Study guide
7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes
Texas Air Conditioning and Refrigeration Contractor License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library
2 Chapter 1: Texas Licensing Laws & TDLR Regulations
1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education
3 Chapter 2: Thermodynamics & Core HVAC Principles
2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure
4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)
3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments
5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition
4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation
6 Chapter 5: Refrigeration Cycle & Core System Components
5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves
7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality
6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms
8 Chapter 7: Heating Systems, Gas Controls & Venting
7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency
9 Chapter 8: Electrical Systems, Controls & Troubleshooting
8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control
10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)
9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support
11 Chapter 10: Commercial Refrigeration & Process Cooling Systems
10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals
12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice
11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses
7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes
Key Takeaways Explain This Topic AI
Electric resistance heating converts electrical energy to heat at a rate of 1 kW = 3,413 BTU/hr, using sequencers and bimetallic/thermal cutouts for safety.
Heat pumps use a 4-way reversing valve to reverse the refrigeration cycle; most brands energize terminal O in cooling, while Rheem/Ruud energize terminal B in heating.
Coefficient of Performance (COP) measures heating energy output versus electrical work input (resistance heat COP = 1.0; heat pumps COP = 2.0 to 4.5).
The thermal balance point is the outdoor temperature where heat pump heating capacity equals building heat loss, requiring auxiliary electric heat below this temperature.
During defrost, the reversing valve shifts to cooling mode, outdoor fan stops, auxiliary heat energizes, and defrost terminates on outdoor coil temperature (55-60°F) or time (10-12 min).
Last updated: August 2026
Electric Resistance Heating Fundamentals
Electric resistance heating generates thermal energy by passing electric current through high-resistance conductor elements (Joule heating). In Texas residential and commercial air handlers, electric heat packages serve as emergency heating or auxiliary supplemental heat for heat pumps.
Resistance Heating Element Mechanics
Material : Open-wire heating elements are constructed from Nichrome alloy (80% Nickel, 20% Chromium). Nichrome resists high-temperature oxidation and exhibits steady electrical resistance across high thermal operating ranges.
Insulation : Coiled Nichrome elements are suspended inside the air handler chassis on high-grade ceramic insulator bushings to isolate high voltage ( 240 V AC 240\text{V AC} 240 V AC ) from the grounded sheet metal cabinet.
Power & Thermal Conversion Formula : Electric power in kilowatts (kW) converts directly into thermal output in BTUs per hour: 1.0 kW = 3 , 413 BTU/hr 1.0 \text{ kW} = 3,413 \text{ BTU/hr} 1.0 kW = 3 , 413 BTU/hr Total Heating Capacity (BTU/hr) = kW Rating × 3 , 413 \text{Total Heating Capacity (BTU/hr)} = \text{kW Rating} \times 3,413 Total Heating Capacity (BTU/hr) = kW Rating × 3 , 413
Sample Field Conversion Calculation
An air handler is fitted with a 15 kW supplemental electric heat strip kit operating at 240 V 240\text{V} 240 V : Thermal Capacity = 15 kW × 3 , 413 BTU/kW = 51 , 195 BTU/hr \text{Thermal Capacity} = 15 \text{ kW} \times 3,413 \text{ BTU/kW} = 51,195 \text{ BTU/hr} Thermal Capacity = 15 kW × 3 , 413 BTU/kW = 51 , 195 BTU/hr
To determine electrical current draw under full load: Current (Amperes) = Power (Watts) Voltage (Volts) = 15 , 000 W 240 V = 62.5 Amperes \text{Current (Amperes)} = \frac{\text{Power (Watts)}}{\text{Voltage (Volts)}} = \frac{15,000 \text{ W}}{240 \text{ V}} = 62.5 \text{ Amperes} Current (Amperes) = Voltage (Volts) Power (Watts) = 240 V 15 , 000 W = 62.5 Amperes
Sequencers and Thermal Safety Limit Controls
Electric heat packages utilize specialized switching devices and multi-stage limit controls to protect building wiring and prevent equipment overheating.
Electric Heat Sequencers
If a 15 kW 15 \text{ kW} 15 kW or 20 kW 20 \text{ kW} 20 kW electric heat package energized simultaneously upon a thermostat call for heat, the sudden 60 − 80 Amp 60 - 80 \text{ Amp} 60 − 80 Amp current spike would trip main circuit breakers and cause severe voltage drops across the building panel. Furthermore, blowing cold air over cold elements creates initial cold air drafts.
Operation : A sequencer is a solid-state or bimetallic disc relay containing a 24V PTC (Positive Temperature Coefficient) heater disc.
Staging Delay : Upon a call for heat ( W 1 / W 2 W_1 / W_2 W 1 / W 2 ), the sequencer internal heater warms a bimetallic disc. After a 20 − 60 second 20 - 60 \text{ second} 20 − 60 second delay, the disc snaps, closing high-voltage contacts to energize Element Bank 1 and start the indoor blower fan. Successive banks energize sequentially in stages ( 20 − 60 seconds 20 - 60 \text{ seconds} 20 − 60 seconds apart). Upon thermostatic satisfaction, elements de-energize sequentially, allowing the blower fan to purge residual heat into the ductwork.
Limit Switches and Thermal Cutouts
Primary High-Limit Switch : A normally-closed bimetallic thermal switch mounted adjacent to the heat strips in the main air stream. Wired in series with the 24 V 24\text{V} 24 V sequencer coil or control circuit. If airflow drops due to a clogged air filter, broken blower belt, or failed blower motor, air temperatures inside the cabinet rise. At setpoint (typically 160 ∘ F − 180 ∘ F 160^\circ\text{F} - 180^\circ\text{F} 16 0 ∘ F − 18 0 ∘ F ), the primary limit opens, de-energizing the heating elements while keeping the blower running. Once cooled, it automatically resets .
Secondary Thermal Cutout (Thermal Fuse) : A one-time fusible link wired directly in series with the 240 V 240\text{V} 240 V high-voltage line feeding each element bank. If the primary limit switch fails or sticks closed during a severe no-airflow event, temperatures rise rapidly. At safety limit (typically 250 ∘ F − 300 ∘ F 250^\circ\text{F} - 300^\circ\text{F} 25 0 ∘ F − 30 0 ∘ F ), the alloy link melts, permanently opening high-voltage power to prevent a structural building fire. Thermal fuses cannot be reset and must be replaced.
Heat Pump Reverse Refrigeration Cycle and 4-Way Reversing Valve
A heat pump provides year-round climate control by reversing the flow of refrigerant using a 4-way reversing valve . Cooling Mode:
Compressor Discharge ---> Reversing Valve ---> Outdoor Coil (Condenser) ---> TXV ---> Indoor Coil (Evaporator) ---> Reversing Valve ---> Compressor Suction
Heating Mode:
Compressor Discharge ---> Reversing Valve ---> Indoor Coil (Condenser) ---> TXV ---> Outdoor Coil (Evaporator) ---> Reversing Valve ---> Compressor Suction
Reversing Valve Construction and Thermodynamics
Internal Slide Block : The reversing valve contains a Teflon-faced D-slide block inside a brass body. High-pressure discharge gas pushes the slide block to redirect refrigerant vapor flow.
Pilot Solenoid Valve : A 24V AC electromagnetic pilot solenoid controls small capillary tubes connected to the main valve body. Shifting the pilot solenoid creates a pressure differential between the left and right ends of the slide block, forcing the slide to shift positions.
Thermostat Terminal Conventions (O vs. B) :
Terminal Designation Solenoid Energized State Equipment Manufacturers Using Convention
O Terminal Solenoid energized in Cooling Mode ; valve rests in Heating Mode when de-energized. Carrier, Trane, Lennox, York, Goodman, Heil, Comfortmaker (Industry Standard)
B Terminal Solenoid energized in Heating Mode ; valve rests in Cooling Mode when de-energized. Rheem, Ruud
Technician Diagnostic Tip: If a thermostat is misconfigured (setting reversing valve to 'B' on a Carrier system requiring 'O'), the heat pump will operate in heating mode when cooling is called, blowing hot air into the structure during Texas summer months.
Heat Pump Efficiency Metrics and Balance Point Dynamics
Heat pump efficiency is rated by comparing energy heat output to electrical energy input.
Coefficient of Performance (COP) COP = Thermal Energy Output (Watts or BTU/hr) Electrical Energy Input (Watts or BTU/hr Equivalent) \text{COP} = \frac{\text{Thermal Energy Output (Watts or BTU/hr)}}{\text{Electrical Energy Input (Watts or BTU/hr Equivalent)}} COP = Electrical Energy Input (Watts or BTU/hr Equivalent) Thermal Energy Output (Watts or BTU/hr)
Electric Resistance Heat : Converts 1 Watt of electricity into 1 Watt of heat ( COP = 1.0 \text{COP} = \mathbf{1.0} COP = 1.0 ).
Heat Pump Performance : At mild outdoor temperatures ( 47 ∘ F 47^\circ\text{F} 4 7 ∘ F ), a modern heat pump moves 3 to 4 units of heat energy for every unit of electrical energy consumed ( COP = 3.0 − 4.5 \text{COP} = \mathbf{3.0 - 4.5} COP = 3.0 − 4.5 ). As outdoor temperature falls, air density drops and heat capacity decreases, lowering COP toward 1.5 - 2.0.
Heating Seasonal Performance Factor (HSPF / HSPF2)
HSPF : Total heating output in BTUs during the annual heating season divided by total watt-hours consumed.
HSPF2 : Updated efficiency metric under M1 testing standards (incorporating higher external static pressure test conditions). Higher numbers indicate greater seasonal efficiency.
- Thermal vs. Economic Balance Point Heat Output / Load (BTU/hr)
- ^
- | / Building Heat Loss Line
- | /
- | / Heat Pump Capacity Line
- |/ \
- +--------X-------------------------> Outdoor Ambient Temp (°F)
- Thermal Balance Point (approx. 30°F - 35°F)
Thermal Balance Point : The outdoor ambient temperature at which the heat pump's maximum heating capacity exactly equals the building's structural heat loss. Below the thermal balance point, the heat pump alone cannot maintain the indoor setpoint, requiring auxiliary electric heat strips (or gas furnace in dual-fuel systems) to energize and supplement the deficit.
Economic Balance Point : The outdoor ambient temperature at which operating supplemental electric heat or a secondary gas furnace becomes cheaper than operating the heat pump, based on local utility electric rates (cents/kWh) versus natural gas rates (dollars/therm).
Heat Pump Defrost Controls and Sequence of Operation
When a heat pump operates in heating mode with outdoor ambient temperatures below 45 ∘ F 45^\circ\text{F} 4 5 ∘ F , the outdoor coil surface temperature drops below 32 ∘ F 32^\circ\text{F} 3 2 ∘ F . Moisture in outdoor air condenses and freezes on the outdoor coil fins. Accumulated frost acts as a thermal insulator and blocks airflow, causing suction pressure to collapse.
Defrost Initiation Logic
Time-Temperature Defrost : Uses an electronic timer module (selectable 30, 60, or 90 minute intervals) combined with an outdoor coil bimetal thermostat. If the coil thermostat senses temperature below freezing ( ≈ 30 ∘ F \approx 30^\circ\text{F} ≈ 3 0 ∘ F ) when the timer interval expires, defrost initiates.
Demand Defrost : Microprocessor boards measure the temperature differential ( Δ T \Delta T Δ T ) between outdoor ambient air and outdoor coil refrigerant temperature, or measure air pressure drop across the outdoor coil face. Defrost initiates only when actual frost accumulation restricts performance , eliminating unnecessary defrost cycles and saving significant energy.
Four Concurrent Steps of a Defrost Cycle
When defrost initiates, the control board executes four simultaneous control actions: Defrost Initiation:
- 1. Reversing Valve Shifts to COOLING (Hot gas melts outdoor ice)
- 2. Outdoor Fan De-energizes (Traps heat at outdoor coil)
- 3. Auxiliary Heat Energizes (Prevents cold indoor draft)
- 4. Compressor Continues Running (Drives thermodynamic cycle)
Reversing Valve Shifts to Cooling Mode : The 4-way valve solenoid shifts refrigerant flow, directing high-pressure, high-temperature discharge gas into the outdoor coil to rapidly melt ice.
Outdoor Fan Motor Shuts Off : De-energizing the outdoor fan prevents freezing outdoor ambient air from blowing across the coil, trapping heat inside the outdoor cabinet to accelerate ice melt.
Auxiliary Electric Heat Energizes (W2/E Terminal) : Because the heat pump is operating in cooling mode during defrost, cold air would dump into the living space. The defrost board energizes indoor electric heat strips to temper the air stream.
Compressor Continues Running : The compressor remains operational to pump hot gas through the outdoor coil.
Defrost Termination
Defrost terminates when either:
The outdoor coil bimetal sensor/thermistor warms up to its termination setpoint (typically 55 ∘ F − 60 ∘ F 55^\circ\text{F} - 60^\circ\text{F} 5 5 ∘ F − 6 0 ∘ F ), proving all frost has melted, or
The maximum override safety time limit (usually 10 to 12 minutes ) is reached.