Study guide
5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves
Texas Air Conditioning and Refrigeration Contractor License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library
2 Chapter 1: Texas Licensing Laws & TDLR Regulations
1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education
3 Chapter 2: Thermodynamics & Core HVAC Principles
2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure
4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)
3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments
5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition
4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation
6 Chapter 5: Refrigeration Cycle & Core System Components
5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves
7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality
6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms
8 Chapter 7: Heating Systems, Gas Controls & Venting
7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency
9 Chapter 8: Electrical Systems, Controls & Troubleshooting
8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control
10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)
9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support
11 Chapter 10: Commercial Refrigeration & Process Cooling Systems
10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals
12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice
11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses
5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves
Key Takeaways Explain This Topic AI
A three-position service valve back-seated gives full line flow with the service port closed; crack it about one turn off the back seat to gauge up; fully front-seated it closes the line and opens the port to the compressor or receiver.
Pump-down begins by front-seating the king valve at the receiver outlet, running the compressor until suction falls to roughly 2-5 psig (never into a vacuum), then front-seating the suction service valve right after the compressor stops.
IMC 2021 Section 1101.9 requires locking-type tamper-resistant caps on refrigerant circuit access ports located outdoors, and Section 1102.3 requires that protection whenever refrigerant is added to or recovered from a system.
Filter-driers are directional: the arrow points downstream, and a heat pump needs a bi-flow drier or two driers piped with check valves; suction-line burnout driers get access valves on both ends so pressure drop can be measured, commonly limited to about 2-3 psi on air conditioning and less on low-temperature work.
Bubbles in a sight glass prove flash gas in the liquid line, not undercharge - a restricted liquid-line drier will bubble the glass with a full charge, so charge to measured subcooling and superheat instead.
Last updated: August 2026
Why valves and accessories carry weight on this exam
The Texas Department of Licensing and Regulation (TDLR) content outline lists Valves as a named sub-topic under Piping , and the accessories that live in the liquid and suction lines also feed the Basic Refrigeration Components and Service areas. On both Commercial Refrigeration endorsement exams these appear in two flavors: isolation-and-recovery questions (how do I get the charge out of the way without venting it?) and diagnostic questions (what does this device do when it fails?).
Because the exam is open book, you are not expected to memorize a manufacturer's part numbers. You are expected to know which valve position does what, which way a filter-drier flows, and what a bubbling sight glass actually proves. A fast triage that eliminates two answers on most items: every device below is either an isolation device, a flow-control device, or an access device.
Three-position service valves: back seat, mid seat, front seat
A front-seating service valve - the brass valve bolted to a compressor body or threaded into a receiver outlet - has three connections: a line port to the system, a component port to the compressor or receiver, and a service port for a gauge hose. A square or hex stem drives a plug between two seats.
- Stem position How to get there Line port Service port When it is used
- Back-seated Stem fully counterclockwise (backed out) Open Closed Normal running position; gauges read nothing
Cracked off the back seat Back-seat, then turn in about one turn Open Open Normal way to gauge up a running system
Mid-seated Stem midway between seats Open Open Charging, recovery, and evacuation through the valve
Front-seated Stem fully clockwise (screwed in) Closed Open to the component Isolating the compressor or receiver for service
The king valve is simply the service valve at the outlet of the liquid receiver . Front-seating it blocks liquid from leaving the receiver, which is exactly what makes a pump-down possible. The suction service valve and discharge service valve sit on the compressor and isolate it from the rest of the system.
Two hard rules worth remembering. First, never run a compressor with the discharge service valve front-seated - there is nowhere for the discharge gas to go. ANSI/ASHRAE Standard 15 requires that a positive-displacement compressor fitted with a stop valve in its discharge connection be protected by a pressure-relief device sized so pressure cannot rise more than 10 percent above the maximum allowable working pressure (MAWP) of any component between the compressor and that stop valve. Second, never leave a compressor running with the suction service valve front-seated; it will pull itself into a deep vacuum and can draw air and moisture in through any low-side leak.
The pump-down sequence
Pumping down stores the charge in the condenser and receiver so the compressor can be changed without recovering the whole system. The order matters:
Gauge up: crack the suction service valve off its back seat and connect to the king valve service port.
With the system running, slowly front-seat the king valve (stem clockwise). This is the step that starts the pump-down.
Watch suction pressure fall. Stop the compressor at roughly 2-5 psig positive pressure . Pulling the low side into a vacuum invites air, moisture, and contamination through any leak or shaft seal.
Front-seat the suction service valve immediately after the compressor stops, before pressure equalizes back through the compressor.
Expect pressure creep. Trapped liquid boils off and refrigerant leaks past valve plates, so many technicians restart briefly and repeat, or open the suction valve slightly and pump down a second time.
Remember that a pump-down still leaves the compressor body holding refrigerant. That residual charge must be recovered with certified recovery equipment under EPA Section 608 before the compressor is opened or cut out - it is never vented.