Study guide
2.3 International Treaties: The Montreal Protocol, Kigali Amendment, & TEWI
City & Guilds 2079 Level 2 Award in F-Gas & ODS Regulations Category I
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: The Refrigeration Cycle & p-h Diagrams
1.1 Thermodynamics: Sensible/Latent Heat & Pressure-Temperature Relationship 1.2 The Vapour-Compression Cycle & The Four Main Components 1.3 Superheat, Sub-cooling, & COP (Coefficient of Performance)
2 Chapter 2: Refrigerants & Environmental Impact
2.1 Refrigerant Classification 2.2 GWP and ODP Metrics & The Greenhouse Effect 2.3 International Treaties: The Montreal Protocol, Kigali Amendment, & TEWI
3 Chapter 3: Retained F-Gas & ODS Regulations
3.1 The UK Legislative Framework & Retained EU Regulation 517/2014 3.2 CO2-Equivalent Calculation & Leak-Testing Thresholds 3.3 HFC Phase-Down, Service Bans, & Placed-on-the-Market Bans
4 Chapter 4: Certification, Records & Components
4.1 Technician & Operator Certification, Record-Keeping Requirements 4.2 Major System Components 4.3 Auxiliary Components
5 Chapter 5: Tools & Leak Detection Methods
Service Valves, Manifold Gauges, and System Interface Tools Leak Inspection Methods: Direct vs. Indirect & Statutory Frequencies Leak Detector Sensitivity & Fixed Leak Detection Systems
6 Chapter 6: Leak Repair, Pressure Testing & Recovery
6.1 Strength & Leak Pressure Testing using OFN 6.2 Follow-Up Testing & Repair Procedures 6.3 Recovery Operations, Cylinders, Safety, & Venting Prohibition
7 Chapter 7: Refrigerant Management, Safety & Standards
7.1 Recovery vs. Recycling vs. Reclamation vs. Destruction 7.2 Workplace Safety: HASAWA 1974, COSHH, PPE, & Safe Isolation 7.3 Safety Standards & Flammability: BS EN 378 & A2L/A3 Refrigerants
2.3 International Treaties: The Montreal Protocol, Kigali Amendment, & TEWI
Key Takeaways Explain This Topic AI
The Montreal Protocol (1987) successfully mandated the global phase-out of ozone-depleting substances (ODS), notably CFCs and HCFCs.
The Kigali Amendment (2016) updated the Montreal Protocol to legally phase down high-GWP HFCs, shifting the focus from ozone protection to climate change mitigation.
TEWI (Total Equivalent Warming Impact) is a comprehensive calculation of a refrigeration system's environmental footprint.
TEWI accounts for Direct Emissions (refrigerant leaks during lifetime and disposal) and Indirect Emissions (carbon dioxide emitted by power plants to generate the electricity the system uses).
Improving system energy efficiency is often the most effective way to lower a system's TEWI, as indirect emissions typically represent the vast majority of a system's carbon footprint.
Last updated: July 2026
The refrigeration and air conditioning industry operates under strict international laws designed to protect the environment. As scientific understanding of ozone depletion and climate change has evolved, so too have the international treaties dictating which refrigerants can be produced, sold, and utilized. Understanding these frameworks is vital for contextualizing national F-Gas regulations and calculating the true environmental impact of a system.
The Montreal Protocol
Adopted in 1987, the Montreal Protocol on Substances that Deplete the Ozone Layer is widely considered the most successful environmental treaty in human history. Prompted by the discovery of a massive "hole" in the ozone layer over Antarctica, the treaty established legally binding, time-targeted phase-out schedules for ozone-depleting substances (ODS).
The primary targets of the initial protocol were CFCs (like R-11 and R-12). In developed nations, CFC production was completely halted by the mid-1990s. The protocol later targeted HCFCs (like R-22) as a secondary phase-out. In the UK and the European Union, the use of virgin HCFCs was banned in 2010, and the use of even reclaimed or recycled HCFCs was fully banned at the end of 2014. Thanks to the Montreal Protocol, the stratospheric ozone layer is currently healing and is projected to recover to pre-1980 levels by the middle of the 21st century.
The Kigali Amendment
While the Montreal Protocol successfully solved the ozone crisis by forcing the industry to adopt HFCs, it inadvertently exacerbated a new crisis: global warming. Because HFCs possess zero ODP, they were not restricted by the original Montreal Protocol, despite having exceptionally high GWPs.
To correct this, the international community adopted the Kigali Amendment to the Montreal Protocol in 2016. The Kigali Amendment is a landmark agreement that legally binds nations to drastically phase down the production and consumption of HFCs. Unlike CFCs, which were "phased out" (banned entirely), HFCs are being "phased down" (gradually reduced to a fraction of historical baselines).
In the UK and EU, the Kigali Amendment is implemented via the F-Gas Regulations , which employ a quota system to forcefully reduce the availability of high-GWP HFCs, driving up their price and forcing the market to transition to low-GWP alternatives like HFOs and natural refrigerants (CO2, ammonia, and hydrocarbons).
Total Equivalent Warming Impact (TEWI)
When assessing the environmental impact of a refrigeration or air conditioning system, looking solely at the GWP of the refrigerant inside the pipes is insufficient. A system impacts the climate in two ways: through the refrigerant it leaks, and through the electricity it consumes.
Total Equivalent Warming Impact (TEWI) is an engineering metric that calculates the comprehensive lifetime greenhouse gas emissions of a system. A TEWI calculation is broken down into two distinct components:
1. Direct Emissions: This is the climate impact caused directly by the refrigerant escaping into the atmosphere. It is calculated by multiplying the refrigerant's GWP by the mass of refrigerant leaked over the system's operational lifetime, plus the refrigerant that is lost and unrecovered during final end-of-life disposal.
2. Indirect Emissions: This is the climate impact caused by the energy consumption of the system. Refrigeration systems use vast amounts of electricity to power compressors, fans, and pumps. This electricity is typically generated by burning fossil fuels at a power plant, which releases massive amounts of CO2. Indirect emissions are calculated by multiplying the system's lifetime energy consumption (in kWh) by the CO2 emission factor of the local electrical grid (kg CO2 per kWh).
The TEWI Equation
To calculate TEWI precisely, engineers use a standardized formula that separates direct leakage, recovery losses, and operational energy consumption: TEWI = Direct Emissions + Indirect Emissions \text{TEWI} = \text{Direct Emissions} + \text{Indirect Emissions} TEWI = Direct Emissions + Indirect Emissions TEWI = ( GWP × L × n ) + ( GWP × m × ( 1 − α ) ) + ( E a × β × n ) \text{TEWI} = (\text{GWP} \times L \times n) + (\text{GWP} \times m \times (1 - \alpha)) + (E_a \times \beta \times n) TEWI = ( GWP × L × n ) + ( GWP × m × ( 1 − α )) + ( E a × β × n )
- Variable Description Units / Format
- GWP Global Warming Potential of the refrigerant Dimensionless (relative to CO2 = 1.0)
- L Annual leakage rate kg / year
- n Operating life of the system years
- m Refrigerant charge mass kg
- α \alpha α Recovery factor at end-of-life Fraction between 0.0 and 1.0 (e.g. 0.90 for 90% recovery)
- E a E_a E a Annual energy consumption kWh / year
- β \beta β Carbon dioxide emission factor of the electricity grid kg CO2 / kWh
- Direct vs. Indirect Comparison
Understanding the balance between direct and indirect contributions is essential for sustainable system design:
Feature Direct Emissions Indirect Emissions
Primary Cause Physical leaks, pipe ruptures, component replacement, improper recovery Power station fossil-fuel combustion to supply electricity to the compressor and fans
Control Mechanism Leak testing, high-quality joints, preventative maintenance, low-loss hoses High COP design, variable speed drives, clean heat exchangers, thermostatic optimization
Share of Impact Typically 5% to 20% in well-maintained systems Typically 80% to 95% in commercial and industrial systems
In almost all traditional refrigeration and air conditioning systems, Indirect Emissions account for the vast majority of the total TEWI. This means that while selecting a low-GWP refrigerant is legally necessary and environmentally responsible, ensuring the system operates with high energy efficiency is mathematically the most effective way to reduce its carbon footprint.
For example, if an engineer replaces a high-GWP refrigerant with a low-GWP alternative, but the new refrigerant is highly inefficient and causes the compressor to run 30% longer, the massive increase in indirect emissions from the power grid could actually result in a higher overall TEWI, worsening the system's climate impact. Conversely, implementing variable-speed compressors, optimising setpoints, and ensuring regular coil cleaning directly reduces E a E_a E a , driving down the dominant indirect term.