2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship

Texas Air Conditioning and Refrigeration Contractor License Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

About the Texas ACR Contractor Exam Open-Book Strategy and the Approved Reference Library

2 Chapter 1: Texas Licensing Laws & TDLR Regulations

1.1 TDLR Licensing Framework, Class A vs Class B Scope, and Technician Registration 1.2 Insurance, Financial Responsibility, Display of License, and Advertising Rules 1.3 TDLR Enforcement, Violations, Administrative Penalties, and Continuing Education

3 Chapter 2: Thermodynamics & Core HVAC Principles

2.1 Heat Transfer Principles: Conduction, Convection, Radiation, and Sensible vs Latent Heat 2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship 2.3 System Airflow Fundamentals, CFM Calculations, and Total External Static Pressure

4 Chapter 3: Load Calculations & System Sizing (Manual J, S, D)

3.1 ACCA Manual J Load Calculations: Heat Gain, Heat Loss, and Building Envelope Factors 3.2 ACCA Manual S Equipment Selection and Manual D Duct Design Principles 3.3 Texas Climate Design Conditions, Solar Gain, and Infiltration Adjustments

5 Chapter 4: Refrigerants, EPA Section 608 & Low-GWP A2L Transition

4.1 Refrigerant Classifications (CFC, HCFC, HFC, HFO) and EPA Section 608 Rules 4.2 AIM Act Phasedown, Next-Gen Low-GWP Refrigerants (R-454B, R-32), and A2L Safety Rules 4.3 Refrigerant Recovery, Recycling, Reclamation, Leak Repair Thresholds, and Evacuation

6 Chapter 5: Refrigeration Cycle & Core System Components

5.1 The Vapor-Compression Refrigeration Cycle and System Component States 5.2 Compressors: Types (Scroll, Reciprocating, Rotary), Maintenance, and Failure Modes 5.3 Condensers, Evaporators, and Expansion Devices (TXV, EEV, Fixed Orifice) 5.4 Service Valves, Filter-Driers, Sight Glasses, and Solenoid & Check Valves

7 Chapter 6: Air Distribution, Ductwork & Indoor Air Quality

6.1 Duct Layouts, Materials, Insulation, Duct Sealing, and Friction Loss 6.2 Air Balancing, Blower Performance Curves, and Air Distribution Fittings 6.3 Indoor Air Quality (IAQ): Ventilation, Filtration, Humidity Control, and ASHRAE 62.2 6.4 Mechanical Ventilation Rates, Air Equipment, and Refrigeration Machinery Rooms

8 Chapter 7: Heating Systems, Gas Controls & Venting

7.1 Gas-Fired Heating: Natural Gas, LP, Burners, Heat Exchangers, and Gas Piping 7.2 Gas Furnace Venting Categories, Draft Hoods, and Combustion Air Requirements 7.3 Electric Resistance Heating and Heat Pump Operation in Heating & Defrost Modes 7.4 Clothes Dryer Exhaust and Product-Conveying Duct Systems 7.5 Combustion Testing and Analysis: CO, Oxygen, Stack Temperature, Draft, and Efficiency

9 Chapter 8: Electrical Systems, Controls & Troubleshooting

8.1 HVAC Electrical Fundamentals: Voltage, Current, Resistance, and Transformer Sizing 8.2 Electric Motors: PSC, ECM, Capacitor Sizing, Relays, Contactors, and Starters 8.3 Schematics Reading, Control Circuits (24V), Thermostats, and Diagnostic Sequence 8.4 Pressure and Safety Controls: High/Low Pressure, Oil Safety, Freeze Protection, and Head Pressure Control

10 Chapter 9: Mechanical Codes & Texas Local Standards (IMC, IFGC & UMC)

9.1 International Mechanical Code (IMC): Equipment Clearances, Access, and Support 9.2 International Fuel Gas Code (IFGC): Pipe Sizing, Materials, Purging, and Testing 9.3 Condensate Drain Piping, Trap Sizing, Secondary Drain Protection, and Auxiliary Pans 9.4 Uniform Mechanical Code vs. International Mechanical Code: Adoption, Differences, and Locating Code Answers 9.5 Refrigerant Line Sizing, Piping Materials, Brazing, Oil Return, and Pipe Support

11 Chapter 10: Commercial Refrigeration & Process Cooling Systems

10.1 Commercial Refrigeration Systems: Walk-in Freezers, Coolers, and Multi-Compressor Racks 10.2 Defrost Systems: Electric, Hot Gas, Off-Cycle, and Evaporator Pressure Regulators (EPR) 10.3 Hydronic Chilled Water Systems, Boilers, and Process Cooling Fundamentals

12 Chapter 11: Jobsite Safety, OSHA Compliance & Business Practice

11.1 OSHA Safety Standards: Fall Protection, Personal Protective Equipment (PPE), and Ladder Safety 11.2 Lockout/Tagout (LOTO), Electrical Safety, High-Pressure Gas Cylinder Handling 11.3 Contractor Business Operations: Contracts, Lien Laws, Permits, Inspections, and Warranties 11.4 OSHA 29 CFR Part 1904: Recording and Reporting Occupational Injuries and Illnesses

2.2 Temperature, Pressure, Enthalpy, and the Pressure-Temperature Relationship

Key Takeaways Explain This Topic AI

Absolute pressure (PSIA) accounts for atmospheric pressure (PSIA = PSIG + 14.7), whereas gauge pressure (PSIG) reads zero at standard atmospheric pressure (14.696 PSIA = 29.92 in. Hg).

Superheat measures sensible heat added to refrigerant vapor above saturation temp (Superheat = Suction Line Temp - Evaporator Saturation Temp) to protect compressors from liquid floodback.

Subcooling measures heat removed from liquid refrigerant below saturation temp (Subcooling = Condenser Saturation Temp - Liquid Line Temp) to ensure a 100% liquid seal at the metering device.

Enthalpy ( h h h ) represents total heat content in BTU/lb, and the vapor-compression cycle expansion phase across a TXV/EEV is an isenthalpic (constant enthalpy) throttling process.

On a Pressure-Enthalpy ( P − h P-h P − h ) diagram, the horizontal distance across the evaporator dome defines Net Refrigerating Effect (NRE), while compressor work defines Heat of Compression (HOC).

Last updated: August 2026

Accurate measurement and diagnostic interpretation of temperature, pressure, and enthalpy are the foundation of HVAC service and installation. A contractor must understand how ambient dry-bulb, wet-bulb, and dew point temperatures interact, how pressure scales convert, and how refrigerant state changes are evaluated using pressure-temperature ( P − T P-T P − T ) relationships and Mollier Pressure-Enthalpy ( P − h P-h P − h ) diagrams.

Temperature Definitions and Psychrometric Properties

In HVAC engineering, three primary temperature parameters describe atmospheric air conditions: [ DRY-BULB TEMP ]

  • Standard Ambient Air Temperature
  • |
  • +------------------+------------------+
  • | |
  • v v
  • [ WET-BULB TEMP ] [ DEW POINT TEMP ]
  • Reflects Evaporative Cooling 100% Relative Humidity
  • (Moisture Content & Enthalpy) Moisture Condensation Point
  • 1. Dry-Bulb Temperature ( T d b T_{db} T d b ​ )

Dry-bulb temperature is the ambient air temperature measured by a standard thermometer exposed to the air stream while shielded from direct radiation and moisture. It measures purely sensible heat content.

2. Wet-Bulb Temperature ( T w b T_{wb} T w b ​ )

Wet-bulb temperature is measured by a thermometer whose sensing bulb is covered by a clean, water-saturated cloth wick over which air is passed at high velocity ( > 500 ft/min >500 \text{ ft/min} > 500 ft/min ). As water evaporates from the wick, it absorbs latent heat, lowering the temperature reading. The rate of evaporation depends on the relative humidity of the surrounding air:

In dry air , evaporation is rapid, resulting in a large wet-bulb depression ( T d b − T w b T_{db} - T_{wb} T d b ​ − T w b ​ ).

In 100% humid air (saturated air) , no net evaporation can occur; thus, dry-bulb, wet-bulb, and dew point temperatures are all identical ( T d b = T w b = T d p T_{db} = T_{wb} = T_{dp} T d b ​ = T w b ​ = T d p ​ ).

Wet-bulb temperature directly reflects the total heat content (enthalpy) of moist air and is critical when charging fixed-orifice air conditioners using superheat charts.

3. Dew Point Temperature ( T d p T_{dp} T d p ​ )

Dew point temperature is the exact temperature to which air must be cooled at constant pressure to reach 100 % 100\% 100% relative humidity (saturation). At the dew point, air can no longer hold water in gaseous form, and water vapor begins condensing into liquid droplets. In Texas air conditioning design, keeping indoor cooling coil surface temperatures below the room dew point is necessary to achieve effective moisture removal.

Pressure Scales and Measurement Fundamentals

Pressure ( P P P ) is defined as force per unit area ( P = F / A P = F / A P = F / A ). In HVAC systems, pressure is measured in multiple units depending on the application.

Unit / Scale Full Name Reference Baseline Common HVAC Application

PSIG Pounds per Square Inch Gauge Atmospheric Pressure ( 0 PSIG 0 \text{ PSIG} 0 PSIG ) Manifold gauge sets, system operating pressures

PSIA Pounds per Square Inch Absolute Perfect Vacuum ( 0 PSIA 0 \text{ PSIA} 0 PSIA ) Thermodynamic equations, low-pressure chillers

in. Hg Inches of Mercury Atmospheric or Vacuum Deep vacuum evacuation ( 29.92 in. Hg 29.92 \text{ in. Hg} 29.92 in. Hg vacuum)

Microns Micrometers of Mercury Absolute Vacuum ( 0 microns 0 \text{ microns} 0 microns ) System evacuation ( 1 in. Hg = 25 , 400 microns 1 \text{ in. Hg} = 25,400 \text{ microns} 1 in. Hg = 25 , 400 microns )

in. w.g. Inches of Water Gauge Atmospheric Pressure Duct static pressure, draft pressure ( 1 PSI = 27.7 in. w.g. 1 \text{ PSI} = 27.7 \text{ in. w.g.} 1 PSI = 27.7 in. w.g. )

Atmospheric Pressure Standards

At standard sea level ( 59 ∘ F 59^\circ\text{F} 5 9 ∘ F or 15 ∘ C 15^\circ\text{C} 1 5 ∘ C ), standard atmospheric pressure created by the weight of the earth's atmosphere is defined as: Standard Atmosphere = 14.696 PSIA ≈ 14.7 PSIA = 0 PSIG = 29.92 in. Hg = 760 mm Hg = 101.325 kPa \text{Standard Atmosphere} = 14.696 \text{ PSIA} \approx 14.7 \text{ PSIA} = 0 \text{ PSIG} = 29.92 \text{ in. Hg} = 760 \text{ mm Hg} = 101.325 \text{ kPa} Standard Atmosphere = 14.696 PSIA ≈ 14.7 PSIA = 0 PSIG = 29.92 in. Hg = 760 mm Hg = 101.325 kPa

To convert between gauge pressure (PSIG) and absolute pressure (PSIA): PSIA = PSIG + 14.7 \text{PSIA} = \text{PSIG} + 14.7 PSIA = PSIG + 14.7 PSIG = PSIA − 14.7 \text{PSIG} = \text{PSIA} - 14.7 PSIG = PSIA − 14.7

Note for Texas Contractors: High-altitude regions such as Amarillo or El Paso ( 3 , 700 − 4 , 000 ft 3,700-4,000 \text{ ft} 3 , 700 − 4 , 000 ft elevation) experience lower atmospheric pressure (approx. 12.7 PSIA 12.7 \text{ PSIA} 12.7 PSIA ). Gauge conversions at high altitudes must adjust atmospheric constants accordingly.

Saturation Temperature and Pressure ( P − T P-T P − T Relationship)

A pure refrigerant in a closed system containing both liquid and vapor exists at a saturated state . At saturation, there is a fixed, direct mathematical relationship between pressure and temperature: for every specific pressure, there is exactly one saturation temperature at which liquid boils into vapor or vapor condenses into liquid.

Boiling Point Elevation : Increasing system pressure raises the saturation boiling temperature.

Condensing Point Depression : Lowering system pressure reduces the saturation condensing temperature.

Refrigerant blends (such as R-454B or R-407C) exhibit temperature glide , boiling across a range of temperatures between the Bubble Point (100% liquid saturation used for subcooling calculations) and the Dew Point (100% vapor saturation used for superheat calculations).

Superheat and Subcooling Diagnostic Calculations

Superheat and subcooling are the two key diagnostic metrics used by technicians to evaluate refrigerant charge, metering device performance, and coil airflow. SUPERHEAT CALCULATION

[ Actual Suction Line Temp ] - [ Evaporator Saturation Temp (from PSIG) ] = SUPERHEAT

  • SUBCOOLING CALCULATION
  • [ Condenser Saturation Temp (from PSIG) ] - [ Actual Liquid Line Temp ] = SUBCOOLING
  • Superheat Calculation

Superheat is the sensible heat added to 100% saturated refrigerant vapor after it has completely boiled in the evaporator coil, raising its temperature above the saturation boiling point. Superheat = T actual suction line − T evaporator saturation \text{Superheat} = T_{\text{actual suction line}} - T_{\text{evaporator saturation}} Superheat = T actual suction line ​ − T evaporator saturation ​

Why Superheat Matters:

Compressor Protection : Ensures 100% pure vapor enters the compressor suction port. Liquid refrigerant is incompressible; liquid floodback will shatter compressor valves, score scrolls, and wash out motor oil.

Coil Capacity : Low superheat ( 5 ∘ F − 8 ∘ F 5^\circ\text{F}-8^\circ\text{F} 5 ∘ F − 8 ∘ F ) indicates a flooded coil maximizing surface area usage, while high superheat ( > 25 ∘ F >25^\circ\text{F} > 2 5 ∘ F ) indicates a starved coil with low capacity.

Subcooling Calculation

Subcooling is sensible heat removed from 100% saturated liquid refrigerant in the condenser coil, cooling it below its saturation condensing temperature. Subcooling = T condenser saturation − T actual liquid line \text{Subcooling} = T_{\text{condenser saturation}} - T_{\text{actual liquid line}} Subcooling = T condenser saturation ​ − T actual liquid line ​

Why Subcooling Matters:

Metering Device Seal : Guarantees a solid column of liquid reaches the expansion valve inlet without flash gas bubbles.

Refrigerant Charge : Subcooling is the primary method for charging systems equipped with Thermostatic Expansion Valves (TXV) or Electronic Expansion Valves (EEV).

Field Diagnostic Matrix

  • Operating Condition Superheat Subcooling Suction Pressure Liquid Pressure Likely Root Cause
  • Undercharged (Low Refrigerant) High Low Low Low Refrigerant leak
  • Overcharged (High Refrigerant) Low High High High Excess refrigerant added
  • Low Evaporator Airflow Low Normal / Low Low Low / Normal Dirty filter, failed blower, restricted return
  • TXV Restriction / Underfeeding High High Low Normal / High Debris/wax in TXV, failed power element
  • Pressure-Enthalpy ( P − h P-h P − h ) Diagram Analysis

The Pressure-Enthalpy ( P − h P-h P − h ) diagram (Mollier Chart) visually maps the thermodynamic states of a refrigerant across the four stages of the mechanical vapor-compression cycle. Pressure (P)

  • ^
  • | /--- SATURATED LIQUID LINE (left boundary, through 3 and 4)
  • | /
  • | LIQUID / VAPOR DOME VAPOR
  • | REGION / (2-PHASE) REGION
  • | / \
  • P_c +----------3--------------------2 <-- Condensing Pressure
  • | | |
  • | | |
  • P_e +----------4--------------------1 <-- Evaporating Pressure
  • | \ /
  • | \ /
  • | \--- SATURATED VAPOR LINE (right boundary, through 2 and 1)
  • +---------------------------------------------> Enthalpy (h)
  • The Four Phases of the Vapor-Compression Cycle

Compression (Point 1 to Point 2) :

Low-pressure, superheated vapor entering compressor port (1) is compressed isentropically (constant entropy) to high-pressure, superheated vapor (2).

Vertical rise in pressure; increase in enthalpy due to mechanical Heat of Compression (HOC) .

Condensing (Point 2 to Point 3) :

High-pressure vapor releases superheat (desuperheating), releases latent heat at constant condensing pressure/temperature across the vapor dome, and cools further into subcooled liquid (3).

Total heat rejected equals Total Heat of Rejection (THOR) ( h 2 − h 3 h_2 - h_3 h 2 ​ − h 3 ​ ).

Expansion / Throttling (Point 3 to Point 4) :

Subcooled liquid expands through TXV/EEV metering device, dropping rapidly to evaporator pressure (4).

This is an isenthalpic (constant enthalpy) process ( h 3 = h 4 h_3 = h_4 h 3 ​ = h 4 ​ ). A portion of liquid flashes into vapor ("flash gas") to cool the remaining liquid down to evaporator temperature.

Evaporation (Point 4 to Point 1) :

Low-pressure 2-phase mixture absorbs heat from indoor air, boiling liquid into vapor across the dome and adding superheat (1).

Enthalpy gained ( h 1 − h 4 h_1 - h_4 h 1 ​ − h 4 ​ ) represents the Net Refrigerating Effect (NRE) .

Key Refrigeration Cycle Equations from P − h P-h P − h Chart Net Refrigerating Effect (NRE) = h 1 − h 4 ( BTU/lb ) \text{Net Refrigerating Effect (NRE)} = h_1 - h_4 \quad (\text{BTU/lb}) Net Refrigerating Effect (NRE) = h 1 ​ − h 4 ​ ( BTU/lb ) Heat of Compression (HOC) = h 2 − h 1 ( BTU/lb ) \text{Heat of Compression (HOC)} = h_2 - h_1 \quad (\text{BTU/lb}) Heat of Compression (HOC) = h 2 ​ − h 1 ​ ( BTU/lb ) Total Heat of Rejection (THOR) = h 2 − h 3 ( BTU/lb ) \text{Total Heat of Rejection (THOR)} = h_2 - h_3 \quad (\text{BTU/lb}) Total Heat of Rejection (THOR) = h 2 ​ − h 3 ​ ( BTU/lb ) Coefficient of Performance (COP) = NRE HOC = h 1 − h 4 h 2 − h 1 \text{Coefficient of Performance (COP)} = \frac{\text{NRE}}{\text{HOC}} = \frac{h_1 - h_4}{h_2 - h_1} Coefficient of Performance (COP) = HOC NRE ​ = h 2 ​ − h 1 ​ h 1 ​ − h 4 ​ ​ Refrigerant Mass Flow Rate = Required System Cooling Capacity (BTU/hr) NRE (BTU/lb) ( lb/hr ) \text{Refrigerant Mass Flow Rate} = \frac{\text{Required System Cooling Capacity (BTU/hr)}}{\text{NRE (BTU/lb)}} \quad (\text{lb/hr}) Refrigerant Mass Flow Rate = NRE (BTU/lb) Required System Cooling Capacity (BTU/hr) ​ ( lb/hr )