5.2 Inspection/Test, Yellow and Red Labels and Impairment Notice
Texas Fire Alarm Installer License Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Texas Insurance Code Chapter 6002 Foundations
1.1 Chapter 6002 Purpose, Scope & Statutory Definitions 1.2 State Preemption and the Limits of Local Regulation 1.3 Commissioner and SFMO Authority; Adopted Standards and Editions 1.4 Activities Not Regulated: The § 6002.155 Exemptions 1.5 Required Device Labels, Listings and Consumer Information
2 Chapter 2: Certificates of Registration and Company Operating Rules
2.1 Registration Certificates: Main Office, Branch Office and Single Station 2.2 Insurance Requirements for Registered Firms 2.3 Business Location, Designated Employee and Vehicle Identification (§ 34.610) 2.4 Ownership Changes, Officer Changes and Revised Certificates
3 Chapter 3: Individual Licenses, Qualifying Tests and Renewal
3.1 The Six Texas Fire Alarm Licenses and What Each May Do 3.2 License Applications, Fingerprinting and Criminal History 3.3 The Qualifying Tests: TFM11, TFM12, TFM13, TFM14 and Their References 3.4 NICET, ESA and Professional Engineer Substitutions 3.5 Fees, the Two-Year Renewal Cycle and Late Renewal 3.6 Training Schools, Instructors and the Residential Technician Course
4 Chapter 4: Texas Field Practice — Installation, Service, Monitoring and Certification
4.1 Sales, Installation and Service Rules (§ 34.616) 4.2 Monitoring Requirements for Registered Firms (§ 34.616(c)) 4.3 The Installation Certificate (SF035) and Its Distribution 4.4 The Three-Stage Installation Inspection (§ 34.618) 4.5 Fire Alarm Plans and Record Drawings (§ 34.619)
5 Chapter 5: Texas Labels, Records and Enforcement
5.1 Installation and Service Labels (§§ 34.620–34.621) 5.2 Inspection/Test, Yellow and Red Labels and Impairment Notice 5.3 The Texas Recordkeeping and Retention Map 5.4 Prohibited Practices, Discipline, Enforcement and Penalties
6 Chapter 6: NFPA 72 Fundamentals, Power, Signals and Pathways
6.1 Identifying the Applicable NFPA Standards for TFM12 6.2 NFPA 72 Scope, Organization & Core Life Safety Definitions 6.3 NFPA 72 Documentation and Personnel Qualifications 6.4 Types of Equipment and Circuits: IDC, NAC, SLC and System Architectures 6.5 Signal Priority, Annunciation and Monitoring Integrity 6.6 Primary & Secondary Power Supply Calculations 6.7 Principles of Electricity and Notification Circuit Voltage Drop 6.8 Initiating & Notification Circuit Pathways (Class A, B, N, X) 6.9 Pathway Survivability, Shared Pathways and Circuit Separation
7 Chapter 7: Initiating Devices and Detection
7.1 Smoke, Heat & Flame Detection Principles & Spacing Rules 7.2 Gas Detection, Carbon Monoxide Detection and Special-Application Devices 7.3 Detector Selection and Environmental Limits 7.4 Duct Smoke Detectors, HVAC Controls & Specialized Sensors 7.5 Manual Fire Alarm Boxes, Waterflow Switches & Supervisory Initiating Devices 7.6 Sprinkler, Suppression and Releasing Service Interface
8 Chapter 8: Notification Appliances, Emergency Communications and Control Functions
8.1 Audible Notification Requirements & Sound Level Standards 8.2 Visible Notification Spacing, Synchronization & Candela Ratings 8.3 Emergency Communications Systems & Mass Notification Integration 8.4 Emergency Control Functions: Elevators, HVAC, Doors and Egress 8.5 Protected Premises Systems and the Sequence of Operation
9 Chapter 9: Wiring Methods, Supervising Stations and Inspection, Testing and Maintenance
9.1 NEC Article 760 Wiring Methods, Cable Classes & Circuit Protection 9.2 NEC Article 300 Wiring Methods and Installation Workmanship 9.3 Supervising Station Monitoring Systems & Signal Transmission Methods 9.4 Public Emergency Alarm Reporting Systems and Auxiliary Systems 9.5 Periodic Inspection, Testing & Impairment Procedures 9.6 System Acceptance Testing, Commissioning & Maintenance Records
5.2 Inspection/Test, Yellow and Red Labels and Impairment Notice
Key Takeaways Explain This Topic AI
Inspection/test labels are blue with printed black lettering and must remain in place for at least five years (§ 34.622(f)–(g)).
For a new installation, an inspection/test label may only be applied after the system has been accepted by the local AHJ (§ 34.622(c)).
A yellow label means the system does not comply with applicable codes and adopted standards or is not being tested or maintained accordingly; written notice to the owner and local AHJ must be postmarked, emailed, faxed, or hand delivered within five business days (§ 34.623(a), (c)).
A red label means the system or a part of it is inoperable, has a fault condition, or is impaired from normal operation, excluding areas under construction (§ 34.624(a)).
If the system is inoperable, the licensee must orally notify the owner and local AHJ immediately and provide written notice within the next business day; for a fault condition or impairment, written notice is due within three business days (§ 34.624(c)).
Last updated: August 2026
Why This Section Matters
These three rules contain the only hard impairment notification clocks in Texas fire alarm law. They are precise, they differ from one another, and they differ from the timelines used in other states — which is exactly why exam writers like them.
- 1. The Inspection/Test Label (§ 34.622)
- When it goes on
"After the inspection and testing of a fire alarm system, a fire alarm inspection/test label must be completed in detail and affixed to either the inside or outside of the control panel cover or, if the system has no panel, in a permanent location. The signature of the licensee on the inspection/test label certifies that the inspection and tests performed comply with requirements of the adopted standards. "
Two conditional rules follow:
§ 34.622(b): If any service or maintenance is performed under the inspection or test, a service label , in addition to the inspection/test label, must be completed and attached.
§ 34.622(c): For new installation, an inspection/test label may only be applied AFTER the system has been accepted by the local AHJ.
Deficiencies found during inspection (§ 34.622(d)–(e))
If during any inspection or test the system does not comply with applicable standards adopted at the time it was installed, has a fault condition, or is impaired, the owner or representative and the local AHJ must be notified and the licensee must attach the appropriate yellow or red label in addition to the inspection/test label. The local AHJ must be notified when the fault or impairment has been corrected.
Specification and content
- Attribute Requirement
- Color Blue with printed black lettering
- Size Approximately 3 in. × 3 in. , adhesive allowing removal
- Stacking About ½ inch of top-back adhesive, over the previous inspection/test label
- Retention At least 5 years , then removable by a licensed employee or agent of a registered firm
Required content (§ 34.622(j)): DO NOT REMOVE BY ORDER OF TEXAS STATE FIRE MARSHAL ; INSPECTION/TEST RECORD ; firm name, address, telephone number and certificate number; date of inspection, licensee's signature ( stamped signature prohibited ) and license number; the type of inspection/test performed — new installation, semi-annual, quarterly or annual ; the last date of sensitivity test, if known ; and the status after the inspection/test — acceptable, yellow label attached, or red label attached.
- 2. The Yellow Label (§ 34.623)
- The trigger
"If, after any service, inspection, or test, a system does not comply with applicable codes and adopted standards or is not being tested or maintained according to those standards , a completed yellow label must be attached to the OUTSIDE of the control panel cover or, if the system has no panel, in a permanent location, to indicate that corrective action is necessary ."
The licensee's signature on a yellow label certifies that the conditions listed on the label cause the system to be out of compliance with applicable codes and standards.
The notification clocks
Event Who must be notified Method Deadline
Attaching a yellow label Property owner, occupant or representative, and the local AHJ , in writing , indicating the non-complying conditions Postmarked, emailed, faxed, or hand delivered Within 5 business days of attachment
Removing or revising a yellow label The local AHJ must be notified when corrections are made Postmarked, emailed, faxed, or hand delivered Within 5 business days of removal
Yellow labels remain in place until the conditions are corrected and a service label is attached certifying that the corrections were made . They may be removed by a licensed employee or agent of a registered firm, an SFMO employee, or an authorized governmental representative.
Content (§ 34.623(g))
DO NOT REMOVE BY ORDER OF TEXAS STATE FIRE MARSHAL ; "SYSTEM DOES NOT COMPLY WITH APPLICABLE CODES & STANDARDS" ; firm name, address, telephone and certificate number; date attached, licensee signature (stamped prohibited) and license number; and a list of conditions resulting in the yellow label .
- 3. The Red Label (§ 34.624)
- The trigger
"If, after any service, inspection or test, a system or any part thereof is inoperable, has a fault condition, or is impaired from normal operation , excluding the area(s) of a building under construction , a completed red label must be attached to the OUTSIDE of the control panel cover … to indicate that corrective action is necessary."
Note the construction-area exclusion, and note that a red label is required for a part of a system, not only for a totally dead panel.
The split notification rule — the single most testable item
Condition Oral notice Written notice Deadline
System is inoperable Immediately after attaching the red label, orally notify the property owner, occupant or representative, and the local AHJ where available Emailed, faxed or hand delivered Within the next business day
System has a fault condition or is impaired from normal operation Not specified Written notice indicating the conditions Postmarked, emailed, faxed or hand delivered within three business days
Removing or revising a red label — Local AHJ notified when corrections are made Within five business days of removal
Red labels remain in place until the conditions are corrected and a service label is attached certifying the corrections .
Content (§ 34.624(g))
DO NOT REMOVE BY ORDER OF TEXAS STATE FIRE MARSHAL ; status of the system to be marked — inoperable, impaired, or fault ; firm name, address, telephone and certificate number; date attached, licensee signature (stamped prohibited) and license number; and a list of conditions resulting in the red label .
4. The Complete Deadline Table
- Action Deadline Rule
- Yellow label attached → written notice to owner and AHJ 5 business days § 34.623(c)
- Yellow label removed → notice to AHJ 5 business days § 34.623(d)
- Red label, system inoperable → oral notice Immediately § 34.624(c)
- Red label, system inoperable → written notice Next business day § 34.624(c)
- Red label, fault or impairment → written notice 3 business days § 34.624(c)
- Red label removed → notice to AHJ 5 business days § 34.624(d)
- Installation inspection corrective action not initiated → notify AHJ 10 calendar days § 34.618
- Installation certificate copy to AHJ 10 days § 34.617(3)
Everything in the label rules is measured in business days ; the two § 34.617/§ 34.618 deadlines are in plain or calendar days.
5. Worked Fact Patterns
Pattern A. During an annual inspection a technician finds the panel dead after a lightning strike.
→ Red label on the outside of the cover, marked inoperable . Immediately notify the owner/occupant and the local AHJ orally , and deliver written notice within the next business day .
Pattern B. A tenant build-out added four offices with no strobe coverage; the system otherwise works.
→ Yellow label — the system does not comply with applicable codes and standards. Written notice to owner and local AHJ within five business days , listing the conditions.
Pattern C. A single notification appliance circuit is open; the rest of the system functions.
→ Red label — "a system or any part thereof … has a fault condition." Written notice within three business days .
Pattern D. A newly installed system has not yet been accepted by the AHJ, and the technician wants to leave an inspection/test label.
→ Not yet. Section 34.622(c) allows an inspection/test label on a new installation only after AHJ acceptance . And § 34.620(a) forbids attaching yellow or red labels for a new installation.
Pattern E. The deficiencies on a red label are corrected.
→ Attach a service label certifying the corrections, mark the color and date of the red label on it (§ 34.621(b)), remove the red label, and notify the local AHJ within five business days .