3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments

Texas Air Conditioning and Refrigeration Contractor License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library

2 Chapter 1: Texas Licensing Laws & TDLR Regulations

1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education

3 Chapter 2: Thermodynamics & Core HVAC Principles

2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure

4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)

3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments

5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition

4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation

6 Chapter 5: Refrigeration Cycle & Core System Components

5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves

7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality

6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms

8 Chapter 7: Heating Systems, Gas Controls & Venting

7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency

9 Chapter 8: Electrical Systems, Controls & Troubleshooting

8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control

10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)

9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support

11 Chapter 10: Commercial Refrigeration & Process Cooling Systems

10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals

12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice

11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses

3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments

Key Takeaways Explain This Topic AI

Texas design outdoor conditions vary significantly across climate zones, ranging from humid coastal zones (Houston 95°F DB / 79°F WB) to hot-arid western zones (El Paso 100°F DB / 64°F WB).

IECC and ACCA Manual J prescribe indoor design conditions of 75°F DB / 50% RH for cooling and 70°F DB for heating when computing design temperature differentials (ΔT).

High outdoor wet-bulb temperatures in East and Gulf Coast Texas produce substantial latent infiltration loads, requiring equipment matched to low Sensible Heat Ratios (SHR).

Installing radiant barriers beneath attic roof decks lowers peak attic ambient temperatures from 130°F–140°F down to 110°F–115°F, significantly reducing ceiling and attic duct heat gains.

Texas energy codes enforce R-8 minimum duct insulation in unconditioned attics to mitigate heat gains driven by extreme 80°F+ temperature differences between attic air and supply air.

Last updated: August 2026

Texas features diverse climate zones ranging from humid subtropical coastal regions to hot-arid western deserts and wind-swept northern plains. Accurate HVAC system engineering requires applying local outdoor design conditions specified in ACCA Manual J Table 1A, the International Energy Conservation Code (IECC), and ASHRAE Fundamentals.

1. Outdoor Design Temperatures Across Texas Climate Zones

Design temperatures represent statistical peak outdoor conditions (typically the 1% cooling design level and 99% heating design level), ensuring HVAC equipment handles extreme weather without excessive over-engineering.

Representative Texas Outdoor Design Conditions

City / Location IECC Climate Zone Outdoor Cooling 1% Dry-Bulb (°F) Outdoor Cooling 1% Wet-Bulb (°F) Outdoor Heating 99% Dry-Bulb (°F) Design Cooling Δ T \Delta T Δ T ( 75 ∘ F 75^\circ\text{F} 7 5 ∘ F Indoor)

  • Houston / Galveston Zone 2A (Humid) 95°F 79°F 32°F 20°F
  • Dallas-Fort Worth Zone 3A (Humid) 100°F 75°F 22°F 25°F
  • San Antonio Zone 2A (Humid) 98°F 76°F 30°F 23°F
  • Austin Zone 2A (Humid) 98°F 75°F 28°F 23°F
  • El Paso Zone 3B (Dry) 100°F 64°F 24°F 25°F
  • Lubbock (3B) / Amarillo (4B) Zone 3B / 4B 96°F 67°F 13°F 21°F
  • Brownsville / McAllen Zone 2A (Humid) 96°F 80°F 38°F 21°F
  • 2. Indoor Design Conditions and Temperature Differentials

Texas building codes (IECC / IRC) prescribe standard indoor design baselines for load calculations:

Summer Cooling Baseline : 75°F Dry-Bulb (DB) and 50% Relative Humidity (RH) (corresponding to an indoor humidity ratio of approximately 64 grains/lb 64 \text{ grains/lb} 64 grains/lb dry air).

Winter Heating Baseline : 70°F Dry-Bulb (DB) .

Design Temperature Differential ( Δ T \Delta T Δ T ) Formulae Cooling Δ T = T outdoor cooling DB − 75 ∘ F \text{Cooling } \Delta T = T_{\text{outdoor cooling DB}} - 75^\circ\text{F} Cooling Δ T = T outdoor cooling DB ​ − 7 5 ∘ F Heating Δ T = 70 ∘ F − T outdoor heating DB \text{Heating } \Delta T = 70^\circ\text{F} - T_{\text{outdoor heating DB}} Heating Δ T = 7 0 ∘ F − T outdoor heating DB ​

Example : For Dallas-Fort Worth ( 100 ∘ F DB 100^\circ\text{F}\text{ DB} 10 0 ∘ F DB cooling / 22 ∘ F DB 22^\circ\text{F}\text{ DB} 2 2 ∘ F DB heating):

  • Cooling Δ T = 100 − 75 = 25 ∘ F \Delta T = 100 - 75 = 25^\circ\text{F} Δ T = 100 − 75 = 2 5 ∘ F
  • Heating Δ T = 70 − 22 = 48 ∘ F \Delta T = 70 - 22 = 48^\circ\text{F} Δ T = 70 − 22 = 4 8 ∘ F
  • 3. High-Humidity Latent Load Challenges in East and Gulf Coast Texas

In East Texas and along the Gulf Coast (Climate Zones 1A and 2A), high outdoor wet-bulb temperatures ( 78 ∘ F– 80 ∘ F 78^\circ\text{F}\text{--}80^\circ\text{F} 7 8 ∘ F – 8 0 ∘ F ) drive substantial latent loads. When outdoor air enters through infiltration or ventilation, it introduces massive moisture loads.

Managing Low Sensible Heat Ratios (SHR)

In high humidity regions, building cooling loads often exhibit Sensible Heat Ratios ( S H R SHR S H R ) below 0.75 0.75 0.75 , meaning more than 25% of the total cooling capacity must be dedicated strictly to moisture condensation.

Lowering Blower Airflow : Standard cooling airflow is 400 CFM/ton 400 \text{ CFM/ton} 400 CFM/ton . In high-humidity regions, setting blower speed to 350 CFM/ton 350 \text{ CFM/ton} 350 CFM/ton lowers the evaporator coil saturation temperature, increasing latent moisture removal rate.

Variable-Speed Inverter Compressors : Modulating systems run prolonged cycles at lower capacities, maintaining coil temperatures below indoor dew point ( 55 ∘ F 55^\circ\text{F} 5 5 ∘ F ) to strip humidity continuously without over-cooling dry-bulb temperatures.

Supplemental Dehumidification : Integrating dedicated whole-house dehumidifiers handles latent loads independently during shoulder seasons when sensible heat gains are minimal but outdoor relative humidity remains near 100%.

4. Radiant Barrier Impact on Attic Heat Transfer

In Texas summers, solar radiation striking dark asphalt roof shingles elevates unconditioned attic temperatures up to 130 ∘ F– 140 ∘ F 130^\circ\text{F}\text{--}140^\circ\text{F} 13 0 ∘ F – 14 0 ∘ F . Heat transfers from the hot roof deck to ceiling insulation and ductwork via radiation.

Thermal Performance Benefits of Radiant Barriers

A radiant barrier consists of a highly reflective foil material (emittance ≤ 0.05 \le 0.05 ≤ 0.05 ) installed facing an open air space under the roof deck.

Attic Temperature Reduction : Installing radiant barriers lowers peak attic temperatures by 20 ∘ F– 25 ∘ F 20^\circ\text{F}\text{--}25^\circ\text{F} 2 0 ∘ F – 2 5 ∘ F (reducing peak attic temperatures from 135 ∘ F 135^\circ\text{F} 13 5 ∘ F down to 110 ∘ F– 115 ∘ F 110^\circ\text{F}\text{--}115^\circ\text{F} 11 0 ∘ F – 11 5 ∘ F ).

Ceiling Heat Load Impact : Decreases heat flux through ceiling insulation into conditioned spaces by 40 % – 50 % 40\%\text{--}50\% 40% – 50% .

Manual J HTM Adjustment : Reduces the ceiling Heat Transfer Multiplier ( H T M HTM H TM ) significantly, allowing smaller equipment selection under Manual S.

5. Duct Heat Gain and Loss in Unconditioned Texas Attics

The vast majority of residential HVAC systems in Texas locate air handlers and flex ductwork in unconditioned attics. When supply air at 55 ∘ F 55^\circ\text{F} 5 5 ∘ F passes through flex duct surrounded by 135 ∘ F 135^\circ\text{F} 13 5 ∘ F attic air, the temperature difference ( Δ T duct \Delta T_{\text{duct}} Δ T duct ​ ) exceeds 80 ∘ F 80^\circ\text{F} 8 0 ∘ F .

Duct Heat Gain Factors

Convective / Conductive Heat Gain : Heat conducted through the duct wall assembly ( Q = A duct × U duct × Δ T duct Q = A_{\text{duct}} \times U_{\text{duct}} \times \Delta T_{\text{duct}} Q = A duct ​ × U duct ​ × Δ T duct ​ ).

Duct Leakage Gains : Conditioned air leaking out of supply joints ( C F M leak CFM_{\text{leak}} CF M leak ​ ) forces hot, humid attic air into return leaks or increases envelope infiltration.

Texas Code Minimum Duct Insulation (IECC)

Texas energy codes require a minimum of R-8 insulation on supply and return ductwork located in unconditioned attics. Upgrading from R-4.2 to R-8 reduces conductive duct heat gain by over 45%. Duct Heat Gain Percentage = Q duct gain Q sensible load × 100 \text{Duct Heat Gain Percentage} = \frac{Q_{\text{duct gain}}}{Q_{\text{sensible load}}} \times 100 Duct Heat Gain Percentage = Q sensible load ​ Q duct gain ​ ​ × 100

In unsealed, poorly insulated attic duct systems (R-4.2 with 15% leakage), duct gains can add 20 % – 35 % 20\%\text{--}35\% 20% – 35% to the total Manual J cooling load. Sealing ducts to less than 4 CFM 25 / 100 sq ft 4 \text{ CFM}_{25} / 100 \text{ sq ft} 4 CFM 25 ​ /100 sq ft and insulating to R-8 reduces duct loads to less than 8 % – 10 % 8\%\text{--}10\% 8% – 10% of total cooling capacity.