEC has already applied the percentage for you.

Annex C — Number of Conductors in Raceway

Annex C is a shortcut: for many common conductor and raceway combinations, it lists the maximum number of conductors that fit in each trade size without any calculation. Annex C is informational (not enforceable code text) but is fully derived from Chapter 9 Tables, so it should always match your manual calculation. Use it as a check on your work.

Worked Example — Minimum EMT Trade Size for 6 #10 THHN

Problem: Find the minimum EMT trade size for 6 THHN #10 copper conductors .

Step 1 — Conductor area:

From Table 5, #10 THHN = 0.0211 in².

6 × 0.0211 = 0.1266 in² .

Step 2 — Fill percentage:

6 conductors = more than 2, so use the 40 percent fill (Table 1).

Step 3 — Compare to Table 4 40% column for EMT:

Trade Size 40% Fill (in²) Fits?

  • 1/2 in. 0.122 0.1266 > 0.122 → No
  • 3/4 in. 0.213 0.1266 ≤ 0.213 → Yes

Answer: The minimum EMT trade size is 3/4 in. (metric designator 21).

Alternative method: divide the conductor area by 0.40 and compare to the total area column. 0.1266 ÷ 0.40 = 0.3165 in² required total area. The 3/4 in. EMT total area is 0.533 in², and 0.3165 ≤ 0.533, so 3/4 in. fits. Both methods produce the same result — pick one and be consistent.

Minimum Trade Size and Pull Rules

Each raceway article sets a minimum trade size. For most metal and nonmetallic raceways, the minimum is 1/2 in. (metric 16) . Conductors must be installed so the insulation is not damaged:

300.14 — At least 6 in. of free conductor at each box, with at least 3 in. outside the box opening.

342.22, 344.22, 358.22 (and similar for other raceways) — Conductors #4 AWG and larger require a bushing or listed fitting at the termination to protect from abrasion.

300.34 — Conductors must not be drawn into raceways in a way that damages the insulation.

Maximum Conductors in a Given Raceway

When the exam asks for the maximum number of a given conductor in a specific raceway, divide the 40 percent fill area by the conductor area and round down (you cannot exceed the fill). Example: maximum #10 THHN in 1 in. EMT:

1 in. EMT 40% fill = 0.346 in².

0.346 ÷ 0.0211 = 16.39 → round down → 16 conductors maximum .

You round down for maximum count (you cannot fit a partial conductor) but round up for minimum raceway size (Note 2).