3.4 System Testing & Inspection Requirements
Texas Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing Laws, Board Rules, & Safety
1.1 TSBPE Laws, Board Rules, & Scope of Practice 1.2 Responsible Master Plumber (RMP) Supervision & Permitting 1.3 Jobsite Safety, OSHA Standards, & Trenching 1.4 Enforcement, Disciplinary Action, & Penalties
2 Chapter 2: Exam Format, Adopted Codes, & Definitions
2.1 Exam Format, Scoring, & Testing Logistics 2.2 Adopted Plumbing Codes & Jurisdictional Authority 2.3 Code Definitions & Trade Terminology
3 Chapter 3: General Regulations & Piping Installation
3.1 Approved Piping Materials & Standards 3.2 Pipe Hangers, Supports, & Spacing 3.3 Structural Protection, Sleeving, & Penetrations 3.4 System Testing & Inspection Requirements
4 Chapter 4: Drainage Systems & Pipe Sizing
4.1 Drainage Fixture Units (DFU) & Fixture Drains 4.2 Building Drains, Sewers, & Minimum Slopes 4.3 Cleanouts: Sizing, Clearances, & Locations 4.4 Sumps, Sewage Ejectors, & Indirect Waste Systems 4.5 Storm Drainage Systems
5 Chapter 5: Traps & Trap Seal Protection
5.1 Trap Design, Sizing, & Prohibited Traps 5.2 Trap Seal Protection, Trap Arms, & Trap Primers
6 Chapter 6: Venting Methods & Design
6.1 Vent Sizing, Developed Length, & Terminations 6.2 Individual, Common, & Relief Vents 6.3 Wet Venting, Circuit Venting, & Combination Systems 6.4 Air Admittance Valves (AAV) & Island Fixture Vents
7 Chapter 7: Potable Water Supply & Distribution
7.1 Water Supply Fixture Units (WSFU) & Pipe Sizing 7.2 Water Pressure, PRVs, & Thermal Expansion 7.3 Cross-Connection Control & Backflow Devices 7.4 Water Service, Metering, & System Disinfection
8 Chapter 8: Water Heaters & Scald Prevention
8.1 Water Heater Types, Sizing, & Installation 8.2 Temperature & Pressure (T&P) Relief Valves & Discharge 8.3 Combustion Air, Venting, & Scald-Prevention Mixing Valves
9 Chapter 9: Fuel Gas Piping Systems
9.1 Fuel Gas Properties & Piping Materials (IFGC / NFPA 54) 9.2 Gas Pipe Sizing & Longest Length Method 9.3 Gas Shutoff Valves, Regulators, & Pressure Testing
10 Chapter 10: Fixtures, Faucets, & Accessibility
10.1 Fixture Clearances & Accessibility Standards (ADA) 10.2 Water Conservation & Flush Rates 10.3 Urinals, Special Fixtures, & Interceptors 10.4 Fixture Fittings, Faucets, & Accessories
11 Chapter 11: Plumbing Math & Trade Calculations
11.1 45-Degree & Rolling Offset Calculations 11.2 Grade, Fall, & Invert Elevation Calculations 11.3 Volume, Capacity, & Hydrostatic Pressure Calculations
12 Chapter 12: Isometric Drawings & TSBPE Practical Exam
12.1 Isometric Drawing Principles & Piping Schematics 12.2 TSBPE 2-Story DWV Dollhouse Design & Layout 12.3 Water & Gas Piping Schematics for Practical Stations 12.4 Hands-On Shop Skills: Brazing, Soldering, & Flaring
3.4 System Testing & Inspection Requirements
Key Takeaways Explain This Topic AI
A DWV water test uses a 10-foot head of water, and no section may be tested with less than a 10-foot head; the system is held at least 15 minutes.
The DWV air test alternative is 5 psi, or 10 inches of mercury, held 15 minutes with no pressure drop.
The IPC final DWV test is an air test at only 1 inch of water column, run after fixtures are set and traps are filled.
Water distribution piping is tested at not less than the system working pressure with water, or at 50 psi with air, and held without leakage.
Shower liners are tested by plugging the drain and filling the pan to a depth of 2 inches for 15 minutes.
Last updated: August 2026
3.4 System Testing & Inspection Requirements
Core Principle: The TSBPE examination review course lists "required types and methods of testing and inspection of the plumbing system" as one of the subjects to master in the General Regulations chapter. Testing is also where the Plumbing License Law bites hardest: Board Rule 367.5(c)(1) makes the Responsible Master Plumber personally responsible for ensuring inspections are requested , and covering work before it is inspected is a violation whether or not the pipe leaks.
1. The General Rule
New, altered, extended, or repaired piping must be tested to disclose leaks and defects , and the test is conducted by the permit holder in the presence of the code official . Piping stays exposed — not backfilled, not covered, not concealed in framing — until the test is complete and accepted. Equipment, material, and labor for the test are furnished by the permit holder.
2. Drainage and Vent System Tests
Test Medium Pressure / head Duration When used
Water test Water 10-foot head of water ; no section tested with less than a 10-foot head Hold at least 15 minutes before inspection begins Rough-in / top-out; the default DWV test
Air test Air 5 psi , or 10 inches of mercury column 15 minutes with no pressure drop Where a water test is impractical
Final test (IPC) Air 1 inch of water column Until inspected After fixtures are set and traps filled
Smoke test Smoke 1 inch of water column of smoke pressure Until all lines show at terminals Only where accepted by the AHJ
How the water test is actually run. Plug the building drain at the base and fill the system with water to the highest opening. On a tall building the whole system may be tested at once or in sections, but where sections are tested, at least the upper 10 feet of the preceding section is included so that no joint is ever proved at less than a 10-foot head. Ten feet of head is only 4.33 psi — but that head, applied at the bottom of a five-story stack, is many times higher, which is why the base plug is the failure point (see the thrust-force calculations in Chapter 11).
Note
Air test caution. Never substitute oxygen, and never assume an air test is interchangeable with the water test where the AHJ has specified water. A 5 psi air test finds a leak but does not verify that the piping will hold a real hydraulic column.
3. Building Sewer Tests
- System Test
- Gravity building sewer Water-tested with a 10-foot head of water , held 15 minutes
- Forced (pumped) sewer Tested at 5 psi greater than the pump rating , held 15 minutes
- 4. Water Supply and Distribution Tests
Upon completion of a section or of the entire hot and cold water supply system, the piping is tested and proved tight under a water pressure not less than the working pressure of the system . Where water is impractical, air at 50 psi is the accepted substitute. The system must hold without leakage — the common practical standard is 15 minutes with no measurable drop.
Remember the distinction that trips candidates up:
DWV = gravity system, tested with a head of water (10 ft) or 5 psi air .
Water distribution = pressure system, tested at working pressure or 50 psi air .
Fuel gas = tested at not less than 1.5 times the maximum working pressure but never less than 3 psig (covered in Chapter 9). Three different numbers, three different systems.
5. Component and Assembly Tests
Component Test method
Shower liner / receptor pan Plug the drain and fill the pan with water to a depth of 2 inches ; hold 15 minutes and check for leakage
Backflow prevention assemblies Tested at the time of installation , immediately after relocation or repair , and at least annually thereafter, by a qualified tester
- Reduced pressure principle assemblies Same schedule; a fouled relief port that will not close is a failed test
- Storm drainage piping Tested as drainage piping — a 10-foot head of water
- 6. The Texas Inspection Sequence +---------------------------------------------------------------------------+
- | 1. UNDERGROUND / GROUNDWORKS -- under-slab DWV and water service |
- | inspected and tested BEFORE any backfill or concrete pour. |
- | | |
- | v |
- | 2. ROUGH-IN / TOP-OUT -- DWV, vent, water, and gas piping in the |
- | framing, on test, BEFORE insulation or drywall. |
- | | |
- | v |
- | 3. FINAL -- fixtures set, traps filled, final DWV air |
- | test at 1 in w.c., water heater and gas appliances connected, |
- | backflow assemblies tested and reported. |
- +---------------------------------------------------------------------------+
Who does what in Texas:
The RMP of record must ensure permits are obtained and inspections are requested in accordance with all applicable plumbing codes (Board Rule 367.5(c)(1)). Delegating the call does not shift the responsibility.
Plumbing installed under an adopted code must be inspected by a licensed Plumbing Inspector , and the political subdivision may contract that inspection out only to a business that uses a licensed inspector, paid directly by the subdivision (Texas Occupations Code 1301.255(e), Board Rule 367.4(c)).
Each plumbing inspector shall enforce the chapter (Section 1301.503). The inspector's license number goes on every green tag or correction notice.
Municipalities of more than 5,000 inhabitants must regulate plumbing material, construction, alteration, and inspection by ordinance and require permits, though repairing leaks and replacing faucets, ballcocks, garbage disposals, and water closets are exempted from the permit requirement by statute.
7. Field Practices That Prevent a Failed Test
Cap every opening before filling. A missed test cap on a second-floor lavatory arm turns a water test into a drywall claim.
Let solvent-cemented joints cure. Below 40°F cure times lengthen dramatically; pressurizing green PVC is the most common self-inflicted failure.
Use the right gauge. A 0-to-200 psi gauge cannot resolve a 3 psi gas test or a 5 psi air test. Match gauge range and increment to the test pressure.
Watch the temperature. Air trapped in a system on a hot afternoon rises in pressure; a gauge that climbs and then falls as the sun moves is temperature, not a leak — but the inspector still needs a steady reading.
Never conceal before sign-off. Backfilled or covered work that has not been inspected can be ordered uncovered at the contractor's expense and is a documented code violation under Section 1301.452(7).