2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure
Texas Air Conditioning and Refrigeration Contractor License Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library
2 Chapter 1: Texas Licensing Laws & TDLR Regulations
1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education
3 Chapter 2: Thermodynamics & Core HVAC Principles
2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure
4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)
3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments
5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition
4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation
6 Chapter 5: Refrigeration Cycle & Core System Components
5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves
7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality
6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms
8 Chapter 7: Heating Systems, Gas Controls & Venting
7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency
9 Chapter 8: Electrical Systems, Controls & Troubleshooting
8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control
10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)
9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support
11 Chapter 10: Commercial Refrigeration & Process Cooling Systems
10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals
12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice
11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses
2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure
Key Takeaways Explain This Topic AI
Standard residential air conditioning requires approximately 400 CFM per ton of cooling (350 CFM/ton for high humidity removal; 450 CFM/ton for dry climates).
Total External Static Pressure (TESP) is measured across the air handler cabinet using a manometer (TESP = |Supply Static| + |Return Static|); standard equipment is rated at 0.50 in. w.g.
Fan Law 1 dictates airflow scales linearly with RPM ( C F M 2 = C F M 1 × R P M 2 / R P M 1 CFM_2 = CFM_1 \times RPM_2/RPM_1 CF M 2 = CF M 1 × RP M 2 / RP M 1 ), Fan Law 2 dictates static pressure scales squared, and Fan Law 3 dictates brake horsepower scales cubed.
System CFM can be determined in the field using the Electric Heat Temperature Rise equation: C F M = ( k W × 3413 ) / ( 1.08 × Δ T ) CFM = (kW \times 3413) / (1.08 \times \Delta T) CFM = ( kW × 3413 ) / ( 1.08 × Δ T ) .
Air density decreases with altitude and high temperatures, requiring density correction multipliers when evaluating blower performance outside standard sea-level air ( 0.075 lb/ft 3 0.075 \text{ lb/ft}^3 0.075 lb/ft 3 ).
Last updated: August 2026
Air distribution is the delivery mechanism for conditioned heating and cooling in forced-air HVAC systems. A system can have a perfectly charged refrigerant circuit and ideal equipment sizing, but if system airflow in cubic feet per minute (CFM) is incorrect, performance degrades catastrophically. Texas HVAC contractors must master duct static pressure diagnostics, fan law scaling calculations, and field CFM measurement techniques.
- Airflow Rules of Thumb and Standard Air Definitions
- Airflow per Ton of Cooling
In comfort air conditioning applications, airflow across the indoor evaporator coil is specified based on cooling capacity: Standard Cooling Airflow Rule of Thumb = 400 CFM per Ton of Cooling \text{Standard Cooling Airflow Rule of Thumb} = \mathbf{400 \text{ CFM per Ton of Cooling}} Standard Cooling Airflow Rule of Thumb = 400 CFM per Ton of Cooling
Where 1 Ton of Cooling = 12 , 000 BTU/hr 1 \text{ Ton of Cooling} = 12,000 \text{ BTU/hr} 1 Ton of Cooling = 12 , 000 BTU/hr .
Standard Target ( 400 CFM/ton 400 \text{ CFM/ton} 400 CFM/ton ) : Designed for typical mixed climates ( 75 ∘ F 75^\circ\text{F} 7 5 ∘ F indoor dry bulb, 50 % 50\% 50% relative humidity).
High-Humidity / Latent Cooling Target ( 350 − 370 CFM/ton 350 - 370 \text{ CFM/ton} 350 − 370 CFM/ton ) : Applied in coastal Texas regions (e.g., Houston, Galveston, Beaumont). Reducing CFM increases air dwell time across cold coil fins, lowering coil temperature below dew point to condense maximum latent moisture.
Low-Humidity / Sensible Cooling Target ( 420 − 450 CFM/ton 420 - 450 \text{ CFM/ton} 420 − 450 CFM/ton ) : Applied in arid West Texas regions (e.g., El Paso, Lubbock). Higher CFM raises coil operating temperature and maximizes sensible dry-bulb cooling capacity.
Standard Air Properties
Standard air is defined at sea-level atmospheric pressure ( 29.92 in. Hg 29.92 \text{ in. Hg} 29.92 in. Hg or 14.7 PSIA 14.7 \text{ PSIA} 14.7 PSIA ) and 70 ∘ F 70^\circ\text{F} 7 0 ∘ F dry-bulb temperature:
Standard Air Density ( ρ \rho ρ ) : 0.075 lb/ft 3 0.075 \text{ lb/ft}^3 0.075 lb/ft 3
Standard Air Specific Volume ( v v v ) : 13.33 ft 3 / lb 13.33 \text{ ft}^3/\text{lb} 13.33 ft 3 / lb ( 1 / 0.075 1 / 0.075 1/0.075 )
Standard Air Specific Heat ( c p c_p c p ) : 0.24 BTU/lb ⋅ ∘ F 0.24 \text{ BTU/lb} \cdot ^\circ\text{F} 0.24 BTU/lb ⋅ ∘ F
Total External Static Pressure (TESP)
What is Static Pressure?
Static pressure is the outward bursting pressure exerted by air against the internal walls of a duct or air handler cabinet, measured in inches of water gauge (in. w.g.) . It represents resistance to airflow caused by filters, coils, duct friction, turns, dampers, and supply/return grilles. MEASURING TESP
- RETURN DUCT AIR HANDLER / FURNACE SUPPLY DUCT
- ------------
- Return Probe ===> [ Filter ] [ Blower ] [ Coil ] ===> Supply Probe
- (e.g., -0.25) (e.g., +0.35)
- ------------
TESP = |Return Static| + |Supply Static| = |-0.25| + |+0.35| = 0.60 in. w.g.
TESP Measurement Protocol
Total External Static Pressure (TESP) is the total resistance that the indoor blower fan must overcome outside the furnace/air handler cabinet.
To measure TESP using a digital dual-port manometer:
Insert the negative (-) static pressure probe into the return air plenum directly before entering the blower cabinet (downstream of the air filter).
Insert the positive (+) static pressure probe into the supply air plenum between the blower outlet/furnace heat exchanger and the evaporator coil (or after the coil if the coil is inside the cabinet assembly as rated by the manufacturer).
Calculate TESP by adding the absolute values of return and supply static pressure: TESP = ∣ S P return ∣ + ∣ S P supply ∣ \text{TESP} = |SP_{\text{return}}| + |SP_{\text{supply}}| TESP = ∣ S P return ∣ + ∣ S P supply ∣
Industry Limits for TESP
Standard residential furnace and air handler blowers (AHRI rated) are designed to deliver rated CFM at an external static pressure limit of 0.50 in. w.g. 0.50 \text{ in. w.g.} 0.50 in. w.g. .
Measured TESP (in. w.g.) System Condition Consequences
0.30 − 0.50 0.30 - 0.50 0.30 − 0.50 Ideal Design Range Maximum airflow efficiency, quiet operation, nominal motor life
0.51 − 0.70 0.51 - 0.70 0.51 − 0.70 Acceptable / Marginal Minor CFM reduction; acceptable on ECM variable-speed blowers
> 0.70 >0.70 > 0.70 Excessive Static Pressure Severe CFM drop on PSC motors; ECM motors over-amp, overheat, and fail
- > 1.00 >1.00 > 1.00 Critical Restriction Evaporator coils freeze, gas furnace limit switches trip, duct noise
- The Fan Laws (Affinity Laws)
The Fan Laws govern the mathematical relationship between blower speed (RPM), volumetric airflow (CFM), static pressure (SP), and motor brake horsepower (BHP). Modifying blower pulley size or motor tap changing alters system parameters predictably. THE THREE FAN LAWS
- FAN LAW 1 (Airflow) : CFM2 = CFM1 * (RPM2 / RPM1)
- FAN LAW 2 (Pressure) : SP2 = SP1 * (RPM2 / RPM1)^2
- FAN LAW 3 (Power) : BHP2 = BHP1 * (RPM2 / RPM1)^3
- Fan Law 1: Airflow vs Speed
Airflow rate (CFM) varies directly and linearly with fan rotational speed (RPM): CFM 2 = CFM 1 × ( RPM 2 RPM 1 ) \text{CFM}_2 = \text{CFM}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right) CFM 2 = CFM 1 × ( RPM 1 RPM 2 )
Fan Law 2: Static Pressure vs Speed
Static pressure (SP) varies with the square of fan speed ratio: SP 2 = SP 1 × ( RPM 2 RPM 1 ) 2 \text{SP}_2 = \text{SP}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^2 SP 2 = SP 1 × ( RPM 1 RPM 2 ) 2
Fan Law 3: Power vs Speed
Brake Horsepower (BHP) required by the motor varies with the cube of fan speed ratio: BHP 2 = BHP 1 × ( RPM 2 RPM 1 ) 3 \text{BHP}_2 = \text{BHP}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^3 BHP 2 = BHP 1 × ( RPM 1 RPM 2 ) 3
Calculation Example: Fan Laws Application
Problem: A belt-drive commercial air handler currently operates at 800 RPM 800 \text{ RPM} 800 RPM , delivering 3 , 000 CFM 3,000 \text{ CFM} 3 , 000 CFM against 0.60 in. w.g. 0.60 \text{ in. w.g.} 0.60 in. w.g. static pressure, drawing 1.50 BHP 1.50 \text{ BHP} 1.50 BHP . The contractor needs to increase airflow to 3 , 600 CFM 3,600 \text{ CFM} 3 , 600 CFM . Determine the new required RPM, new static pressure, and new motor horsepower.
Solution:
Calculate Speed Ratio: Ratio = CFM 2 CFM 1 = 3 , 600 3 , 000 = 1.20 \text{Ratio} = \frac{\text{CFM}_2}{\text{CFM}_1} = \frac{3,600}{3,000} = 1.20 Ratio = CFM 1 CFM 2 = 3 , 000 3 , 600 = 1.20
Find New Speed ( RPM 2 \text{RPM}_2 RPM 2 ) using Fan Law 1: RPM 2 = 800 × 1.20 = 960 RPM \text{RPM}_2 = 800 \times 1.20 = 960 \text{ RPM} RPM 2 = 800 × 1.20 = 960 RPM
Find New Static Pressure ( SP 2 \text{SP}_2 SP 2 ) using Fan Law 2: SP 2 = 0.60 × ( 1.20 ) 2 = 0.60 × 1.44 = 0.864 in. w.g. \text{SP}_2 = 0.60 \times (1.20)^2 = 0.60 \times 1.44 = 0.864 \text{ in. w.g.} SP 2 = 0.60 × ( 1.20 ) 2 = 0.60 × 1.44 = 0.864 in. w.g.
Find New Motor Horsepower ( BHP 2 \text{BHP}_2 BHP 2 ) using Fan Law 3: BHP 2 = 1.50 × ( 1.20 ) 3 = 1.50 × 1.728 = 2.592 BHP \text{BHP}_2 = 1.50 \times (1.20)^3 = 1.50 \times 1.728 = 2.592 \text{ BHP} BHP 2 = 1.50 × ( 1.20 ) 3 = 1.50 × 1.728 = 2.592 BHP
Critical Field Note: Increasing airflow by just 20 % 20\% 20% ( 1.20 × 1.20\times 1.20 × ) increased motor power demand by 72.8 % 72.8\% 72.8% ( 1.728 × 1.728\times 1.728 × ). Failing to check motor nameplate FLA when increasing fan speed will burn out the fan motor.
Field CFM Measurement Techniques
When verifying system airflow on job sites, three primary methods are utilized:
1. Electric Heat Temperature Rise Method
In heating mode with electric resistance heat strips energized, sensible heat output is precisely known from electrical measurements ( W = V × A W = V \times A W = V × A ): BTU/hr Output = Volts × Amps × 3.413 \text{BTU/hr Output} = \text{Volts} \times \text{Amps} \times 3.413 BTU/hr Output = Volts × Amps × 3.413
Rearranging the sensible heat equation ( Q s = 1.08 × CFM × Δ T Q_s = 1.08 \times \text{CFM} \times \Delta T Q s = 1.08 × CFM × Δ T ): CFM = Volts × Amps × 3.413 1.08 × Δ T rise \text{CFM} = \frac{\text{Volts} \times \text{Amps} \times 3.413}{1.08 \times \Delta T_{\text{rise}}} CFM = 1.08 × Δ T rise Volts × Amps × 3.413
2. Blower Performance Curve (Static Pressure Method)
Manufacturer performance tables list CFM output relative to measured TESP and motor speed taps. By measuring actual TESP across the cabinet and noting motor speed tap connection, technicians look up true delivered CFM on the manufacturer chart.
3. Total Enthalpy Cooling Method
Using total heat formula across the evaporator coil in cooling mode: CFM = Q t Total Coil Heat Removal (BTU/hr) = Coil Total Capacity 4.5 × ( h entering wb − h leaving wb ) \text{CFM} = \frac{Q_t}{\text{Total Coil Heat Removal (BTU/hr)}} = \frac{\text{Coil Total Capacity}}{4.5 \times (h_{\text{entering wb}} - h_{\text{leaving wb}})} CFM = Total Coil Heat Removal (BTU/hr) Q t = 4.5 × ( h entering wb − h leaving wb ) Coil Total Capacity
Air Density and Altitude Corrections
Air density varies inversely with altitude and temperature. As elevation increases above sea level, atmospheric pressure drops, making air thinner (lower mass per cubic foot). Air Density Correction Factor (ADCF) = Actual Barometric Pressure (in. Hg) 29.92 × 530 ∘ R 460 + T actual ∘ F \text{Air Density Correction Factor (ADCF)} = \frac{\text{Actual Barometric Pressure (in. Hg)}}{29.92} \times \frac{530^\circ\text{R}}{460 + T_{\text{actual}^\circ\text{F}}} Air Density Correction Factor (ADCF) = 29.92 Actual Barometric Pressure (in. Hg) × 460 + T actual ∘ F 53 0 ∘ R
At 5 , 000 feet 5,000 \text{ feet} 5 , 000 feet altitude (in Texas, the Davis Mountains region of far West Texas — note that Amarillo, the highest large city in the Panhandle, sits near 3 , 600 ft 3,600 \text{ ft} 3 , 600 ft ), air density is approximately 0.062 lb/ft 3 0.062 \text{ lb/ft}^3 0.062 lb/ft 3 ( 83 % 83\% 83% of standard sea-level density).
Impact on Heat Transfer : Because thinner air carries less heat mass per unit volume, the sensible heat constant 1.08 1.08 1.08 drops proportionally: Adjusted Constant = 1.08 × ( ρ actual 0.075 ) \text{Adjusted Constant} = 1.08 \times \left( \frac{\rho_{\text{actual}}}{0.075} \right) Adjusted Constant = 1.08 × ( 0.075 ρ actual )
At 5 , 000 ft 5,000 \text{ ft} 5 , 000 ft , sensible constant drops from 1.08 1.08 1.08 down to approximately 0.90 0.90 0.90 . To deliver equivalent cooling capacity, volumetric airflow must be increased ( C F M actual = C F M standard / ADCF CFM_{\text{actual}} = CFM_{\text{standard}} / \text{ADCF} CF M actual = CF M standard / ADCF ).