4.1 Sales, Installation and Service Rules (§ 34.616)

Texas Fire Alarm Installer License Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Texas Insurance Code Chapter 6002 Foundations

1.1 Chapter 6002 Purpose, Scope & Statutory Definitions 1.2 State Preemption and the Limits of Local Regulation 1.3 Commissioner and SFMO Authority; Adopted Standards and Editions 1.4 Activities Not Regulated: The § 6002.155 Exemptions 1.5 Required Device Labels, Listings and Consumer Information

2 Chapter 2: Certificates of Registration and Company Operating Rules

2.1 Registration Certificates: Main Office, Branch Office and Single Station 2.2 Insurance Requirements for Registered Firms 2.3 Business Location, Designated Employee and Vehicle Identification (§ 34.610) 2.4 Ownership Changes, Officer Changes and Revised Certificates

3 Chapter 3: Individual Licenses, Qualifying Tests and Renewal

3.1 The Six Texas Fire Alarm Licenses and What Each May Do 3.2 License Applications, Fingerprinting and Criminal History 3.3 The Qualifying Tests: TFM11, TFM12, TFM13, TFM14 and Their References 3.4 NICET, ESA and Professional Engineer Substitutions 3.5 Fees, the Two-Year Renewal Cycle and Late Renewal 3.6 Training Schools, Instructors and the Residential Technician Course

4 Chapter 4: Texas Field Practice — Installation, Service, Monitoring and Certification

4.1 Sales, Installation and Service Rules (§ 34.616) 4.2 Monitoring Requirements for Registered Firms (§ 34.616(c)) 4.3 The Installation Certificate (SF035) and Its Distribution 4.4 The Three-Stage Installation Inspection (§ 34.618) 4.5 Fire Alarm Plans and Record Drawings (§ 34.619)

5 Chapter 5: Texas Labels, Records and Enforcement

5.1 Installation and Service Labels (§§ 34.620–34.621) 5.2 Inspection/Test, Yellow and Red Labels and Impairment Notice 5.3 The Texas Recordkeeping and Retention Map 5.4 Prohibited Practices, Discipline, Enforcement and Penalties

6 Chapter 6: NFPA 72 Fundamentals, Power, Signals and Pathways

6.1 Identifying the Applicable NFPA Standards for TFM12 6.2 NFPA 72 Scope, Organization & Core Life Safety Definitions 6.3 NFPA 72 Documentation and Personnel Qualifications 6.4 Types of Equipment and Circuits: IDC, NAC, SLC and System Architectures 6.5 Signal Priority, Annunciation and Monitoring Integrity 6.6 Primary & Secondary Power Supply Calculations 6.7 Principles of Electricity and Notification Circuit Voltage Drop 6.8 Initiating & Notification Circuit Pathways (Class A, B, N, X) 6.9 Pathway Survivability, Shared Pathways and Circuit Separation

7 Chapter 7: Initiating Devices and Detection

7.1 Smoke, Heat & Flame Detection Principles & Spacing Rules 7.2 Gas Detection, Carbon Monoxide Detection and Special-Application Devices 7.3 Detector Selection and Environmental Limits 7.4 Duct Smoke Detectors, HVAC Controls & Specialized Sensors 7.5 Manual Fire Alarm Boxes, Waterflow Switches & Supervisory Initiating Devices 7.6 Sprinkler, Suppression and Releasing Service Interface

8 Chapter 8: Notification Appliances, Emergency Communications and Control Functions

8.1 Audible Notification Requirements & Sound Level Standards 8.2 Visible Notification Spacing, Synchronization & Candela Ratings 8.3 Emergency Communications Systems & Mass Notification Integration 8.4 Emergency Control Functions: Elevators, HVAC, Doors and Egress 8.5 Protected Premises Systems and the Sequence of Operation

9 Chapter 9: Wiring Methods, Supervising Stations and Inspection, Testing and Maintenance

9.1 NEC Article 760 Wiring Methods, Cable Classes & Circuit Protection 9.2 NEC Article 300 Wiring Methods and Installation Workmanship 9.3 Supervising Station Monitoring Systems & Signal Transmission Methods 9.4 Public Emergency Alarm Reporting Systems and Auxiliary Systems 9.5 Periodic Inspection, Testing & Impairment Procedures 9.6 System Acceptance Testing, Commissioning & Maintenance Records

4.1 Sales, Installation and Service Rules (§ 34.616)

Key Takeaways Explain This Topic AI

Installation of all fire detection and fire alarm devices or systems, including monitoring equipment, must be performed by or under the direct on-site supervision of a licensed FAL, RAL, RAS, or APS for the work permitted by that license (§ 34.616(b)(1)).

The certifying licensee, licensed under the ACR number of the firm responsible for the installation, must be present for the final acceptance test prior to certification (§ 34.616(b)(1)).

The firm responsible for planning can be different from the firm responsible for installation, but the planner must be licensed under the planning firm's ACR number (§ 34.616(b)(1)).

Like-for-like equipment replacement determined by an APS may be considered a repair; the replaced equipment must comply with currently adopted standards but the entire system is not automatically required to be updated, and the AHJ must be consulted (§ 34.616(b)(5)).

On request of the system owner, a registered firm must provide all passwords including site-specific software, though it may withhold them until the owner signs the firm's liability waiver (§ 34.616(b)(6)).

Last updated: August 2026

Why This Section Matters

If TFM11 has a "how do I actually run a job in Texas" section, this is it. Section 34.616(b) answers four questions that come up on every project: who must be there, whose ACR number applies, what counts as a repair, and what the owner is entitled to receive.

1. Direct On-Site Supervision (§ 34.616(b)(1)–(2))

"The installation of all fire detection and fire alarm devices or systems, including monitoring equipment ... must be performed by or under the direct on-site supervision of a licensed fire alarm technician, residential fire alarm technician, residential fire alarm superintendent, or a fire alarm planning superintendent for the work permitted by the license ."

The identical requirement applies to maintenance or servicing in § 34.616(b)(2).

"Direct supervision" is a defined term. 28 TAC § 34.606(8): "The control of work, excluding the installation of conduit, raceways, junction boxes, back boxes, or similar electrical enclosures, as it is being performed on fire detection or fire alarm devices and systems by a licensed fire alarm technician or a licensed fire alarm planning superintendent."

Two consequences fall out of that definition:

Rough-in raceway work is carved out. Installing conduit, raceways, junction boxes, back boxes, and similar enclosures is expressly excluded from the definition of direct supervision — which is how electrical contractors lawfully rough in a job before the alarm contractor arrives.

"Direct" means "on-site" and contemporaneous — "as it is being performed." Phone supervision from another job is not supervision.

The phrase "for the work permitted by the license" limits each supervisor to their own scope: an RAL may supervise only work in a single-family or two-family dwelling (§ 6002.154(d-1)).

2. Which ACR Number Applies

  • Role Whose ACR number the licensee must be licensed under
  • Planner The registered firm responsible for the planning
  • Certifier The registered firm responsible for the installation
  • Licensee attaching a label The primary registered firm (§ 34.616(b)(2))

Section 34.616(b)(1) closes with the sentence that makes split projects legal: "The registered firm responsible for the planning of the fire devices or system can be different from the firm responsible for the installation."

28 TAC § 34.606(19) defines primary registered firm as "the registered fire alarm company with the responsibility for the fire alarm system certification." So when a design-build firm plans a system and a second firm installs it, the installing firm certifies and its licensee attaches the labels.

The certifier must be physically present. "The certifying licensee ... must be present for the final acceptance test prior to certification." Certifying a system from paperwork you did not witness is a direct rule violation and a § 6002.301(3) prohibited practice.

3. Crossing Trades (§ 34.616(b)(3))

"If the installation or servicing of a fire alarm system also includes installation or servicing of any part of a fire protection sprinkler system or a fire extinguisher system , the licensing requirements of Insurance Code Chapters 6001 and 6003 must be satisfied, as appropriate."

  • Chapter 6001 — Fire Protection Sprinkler System Service and Installation
  • Chapter 6003 — Fire Extinguisher Service and Installation

Wiring a tamper switch to the panel is fire alarm work. Installing the tamper switch on the valve, or servicing the kitchen hood suppression system it monitors, reaches into Chapter 6001/6003 territory and requires those separate credentials.

4. Which Edition Applies (§ 34.616(b)(4))

Planning, installation, and servicing must follow the standards adopted in § 34.607 — except when the planning and installation complies with an edition of the standard previously adopted by the political subdivision where the system is installed. That is the field-level counterpart to § 6002.003(b)(2), which lets local government require a better system than the state minimum.

5. Repair vs. Modification (§ 34.616(b)(5))

This is the most practically valuable rule in Subchapter F:

"Fire alarm system equipment replaced in the same location with the same or similar electrical and functional characteristics and listed to be compatible with the existing equipment, as determined by a fire alarm planning superintendent , may be considered a repair . The equipment replaced must comply with the currently adopted standards , but the entire system is not automatically required to be modified to meet the applicable adopted code. The local authority having jurisdiction must be consulted to determine whether to update the entire system to comply with the current code and if plans or a permit is required prior to making the repair."

Five conditions must all hold: same location , same or similar electrical and functional characteristics , listed compatible , determined by an APS , and the new component itself meets current standards . Then the AHJ consultation is mandatory, not optional.

Work Repair or installation?

Swapping a failed horn/strobe for a listed-compatible model of the same candela in the same box, APS-determined Repair

Replacing that appliance with a higher-candela unit at a new location Installation — device relocation and change

Replacing a failed smoke detector head with the same listed model Repair

Replacing an obsolete panel with a different manufacturer's panel Installation — new planning, certificate, and label

6. The Password Rule (§ 34.616(b)(6))

"On request of the owner of the fire alarm system, a registered firm must provide all passwords , including those for the site-specific software , but the registered firm may refrain from providing that information until the system owner signs a liability waiver provided by the registered firm."

Texas resolved the industry's "we own the programming" dispute in the owner's favor, with one procedural condition. The firm cannot refuse outright; it can only condition delivery on a signed waiver.

7. Recordkeeping (§ 34.616(d))

"The firm must keep complete records of all service, maintenance, and testing on the system for a minimum of two years . The records must be available for examination by the state fire marshal or the state fire marshal's representative."

Two years is the retention period for service, maintenance, and testing records — not for everything. Installation certificates, installation inspection forms, and residential drawings have their own, longer periods (see § 5.3 of this guide).