2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat

Texas Air Conditioning and Refrigeration Contractor License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library

2 Chapter 1: Texas Licensing Laws & TDLR Regulations

1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education

3 Chapter 2: Thermodynamics & Core HVAC Principles

2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure

4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)

3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments

5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition

4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation

6 Chapter 5: Refrigeration Cycle & Core System Components

5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves

7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality

6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms

8 Chapter 7: Heating Systems, Gas Controls & Venting

7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency

9 Chapter 8: Electrical Systems, Controls & Troubleshooting

8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control

10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)

9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support

11 Chapter 10: Commercial Refrigeration & Process Cooling Systems

10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals

12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice

11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses

2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat

Key Takeaways Explain This Topic AI

The First Law of Thermodynamics dictates energy conservation, while the Second Law dictates that heat flows naturally from higher to lower temperature bodies unless external work is performed.

Sensible heat causes a dry-bulb temperature change without a phase change ( Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s ​ = 1.08 × CFM × Δ T ), whereas latent heat causes a state change at constant temperature ( Q l = 4840 × CFM × Δ W Q_l = 4840 \times \text{CFM} \times \Delta W Q l ​ = 4840 × CFM × Δ W ).

Water requires 144 BTU/lb for phase change at fusion (melting/freezing at 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ) and 970 BTU/lb for phase change at evaporation/vaporization at 212 ∘ F 212^\circ\text{F} 21 2 ∘ F under standard atmospheric conditions.

Conduction heat transfer through building assemblies is governed by Q = k ⋅ A ⋅ Δ T / d Q = k \cdot A \cdot \Delta T / d Q = k ⋅ A ⋅ Δ T / d , where insulation effectiveness is evaluated by R R R -value ( R = d / k R = d/k R = d / k ) and overall thermal transmittance ( U = 1 / R total U = 1/R_{\text{total}} U = 1/ R total ​ ).

Total heat transfer in air distribution systems combines sensible and latent loads using total enthalpy change: Q t = 4.5 × CFM × Δ h Q_t = 4.5 \times \text{CFM} \times \Delta h Q t ​ = 4.5 × CFM × Δ h .

Last updated: August 2026

Thermodynamics is the branch of physical science that governs heat energy, work, and the properties of fluids. For Texas HVAC contractors, a mastery of thermodynamic principles is necessary to properly size equipment, calculate building cooling and heating loads, evaluate heat exchanger performance, and troubleshoot vapor-compression systems. All heating, ventilation, air conditioning, and refrigeration (HVACR) operations rely on controlling thermal energy transfer between indoor spaces, working fluids (refrigerants), and the ambient atmosphere.

The Laws of Thermodynamics in HVACR

Two fundamental laws of thermodynamics govern every HVAC process:

The First Law of Thermodynamics (Conservation of Energy)

The First Law of Thermodynamics states that energy cannot be created or destroyed; it can only change form or be transferred from one medium to another. In an HVAC system, electrical energy supplied to a compressor motor is converted into mechanical work, which pumps refrigerant and compresses gas. The thermal energy absorbed by the refrigerant in the indoor evaporator coil, combined with the heat of compression generated by the compressor motor, must equal the total thermal energy rejected to the outdoor environment through the condenser coil. Energy Input (Electrical + Heat Absorbed) = Energy Output (Heat Rejected) \text{Energy Input (Electrical + Heat Absorbed)} = \text{Energy Output (Heat Rejected)} Energy Input (Electrical + Heat Absorbed) = Energy Output (Heat Rejected)

The Second Law of Thermodynamics (Direction of Heat Flow)

The Second Law of Thermodynamics dictates that thermal energy spontaneously flows in only one direction: from a body of higher temperature to a body of lower temperature . Heat cannot naturally flow from a cold object to a warm object.

To move heat from a cool indoor room ( 75 ∘ F 75^\circ\text{F} 7 5 ∘ F ) to a hot outdoor ambient environment ( 105 ∘ F 105^\circ\text{F} 10 5 ∘ F during a Texas summer), external mechanical work must be applied. The mechanical vapor-compression refrigeration cycle uses a compressor and metering device to manipulate refrigerant pressure, creating a cold refrigerant surface ( 40 ∘ F 40^\circ\text{F} 4 0 ∘ F ) indoors to absorb heat and a hot refrigerant surface ( 125 ∘ F 125^\circ\text{F} 12 5 ∘ F ) outdoors to reject heat.

Modes of Heat Transfer

Heat transfer occurs whenever a temperature differential ( Δ T \Delta T Δ T ) exists between two regions. Heat moves via three distinct physical mechanisms: conduction , convection , and radiation .

Mode Physical Mechanism Primary HVAC Application Governing Equation / Factor

Conduction Direct molecular contact & vibration in solids/fluids Wall/roof heat gain, copper tubing heat exchange Q = k ⋅ A ⋅ Δ T d Q = \frac{k \cdot A \cdot \Delta T}{d} Q = d k ⋅ A ⋅ Δ T ​

Convection Fluid mass movement (liquid or gas) Airflow over evaporator coils, water flow in chillers Forced (fans/pumps) vs Natural (buoyancy)

Radiation Electromagnetic infrared waves Solar heat gain through glass, radiant floor heating Q ∝ ( T emitter 4 − T receiver 4 ) Q \propto (T_{\text{emitter}}^4 - T_{\text{receiver}}^4) Q ∝ ( T emitter 4 ​ − T receiver 4 ​ )

Conduction

Conduction is the transfer of thermal energy through a solid substance or stationary fluid via direct contact between adjacent molecules. Higher energy (hotter) molecules vibrate rapidly and collide with neighboring lower energy (cooler) molecules, transferring kinetic energy.

Fourier's Law of Thermal Conduction expresses the rate of conductive heat transfer: Q = k ⋅ A ⋅ Δ T d Q = \frac{k \cdot A \cdot \Delta T}{d} Q = d k ⋅ A ⋅ Δ T ​

Where:

Q Q Q = Rate of heat conduction (BTU/hr)

k k k = Thermal conductivity of the material (BTU ⋅ \cdot ⋅ in. / hr ⋅ ft 2 ⋅ ∘ F \cdot \text{ft}^2 \cdot ^\circ\text{F} ⋅ ft 2 ⋅ ∘ F )

A A A = Surface area perpendicular to heat flow ( ft 2 \text{ft}^2 ft 2 )

Δ T \Delta T Δ T = Temperature difference across the material ( T hot − T cold T_{\text{hot}} - T_{\text{cold}} T hot ​ − T cold ​ in ∘ F ^\circ\text{F} ∘ F )

d d d = Thickness of the material (inches or feet)

In building load calculations (ACCA Manual J), conduction through walls and ceilings is simplified using Thermal Resistance ( R R R -value) and Thermal Transmittance ( U U U -factor) : R = d k and U = 1 R total R = \frac{d}{k} \quad \text{and} \quad U = \frac{1}{R_{\text{total}}} R = k d ​ and U = R total ​ 1 ​ Q = U ⋅ A ⋅ Δ T Q = U \cdot A \cdot \Delta T Q = U ⋅ A ⋅ Δ T

Convection

Convection is the transfer of heat between a solid surface and a moving fluid (gas or liquid). It combines molecular conduction near the surface with bulk fluid motion.

Natural (Free) Convection : Fluid motion is driven solely by density differences resulting from temperature gradients (e.g., warm air rising off a baseboard heater as cold air falls).

Forced Convection : Fluid motion is mechanically driven by blowers, fans, or pumps (e.g., air forced across an evaporator coil by a centrifugal blower or water circulated through a hydronic fan coil).

Forced convection vastly increases the heat transfer coefficient compared to natural convection, allowing compact heat exchanger coils to transfer tens of thousands of BTUs per hour.

Radiation

Radiation is the transfer of heat by electromagnetic waves (infrared spectrum) without requiring a physical intervening medium. Radiated heat travels in straight lines through a vacuum or air until absorbed, reflected, or transmitted by a surface.

In Texas residential and commercial structures, solar radiation is the single largest heat gain factor during summer months. Radiant solar energy hits dark roof shingles and single-pane window glass, elevating surface temperatures dramatically above ambient air temperature. Radiant barriers (aluminum foil sheets installed in attics) reduce radiative heat transfer into ductwork and ceiling insulation by lowering attic emittance values from 0.90 0.90 0.90 down to 0.03 − 0.05 0.03-0.05 0.03 − 0.05 .

Sensible Heat, Latent Heat, and Total Enthalpy

In air conditioning systems, heat content is classified based on whether heat addition or removal alters dry-bulb temperature or physical state. [ SENSIBLE HEAT ]

  • Causes Dry-Bulb Temperature Change Only
  • (No Change in Physical State)
  • |
  • v
  • [ TOTAL HEAT ] (Enthalpy)
  • ^
  • |
  • [ LATENT HEAT ]
  • Causes Phase / State Change Only
  • (Constant Dry-Bulb Temperature)
  • Sensible Heat

Sensible heat is thermal energy that, when added to or removed from a substance, results in a measurable change in dry-bulb temperature without altering the physical state (phase) of the substance. It is called "sensible" because it can be sensed by a standard thermometer.

To calculate sensible heat gain or loss in standard air distribution systems, use the standard air sensible heat formula: Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s ​ = 1.08 × CFM × Δ T

Where:

  • Q s Q_s Q s ​ = Sensible heat transfer rate (BTU/hr)
  • CFM \text{CFM} CFM = Volumetric airflow rate in cubic feet per minute

Δ T \Delta T Δ T = Dry-bulb temperature difference ( T entering − T leaving T_{\text{entering}} - T_{\text{leaving}} T entering ​ − T leaving ​ in ∘ F ^\circ\text{F} ∘ F )

1.08 = Standard air sensible constant ( 60 min/hr × 0.075 lb/ft 3 density × 0.24 BTU/lb ∘ F specific heat 60 \text{ min/hr} \times 0.075 \text{ lb/ft}^3 \text{ density} \times 0.24 \text{ BTU/lb}^\circ\text{F} \text{ specific heat} 60 min/hr × 0.075 lb/ft 3 density × 0.24 BTU/lb ∘ F specific heat )

Latent Heat

Latent heat ("hidden heat") is thermal energy absorbed or released during a phase change (solid to liquid, liquid to gas, or vice versa) at constant temperature and pressure. In HVAC air conditioning, latent heat removal corresponds directly to dehumidification —condensing water vapor out of the airstream across an evaporator coil operating below the dew point temperature.

The standard air latent heat formula is: Q l = 4840 × CFM × Δ W Q_l = 4840 \times \text{CFM} \times \Delta W Q l ​ = 4840 × CFM × Δ W

Alternatively, expressed using moisture content in grains of moisture per pound of dry air ( 7 , 000 grains = 1 lb H 2 O 7,000 \text{ grains} = 1 \text{ lb}_{H_2O} 7 , 000 grains = 1 lb H 2 ​ O ​ ): Q l = 0.68 × CFM × Δ G Q_l = 0.68 \times \text{CFM} \times \Delta G Q l ​ = 0.68 × CFM × Δ G

Where:

Q l Q_l Q l ​ = Latent heat transfer rate (BTU/hr)

Δ W \Delta W Δ W = Humidity ratio difference ( lb H 2 O / lb dry air \text{lb}_{H_2O} / \text{lb}_{\text{dry air}} lb H 2 ​ O ​ / lb dry air ​ )

Δ G \Delta G Δ G = Moisture content difference in grains per pound of dry air ( G entering − G leaving G_{\text{entering}} - G_{\text{leaving}} G entering ​ − G leaving ​ )

4840 = Standard air latent constant ( 60 min/hr × 0.075 lb/ft 3 × 1076 BTU/lb latent heat of vaporization 60 \text{ min/hr} \times 0.075 \text{ lb/ft}^3 \times 1076 \text{ BTU/lb latent heat of vaporization} 60 min/hr × 0.075 lb/ft 3 × 1076 BTU/lb latent heat of vaporization )

  • 0.68 = Grains latent constant ( 4840 / 7000 grains/lb 4840 / 7000 \text{ grains/lb} 4840/7000 grains/lb )
  • Total Heat (Enthalpy)

Total heat ( Q t Q_t Q t ​ ) is the sum of sensible heat and latent heat. It represents the overall enthalpy change of the air passing through an HVAC coil: Q t = Q s + Q l Q_t = Q_s + Q_l Q t ​ = Q s ​ + Q l ​

The standard air total heat formula using psychrometric enthalpy values ( h h h in BTU/lb dry air) is: Q t = 4.5 × CFM × Δ h Q_t = 4.5 \times \text{CFM} \times \Delta h Q t ​ = 4.5 × CFM × Δ h

Where:

Q t Q_t Q t ​ = Total heat transfer rate (BTU/hr)

Δ h \Delta h Δ h = Enthalpy difference of air ( h entering − h leaving h_{\text{entering}} - h_{\text{leaving}} h entering ​ − h leaving ​ in BTU/lb)

4.5 = Standard air total constant ( 60 min/hr × 0.075 lb/ft 3 60 \text{ min/hr} \times 0.075 \text{ lb/ft}^3 60 min/hr × 0.075 lb/ft 3 )

Sensible Heat Ratio (SHR)

The Sensible Heat Ratio (SHR) evaluates the proportion of sensible cooling relative to total cooling performed by an air conditioner: SHR = Q s Q t = Q s Q s + Q l \text{SHR} = \frac{Q_s}{Q_t} = \frac{Q_s}{Q_s + Q_l} SHR = Q t ​ Q s ​ ​ = Q s ​ + Q l ​ Q s ​ ​

Standard residential comfort cooling equipment operates at an SHR of approximately 0.70 to 0.80 , meaning 70 % − 80 % 70\%-80\% 70% − 80% of coil capacity removes sensible heat (lowers dry-bulb temperature) and 20 % − 30 % 20\%-30\% 20% − 30% removes latent heat (condenses moisture). In humid Texas climates (e.g., Houston or Corpus Christi), a lower SHR ( 0.65 − 0.70 0.65-0.70 0.65 − 0.70 ) is required to prevent indoor high humidity.

Specific Heat and Phase Change Constants for Water

Understanding the physical constant values of water is mandatory for license exam calculations and hydronic/refrigeration engineering.

Property / Phase Change Temperature Value (BTU / lb) Description

Specific Heat of Ice ( c p , ice c_{p,\text{ice}} c p , ice ​ ) < 32 ∘ F <32^\circ\text{F} < 3 2 ∘ F 0.50 BTU/lb ⋅ ∘ F \cdot ^\circ\text{F} ⋅ ∘ F Sensible heat to raise/lower ice temp

Latent Heat of Fusion ( h s f h_{sf} h s f ​ ) 32 ∘ F 32^\circ\text{F} 3 2 ∘ F 144 BTU/lb Heat absorbed to melt ice / released to freeze water

Specific Heat of Liquid Water ( c p , water c_{p,\text{water}} c p , water ​ ) 32 ∘ F − 212 ∘ F 32^\circ\text{F} - 212^\circ\text{F} 3 2 ∘ F − 21 2 ∘ F 1.00 BTU/lb ⋅ ∘ F \cdot ^\circ\text{F} ⋅ ∘ F Standard heat capacity of liquid water

Latent Heat of Evaporation ( h f g h_{fg} h f g ​ ) 212 ∘ F 212^\circ\text{F} 21 2 ∘ F (at 14.7 PSIA) 970 BTU/lb Heat absorbed to vaporize water into steam

Specific Heat of Superheated Steam ( c p , steam c_{p,\text{steam}} c p , steam ​ ) > 212 ∘ F >212^\circ\text{F} > 21 2 ∘ F 0.48 BTU/lb ⋅ ∘ F \cdot ^\circ\text{F} ⋅ ∘ F Sensible heat to raise steam temp

Calculation Example: Full Phase Change of Water

Problem: Calculate the total heat in BTUs required to convert a 10-pound block of ice at 12 ∘ F 12^\circ\text{F} 1 2 ∘ F completely into superheated steam at 232 ∘ F 232^\circ\text{F} 23 2 ∘ F under standard atmospheric pressure.

Solution Breakdown:

Sensible Heat of Ice ( 12 ∘ F 12^\circ\text{F} 1 2 ∘ F to 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ): Q 1 = m × c p , ice × Δ T = 10 lbs × 0.50 BTU/lb ∘ F × ( 32 − 12 ) ∘ F = 100 BTU Q_1 = m \times c_{p,\text{ice}} \times \Delta T = 10 \text{ lbs} \times 0.50 \text{ BTU/lb}^\circ\text{F} \times (32 - 12)^\circ\text{F} = 100 \text{ BTU} Q 1 ​ = m × c p , ice ​ × Δ T = 10 lbs × 0.50 BTU/lb ∘ F × ( 32 − 12 ) ∘ F = 100 BTU

Latent Heat of Fusion (Melting at 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ): Q 2 = m × h s f = 10 lbs × 144 BTU/lb = 1 , 440 BTU Q_2 = m \times h_{sf} = 10 \text{ lbs} \times 144 \text{ BTU/lb} = 1,440 \text{ BTU} Q 2 ​ = m × h s f ​ = 10 lbs × 144 BTU/lb = 1 , 440 BTU

Sensible Heat of Liquid Water ( 32 ∘ F 32^\circ\text{F} 3 2 ∘ F to 212 ∘ F 212^\circ\text{F} 21 2 ∘ F ): Q 3 = m × c p , water × Δ T = 10 lbs × 1.00 BTU/lb ∘ F × ( 212 − 32 ) ∘ F = 1 , 800 BTU Q_3 = m \times c_{p,\text{water}} \times \Delta T = 10 \text{ lbs} \times 1.00 \text{ BTU/lb}^\circ\text{F} \times (212 - 32)^\circ\text{F} = 1,800 \text{ BTU} Q 3 ​ = m × c p , water ​ × Δ T = 10 lbs × 1.00 BTU/lb ∘ F × ( 212 − 32 ) ∘ F = 1 , 800 BTU

Latent Heat of Evaporation (Vaporizing at 212 ∘ F 212^\circ\text{F} 21 2 ∘ F ): Q 4 = m × h f g = 10 lbs × 970 BTU/lb = 9 , 700 BTU Q_4 = m \times h_{fg} = 10 \text{ lbs} \times 970 \text{ BTU/lb} = 9,700 \text{ BTU} Q 4 ​ = m × h f g ​ = 10 lbs × 970 BTU/lb = 9 , 700 BTU

Sensible Heat of Steam ( 212 ∘ F 212^\circ\text{F} 21 2 ∘ F to 232 ∘ F 232^\circ\text{F} 23 2 ∘ F ): Q 5 = m × c p , steam × Δ T = 10 lbs × 0.48 BTU/lb ∘ F × ( 232 − 212 ) ∘ F = 96 BTU Q_5 = m \times c_{p,\text{steam}} \times \Delta T = 10 \text{ lbs} \times 0.48 \text{ BTU/lb}^\circ\text{F} \times (232 - 212)^\circ\text{F} = 96 \text{ BTU} Q 5 ​ = m × c p , steam ​ × Δ T = 10 lbs × 0.48 BTU/lb ∘ F × ( 232 − 212 ) ∘ F = 96 BTU

Total Heat Required ( Q total Q_{\text{total}} Q total ​ ): Q total = 100 + 1 , 440 + 1 , 800 + 9 , 700 + 96 = 13 , 136 BTU Q_{\text{total}} = 100 + 1,440 + 1,800 + 9,700 + 96 = 13,136 \text{ BTU} Q total ​ = 100 + 1 , 440 + 1 , 800 + 9 , 700 + 96 = 13 , 136 BTU

This 5-step calculation highlights the vast magnitude of latent heat (9,700 BTU out of 13,136 BTU, or nearly 74%) compared to sensible heat, proving why phase-change refrigeration systems are so exceptionally efficient at moving energy.