Study guide
9.2 Gas Pipe Sizing & Longest Length Method
Texas Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing Laws, Board Rules, & Safety
1.1 TSBPE Laws, Board Rules, & Scope of Practice 1.2 Responsible Master Plumber (RMP) Supervision & Permitting 1.3 Jobsite Safety, OSHA Standards, & Trenching 1.4 Enforcement, Disciplinary Action, & Penalties
2 Chapter 2: Exam Format, Adopted Codes, & Definitions
2.1 Exam Format, Scoring, & Testing Logistics 2.2 Adopted Plumbing Codes & Jurisdictional Authority 2.3 Code Definitions & Trade Terminology
3 Chapter 3: General Regulations & Piping Installation
3.1 Approved Piping Materials & Standards 3.2 Pipe Hangers, Supports, & Spacing 3.3 Structural Protection, Sleeving, & Penetrations 3.4 System Testing & Inspection Requirements
4 Chapter 4: Drainage Systems & Pipe Sizing
4.1 Drainage Fixture Units (DFU) & Fixture Drains 4.2 Building Drains, Sewers, & Minimum Slopes 4.3 Cleanouts: Sizing, Clearances, & Locations 4.4 Sumps, Sewage Ejectors, & Indirect Waste Systems 4.5 Storm Drainage Systems
5 Chapter 5: Traps & Trap Seal Protection
5.1 Trap Design, Sizing, & Prohibited Traps 5.2 Trap Seal Protection, Trap Arms, & Trap Primers
6 Chapter 6: Venting Methods & Design
6.1 Vent Sizing, Developed Length, & Terminations 6.2 Individual, Common, & Relief Vents 6.3 Wet Venting, Circuit Venting, & Combination Systems 6.4 Air Admittance Valves (AAV) & Island Fixture Vents
7 Chapter 7: Potable Water Supply & Distribution
7.1 Water Supply Fixture Units (WSFU) & Pipe Sizing 7.2 Water Pressure, PRVs, & Thermal Expansion 7.3 Cross-Connection Control & Backflow Devices 7.4 Water Service, Metering, & System Disinfection
8 Chapter 8: Water Heaters & Scald Prevention
8.1 Water Heater Types, Sizing, & Installation 8.2 Temperature & Pressure (T&P) Relief Valves & Discharge 8.3 Combustion Air, Venting, & Scald-Prevention Mixing Valves
9 Chapter 9: Fuel Gas Piping Systems
9.1 Fuel Gas Properties & Piping Materials (IFGC / NFPA 54) 9.2 Gas Pipe Sizing & Longest Length Method 9.3 Gas Shutoff Valves, Regulators, & Pressure Testing
10 Chapter 10: Fixtures, Faucets, & Accessibility
10.1 Fixture Clearances & Accessibility Standards (ADA) 10.2 Water Conservation & Flush Rates 10.3 Urinals, Special Fixtures, & Interceptors 10.4 Fixture Fittings, Faucets, & Accessories
11 Chapter 11: Plumbing Math & Trade Calculations
11.1 45-Degree & Rolling Offset Calculations 11.2 Grade, Fall, & Invert Elevation Calculations 11.3 Volume, Capacity, & Hydrostatic Pressure Calculations
12 Chapter 12: Isometric Drawings & TSBPE Practical Exam
12.1 Isometric Drawing Principles & Piping Schematics 12.2 TSBPE 2-Story DWV Dollhouse Design & Layout 12.3 Water & Gas Piping Schematics for Practical Stations 12.4 Hands-On Shop Skills: Brazing, Soldering, & Flaring
9.2 Gas Pipe Sizing & Longest Length Method
Key Takeaways Explain This Topic AI
Low-pressure natural gas systems operate at standard appliance inlet pressure of 0.5 psi (1/2 psig) or 7 inches water column (7 in. w.c.), while LP-Gas systems operate at 11 in. w.c. (1 psi = 27.7 in. w.c., with a standard allowable pressure drop of 0.5 in. w.c.).
The Longest Length Method sizes every pipe section in the entire system using ONE single table column corresponding to the total developed length from the meter/regulator to the most hydraulically remote appliance.
Gas load demand is converted from appliance input rating (BTU/hr) to Cubic Feet per Hour (CFH) using CFH = Appliance BTU/hr/Gas Heating Value, yielding 1 CFH ≈ 1,000 BTU/hr for Natural Gas and 1 CFH ≈ 2,500 BTU/hr for LP-Gas.
Each pipe segment (main header, sub-main, or branch) must be sized using the Longest Length column for the cumulative downstream volume (CFH) that passes through that specific section.
Hybrid 2-psig medium-pressure gas distribution systems utilize smaller pipe diameters with line pressure regulators (ANSI Z21.18) installed upstream of each appliance to step down pressure to 7-11 in. w.c.
Last updated: August 2026
9.2 Gas Pipe Sizing & Longest Length Method
Accurate gas pipe sizing is vital to ensure that every gas appliance receives its required volumetric fuel flow under peak concurrent operating conditions without suffering excessive pressure drops. An undersized gas line starves appliances of fuel, resulting in incomplete combustion, lethal carbon monoxide (CO) generation, pilot outage, and premature heat exchanger failure.
The Texas State Board of Plumbing Examiners (TSBPE) tests candidates extensively on the Longest Length Method (also known as the Longest Run Method) outlined in IFGC Chapter 4 and NFPA 54 Chapter 6 .
1. Fuel Gas Pressure Systems & Units of Measure
Fuel gas distribution systems are classified by operating gauge pressure: +---------------------------------------------------------------------------------------------------+
- | GAS PRESSURE CLASSIFICATIONS & CONVERSIONS |
- | |
- | SYSTEM TYPE OPERATING PRESSURE TYPICAL APPLIANCE / APPLICATION |
- | ==================== =========================== ========================================== |
- | - Low-Pressure NG: 1/2 psi (0.5 psig) Standard residential / commercial fixtures. |
- | Nominal 7.0" w.c. (5"-7" w.c.)Manifold operates at 3.5" w.c. |
- | - Low-Pressure LP: 1/2 psi (0.5 psig) Propane residential systems. |
- | Nominal 11.0" w.c. (10"-12") Manifold operates at 10.0" w.c. |
- | - Medium-Pressure: 2.0 psig (55.4" w.c.) Hybrid CSST / Steel residential mains with |
- | appliance line pressure regulators (MPR). |
- | - High-Pressure: 5.0 to 10.0+ psig Commercial / Industrial distribution loops. |
- +---------------------------------------------------------------------------------------------------+
- The "Inches Water Column" (in. w.c.) Unit
Low gas pressures are too minute to measure accurately on standard Bourdon tube PSI gauges. Instead, the industry utilizes a U-tube water manometer to measure the hydrostatic displacement of a column of water in inches: Pressure Equivalents: \text{Pressure Equivalents:} Pressure Equivalents: 1.0 psi = 27.7 inches water column (in. w.c.) = 16.0 ounces/sq in 1.0\text{ psi} = 27.7\text{ inches water column (in. w.c.)} = 16.0\text{ ounces/sq in} 1.0 psi = 27.7 inches water column (in. w.c.) = 16.0 ounces/sq in 0.5 psi (1/2 psig) = 13.85 in. w.c. 0.5\text{ psi (1/2 psig)} = 13.85\text{ in. w.c.} 0.5 psi (1/2 psig) = 13.85 in. w.c. 1.0 in. w.c. = 0.0361 psi = 0.578 oz/sq in 1.0\text{ in. w.c.} = 0.0361\text{ psi} = 0.578\text{ oz/sq in} 1.0 in. w.c. = 0.0361 psi = 0.578 oz/sq in
Allowable Pressure Drop (Δ P): In standard low-pressure systems (< 0.5 psig), sizing tables are calibrated to limit total friction loss between the gas meter outlet and any appliance shutoff valve to 0.5 in. w.c. (0.125 kPa) (or 0.3 in. w.c. in select conservation codes).
Operational Logic: If utility meter delivery pressure is 7.0 in. w.c. and line friction drop is 0.5 in. w.c., appliance inlet pressure is 6.5 in. w.c., easily satisfying the 3.5 in. w.c. manifold burner requirement.
Loading diagram... Low-Pressure Natural Gas Delivery & Pressure Drop Flow
2. Converting Appliance BTU/hr Ratings to Volume Demand (CFH)
Gas sizing tables express pipe capacity in Cubic Feet per Hour (CFH) . Before sizing pipe, all connected appliance nameplate ratings (expressed in BTU/hr) must be converted to volumetric flow rate: +-----------------------------------------------------------------------------------+
- | VOLUMETRIC DEMAND (CFH) FORMULA |
- | |
- | Appliance Input Rating (BTU/hr) |
- | CFH = --------------------------------- |
- | Heating Value of Gas (BTU/cu ft) |
- | |
- | - FOR NATURAL GAS: Use 1,000 BTU/cu ft --> CFH = BTU/hr / 1,000 |
- | - FOR LP-GAS: Use 2,500 BTU/cu ft --> CFH = BTU/hr / 2,500 |
- +-----------------------------------------------------------------------------------+
- Standard Residential Appliance Demands
- Appliance Type Standard Rating (BTU/hr) Natural Gas Demand (CFH) Propane Demand (CFH)
- Central Warm-Air Furnace 80,000 to 120,000 80 to 120 CFH 32 to 48 CFH
- Storage Water Heater (50 gal) 40,000 to 50,000 40 to 50 CFH 16 to 20 CFH
- Tankless Water Heater 180,000 to 199,000 180 to 199 CFH 72 to 80 CFH
- Domestic Cooking Range / Oven 65,000 65 CFH 26 CFH
- Clothes Dryer 35,000 35 CFH 14 CFH
- Outdoor Barbecue Grill 40,000 40 CFH 16 CFH
- Gas Fireplace Log Set 40,000 40 CFH 16 CFH
Important
No Diversity Factor for Gas Piping: Unlike electrical load calculations or water supply fixture units (Hunter's Curve), fuel gas piping codes prohibit applying any diversity factor to general residential systems. The piping must be engineered to deliver 100% full-load capacity assuming every appliance operates simultaneously at maximum firing rate.
3. The Longest Length Method: Step-by-Step Procedure
The Longest Length sizing procedure prevents cumulative friction loss from choking the most remote appliance during simultaneous peak firing. +-----------------------------------------------------------------------------------+
- | THE LONGEST LENGTH SIZING METHOD WORKFLOW |
- | |
- | [STEP 1] MEASURE TOTAL LONGEST DEVELOPED LENGTH: |
- | Measure from the outlet of the gas meter (or regulator) to the MOST REMOTE |
- | appliance in the entire piping layout (summing pipe run + fitting allowances). |
- | |
- | [STEP 2] SELECT CODE SIZING TABLE & IDENTIFY LENGTH COLUMN: |
- | Choose the table for gas type, pipe material, inlet pressure, and ΔP. |
- | Locate the column equal to or greater than the total longest developed length. |
- | |
- | [STEP 3] MAINTAIN THAT SINGLE COLUMN FOR THE ENTIRE SYSTEM: |
- | LOCK IN THIS COLUMN. Do NOT change columns when sizing shorter branch lines! |
- | |
- | [STEP 4] CALCULATE CUMULATIVE DOWNSTREAM LOAD FOR EACH PIPE SECTION: |
- | For every main run, sub-main, and branch, sum all downstream appliance loads. |
- | |
- | [STEP 5] SELECT PIPE DIAMETER SATISFYING LOAD: |
- | Read down the longest length column; choose the smallest nominal pipe diameter |
- | whose tabulated capacity equals or exceeds the section's cumulative load. |
- +-----------------------------------------------------------------------------------+
- Simplified IFGC Sizing Table Extract
Table: Natural Gas Schedule 40 Metallic Pipe (Inlet < 0.5 psig, Pressure Drop 0.5 in. w.c., Specific Gravity 0.60) — Capacities in CFH :
- Nominal Pipe Size 10 ft 20 ft 30 ft 40 ft 50 ft 60 ft 70 ft 80 ft 90 ft 100 ft
- 1/2-inch 172 118 95 81 72 65 60 56 52 50
- 3/4-inch 360 247 199 170 151 138 126 117 110 104
- 1-inch 678 466 374 320 284 260 237 220 207 195
- 1-1/4-inch 1,390 957 768 657 583 534 488 452 424 400
- 1-1/2-inch 2,090 1,430 1,150 985 873 801 732 677 635 600
- 2-inch 4,020 2,760 2,220 1,900 1,680 1,540 1,410 1,300 1,220 1,160
- 4. Comprehensive Worked Sizing Example
Consider a single-family residential natural gas system (1,000 BTU/cu ft, 0.5 psig, Δ P = 0.5 in. w.c.): [FURNACE: 100,000 BTU / 100 CFH]
- ^
- | (10 ft Branch C-F)
- [GAS METER] ====(20 ft A-B)====[B]====(20 ft B-C)====[C]====(20 ft C-D)====[WATER HEATER: 40 CFH]
- |
- +====(10 ft Branch B-R)====[RANGE: 65 CFH]
- |
- +====(15 ft Branch B-Y)====[DRYER: 35 CFH]
Sizing Calculation Steps:
Appliance Loads:
- Water Heater (at D): 40,000 BTU/hr = 40 CFH
- Furnace (at F): 100,000 BTU/hr = 100 CFH
- Cooking Range (at R): 65,000 BTU/hr = 65 CFH
- Clothes Dryer (at Y): 35,000 BTU/hr = 35 CFH
- Total System Demand: 40 + 100 + 65 + 35 = 240 CFH
Determine Longest Developed Length:
- Path to Range: 20 ft (A-B) + 10 ft (B-R) = 30 ft
- Path to Dryer: 20 ft (A-B) + 15 ft (B-Y) = 35 ft
- Path to Furnace: 20 ft (A-B) + 20 ft (B-C) + 10 ft (C-F) = 50 ft
- Path to Water Heater: 20 ft (A-B) + 20 ft (B-C) + 20 ft (C-D) = 60 ft
Total Longest Developed Length = 60 feet (Governs the entire layout!).
Select Table Column: Use the 60-Foot Column for ALL pipe segments.
Size Each Individual Section:
Main Run A-B: Carries total load = 240 CFH. In the 60-ft column, a 3/4" pipe carries 138 CFH (too small); a 1-inch pipe carries 260 CFH (260 ≥ 240). → Select 1-inch .
Sub-Main B-C: Carries Furnace (100 CFH) + Water Heater (40 CFH) = 140 CFH. In the 60-ft column, 3/4" carries 138 CFH (fails by 2 CFH); a 1-inch pipe carries 260 CFH. → Select 1-inch .
Branch C-D (Water Heater): Carries 40 CFH. In the 60-ft column, a 1/2-inch pipe carries 65 CFH (65 ≥ 40). → Select 1/2-inch .
Branch C-F (Furnace): Carries 100 CFH. In the 60-ft column, 1/2" carries 65 CFH (too small); a 3/4-inch pipe carries 138 CFH. → Select 3/4-inch .
Branch B-R (Range): Carries 65 CFH. In the 60-ft column, 1/2" carries exactly 65 CFH (65 ≥ 65). → Select 1/2-inch (or 3/4" for field safety margin).
Branch B-Y (Dryer): Carries 35 CFH. In the 60-ft column, a 1/2-inch pipe carries 65 CFH (65 ≥ 35). → Select 1/2-inch .
Loading diagram... Worked Sizing Example: Isometric Flow and Sized Segments
5. Branch Method vs. Longest Length Method & Common Traps
A critical mistake made on licensing exams is switching table columns when sizing branches:
The Sizing Trap: For Branch B-R (Range, 10 ft long), looking at the 10-ft column where a 1/2" pipe delivers 172 CFH. While 172 CFH seems generous, the Range is fed through Section A-B which has already consumed part of the available pressure budget over its 20-foot run. If the branch is sized using a short length column, the system pressure drop will exceed 0.5 in. w.c., causing low-pressure starvation.
The Rule: The longest developed length represents the overall hydraulic resistance of the piping network; therefore, all downstream sections must be evaluated against the resistance of that longest path .
Hybrid 2-PSI Medium Pressure Systems
Modern residential construction frequently incorporates 2-psig medium-pressure systems utilizing CSST manifolds:
Operation: Utility gas is delivered at 2.0 psig (55.4 in. w.c.) directly to a central distribution manifold. Because higher pressure pushes significantly more mass through smaller tubing, 1/2-inch and 3/8-inch CSST lines can run extended distances.
Maxitrol / Line Regulators: At each appliance, an Appliance Line Pressure Regulator (ANSI Z21.18) reduces the 2.0 psig line pressure down to 7.0 in. w.c. for appliance operation.