Study guide
7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency
Texas Air Conditioning and Refrigeration Contractor License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library
2 Chapter 1: Texas Licensing Laws & TDLR Regulations
1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education
3 Chapter 2: Thermodynamics & Core HVAC Principles
2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure
4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)
3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments
5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition
4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation
6 Chapter 5: Refrigeration Cycle & Core System Components
5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves
7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality
6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms
8 Chapter 7: Heating Systems, Gas Controls & Venting
7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency
9 Chapter 8: Electrical Systems, Controls & Troubleshooting
8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control
10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)
9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support
11 Chapter 10: Commercial Refrigeration & Process Cooling Systems
10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals
12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice
11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses
7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency
Key Takeaways Explain This Topic AI
Natural gas needs roughly 10 cubic feet of air per cubic foot of gas for stoichiometric combustion (about 17:1 by mass); real burners must run 20 to 50 percent excess air because mixing is never perfect.
A combustion analyzer measures oxygen, stack temperature, ambient temperature, and carbon monoxide directly, and calculates carbon dioxide, excess air, net stack temperature, air-free CO, and combustion efficiency.
Air-free CO equals measured CO multiplied by 20.9 divided by (20.9 minus measured O2 percent); ANSI Z21.47 and ANSI/BPI-1200 both use 400 ppm air-free as the central-furnace threshold above which the appliance is unsafe and must be shut off.
Published field ranges for atmospheric gas burners run about 7 to 9 percent O2, 6.5 to 8 percent CO2, 325 to 500 degrees F stack temperature and 75 to 80 percent combustion efficiency, but the appliance rating plate and manufacturer service data govern.
Clocking the meter: CFH equals 3600 times the dial size divided by seconds per revolution; a 1 cubic foot dial timed at 36 seconds with 1,030 BTU per cubic foot gas equals 100 CFH, or 103,000 BTU per hour of input.
Last updated: August 2026
Why Combustion Analysis Is the Only Objective Proof
A gas appliance can look perfect — blue flame, warm supply air, no odor, no complaints — and still be producing dangerous carbon monoxide (CO) , running thirty percent overfired, or spilling flue gas into the room every time the dryer runs. Flame color, supply-air temperature, and the customer's impression are opinions. A combustion analysis is a measurement. It is the only way to demonstrate, on paper, that the appliance you installed or serviced is burning fuel completely, venting properly, and delivering its rated input. The TDLR content outline lists Testing — Combustion as its own sub-topic, and Modern Refrigeration and Air Conditioning , the approved reference on the exam's list, covers the same procedure.
Stoichiometric air and why excess air is unavoidable
Stoichiometric combustion is the exact air-to-fuel ratio at which every fuel molecule finds precisely the oxygen it needs — no leftover fuel, no leftover oxygen. For natural gas that ratio is approximately 10:1 by volume , about 10 cubic feet of air per cubic foot of gas, which works out to roughly 17:1 by mass . Complete combustion of methane yields carbon dioxide, water vapor, and heat:
C H 4 + 2 O 2 → C O 2 + 2 H 2 O + heat \mathrm{CH_4} + 2\,\mathrm{O_2} \rightarrow \mathrm{CO_2} + 2\,\mathrm{H_2O} + \text{heat} C H 4 + 2 O 2 → C O 2 + 2 H 2 O + heat
No field burner achieves that ratio. Fuel and air cannot blend perfectly in the fraction of a second available in the combustion zone, so a burner set at exactly 10:1 would leave unburned fuel and generate CO. Every practical burner therefore runs with excess air — commonly 20 to 50 percent above stoichiometric on residential gas equipment. Excess air is the safety margin that guarantees complete combustion, and its cost is efficiency, because every extra cubic foot of air is heated and thrown up the flue. Tuning combustion is the search for the lowest excess air that still holds CO down . That is exactly why the analyzer reports oxygen and CO side by side: one is the cost, the other is the risk.
What the Analyzer Measures Versus What It Calculates
A modern residential analyzer contains electrochemical sensors and thermocouples. On most instruments it measures only four things directly:
Oxygen (O2) in the flue gas, as a percent by volume, from an O2 cell. (A few instruments carry a direct CO2 sensor instead.)
Stack temperature , from the thermocouple in the probe tip.
Ambient or combustion air temperature , from a second thermocouple at the analyzer body.
Carbon monoxide (CO) , in parts per million, as it exists in the sample drawn through the probe.
Everything else on the display is calculated : carbon dioxide (CO2) from the measured O2 and a fuel factor, excess air , net stack temperature (stack minus ambient), air-free CO , and combustion efficiency . Combustion efficiency is a steady-state number derived from net stack temperature and O2 or CO2. It is not AFUE and it is not system efficiency — an 80 percent AFUE furnace commonly displays 78 to 82 percent combustion efficiency, while a condensing appliance displays numbers in the 90s only because its stack temperature is so much lower.
Reference table: measurement, instrument, typical range, and interpretation
Measurement Instrument / method Typical range, residential gas An out-of-range reading suggests
Oxygen (O2) Analyzer O2 cell, probe in undiluted flue gas About 7 to 9 percent for atmospheric burners; many programs teach a 6 to 9 percent target window High: excessive excess air, a leak, or a diluted sample. Low: starved for combustion air, CO risk rising
Carbon dioxide (CO2) Calculated from O2, or a direct CO2 cell About 6.5 to 8 percent; the theoretical maximum on natural gas is roughly 11.8 percent Low CO2 means high excess air and wasted heat. High CO2 paired with high CO means under-aerated combustion
Carbon monoxide (CO) Electrochemical CO cell, reported as-measured and air-free Well under 100 ppm air-free on a properly tuned appliance Flame impingement, dirty or misaligned burners, overfiring, blocked flue, or inadequate combustion air
Stack temperature Probe thermocouple in the flue Roughly 325 to 500 degrees F non-condensing; roughly 100 to 140 degrees F condensing High: overfiring, low air flow, or a fouled heat exchanger. Low on a non-condensing unit: underfiring and flue condensation risk
Draft Manometer or analyzer draft port in the vent connector Negative, roughly -0.02 to -0.04 in. w.c. on atmospheric appliances Zero or positive means spillage or blockage. Excessive negative draft means over-draft and heat loss up the flue
Manifold gas pressure Manometer at the gas valve outlet tap, burner firing Commonly 3.5 in. w.c. natural gas, 10 to 11 in. w.c. LP Off the rating plate value: wrong regulator setting, undersized piping, wrong orifice, or wrong fuel
Input rate Clock the gas meter Within roughly 5 percent of nameplate input Over nameplate: overfiring and heat exchanger stress. Under: low capacity and comfort callbacks
Say this out loud before you use any of those numbers: they are field benchmarks published for typical residential gas equipment, not code limits. The appliance rating plate, the manufacturer's service instructions, and the authority having jurisdiction govern every one of them. A condensing modulating furnace, a power burner, and a 1960s atmospheric unit will not share a target window. When a manufacturer publishes a setup table, that table wins.