3.2 CO2-Equivalent Calculation & Leak-Testing Thresholds
City & Guilds 2079 Level 2 Award in F-Gas & ODS Regulations Category I
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: The Refrigeration Cycle & p-h Diagrams
1.1 Thermodynamics: Sensible/Latent Heat & Pressure-Temperature Relationship 1.2 The Vapour-Compression Cycle & The Four Main Components 1.3 Superheat, Sub-cooling, & COP (Coefficient of Performance)
2 Chapter 2: Refrigerants & Environmental Impact
2.1 Refrigerant Classification 2.2 GWP and ODP Metrics & The Greenhouse Effect 2.3 International Treaties: The Montreal Protocol, Kigali Amendment, & TEWI
3 Chapter 3: Retained F-Gas & ODS Regulations
3.1 The UK Legislative Framework & Retained EU Regulation 517/2014 3.2 CO2-Equivalent Calculation & Leak-Testing Thresholds 3.3 HFC Phase-Down, Service Bans, & Placed-on-the-Market Bans
4 Chapter 4: Certification, Records & Components
4.1 Technician & Operator Certification, Record-Keeping Requirements 4.2 Major System Components 4.3 Auxiliary Components
5 Chapter 5: Tools & Leak Detection Methods
Service Valves, Manifold Gauges, and System Interface Tools Leak Inspection Methods: Direct vs. Indirect & Statutory Frequencies Leak Detector Sensitivity & Fixed Leak Detection Systems
6 Chapter 6: Leak Repair, Pressure Testing & Recovery
6.1 Strength & Leak Pressure Testing using OFN 6.2 Follow-Up Testing & Repair Procedures 6.3 Recovery Operations, Cylinders, Safety, & Venting Prohibition
7 Chapter 7: Refrigerant Management, Safety & Standards
7.1 Recovery vs. Recycling vs. Reclamation vs. Destruction 7.2 Workplace Safety: HASAWA 1974, COSHH, PPE, & Safe Isolation 7.3 Safety Standards & Flammability: BS EN 378 & A2L/A3 Refrigerants
3.2 CO2-Equivalent Calculation & Leak-Testing Thresholds
Key Takeaways Explain This Topic AI
CO2e standardizes the environmental impact of F-gases based on their Global Warming Potential (GWP).
The formula for CO2e in tonnes is (Weight in kg × GWP) ÷ 1000.
Mandatory leak testing intervals are 12, 6, and 3 months for 5, 50, and 500 tonnes CO2e respectively.
Having a fixed automatic leak detection system halves the required frequency of manual leak tests.
Hermetically sealed systems benefit from a higher threshold, requiring leak tests only at 10 tonnes CO2e.
Last updated: July 2026
The shift from measuring refrigerant charges strictly by their physical weight (kilograms) to evaluating their environmental impact via Carbon Dioxide Equivalent (CO2e) was one of the most critical changes introduced by EU Regulation 517/2014. Because different fluorinated greenhouse gases have vastly different Global Warming Potentials (GWP), treating 10 kg of R-134a the same as 10 kg of R-404A fails to account for the true climate damage a leak would cause. The CO2e metric solves this by standardizing the impact of all F-gases against carbon dioxide. Understanding how to calculate CO2e and how it dictates mandatory leak-testing frequencies is essential for Category I engineers.
The CO2 Equivalent (CO2e) Formula
Carbon Dioxide Equivalent is a measure used to compare the emissions from various greenhouse gases based upon their global warming potential. The GWP of carbon dioxide is always 1. If a refrigerant has a GWP of 2000, it means that releasing one kilogram of that refrigerant traps 2000 times more heat in the atmosphere than releasing one kilogram of CO2.
The formula to convert the physical charge of a system (in kilograms) into tonnes of CO2 equivalent is:
CO2e (in tonnes) = (Weight of Refrigerant in kg × GWP of Refrigerant) ÷ 1000
Alternatively, if you know the threshold in tonnes of CO2e and need to find the maximum allowed charge in kilograms, the formula is rearranged:
- Maximum Charge (kg) = (Threshold in Tonnes CO2e × 1000) ÷ GWP of Refrigerant
- Worked Example 1: Calculating CO2e
A supermarket pack system holds 45 kg of R-404A. The GWP of R-404A is 3922. What is the CO2e of this system?
- Weight = 45 kg
- GWP = 3922
Calculation : (45 × 3922) / 1000 = 176,490 / 1000 = 176.49 tonnes CO2e.
Despite holding a relatively moderate physical charge, this system represents a massive climate risk.
Worked Example 2: Determining Maximum Charge for a Threshold
You are installing a new R-32 air conditioning system (GWP of R-32 is 675) and want to know how many kilograms you can install before hitting the 50 tonnes CO2e threshold that mandates more frequent leak checks.
- Target CO2e = 50 tonnes
- GWP = 675
Calculation : (50 × 1000) / 675 = 50,000 / 675 = 74.07 kg.
You can install up to 74.07 kg of R-32 before crossing the 50-tonne CO2e boundary.
Leak-Testing Frequencies and CO2e Bands
The Retained F-Gas Regulation establishes mandatory, periodic leak-testing intervals based solely on the CO2e of the system's charge. As the environmental risk increases, the testing must become more frequent. There are three primary tiers:
- CO2e Threshold Minimum Leak Testing Frequency Frequency with Fixed Automatic Leak Detection
- 5 to < 50 tonnes CO2e Every 12 months Every 24 months
- 50 to < 500 tonnes CO2e Every 6 months Every 12 months
- 500+ tonnes CO2e Every 3 months Every 6 months
Note: Systems with a charge of 500 tonnes CO2e or more are legally required to have a fixed, automatic leak detection system installed. Therefore, in practice, their manual testing frequency is usually halved to every 6 months, but the detection system itself must be checked every 12 months.
The Hermetic Exemption
There is an important exemption for hermetically sealed equipment (such as domestic refrigerators, small self-contained display cabinets, or plug-in water coolers). For standard split systems or built-up field installations, the leak testing requirements begin at 5 tonnes CO2e. However, if the equipment is hermetically sealed and correctly labeled as such by the manufacturer, the mandatory leak-testing threshold is doubled to 10 tonnes CO2e .
To qualify for this exemption, the system must have a tested leak rate of less than 3 grams per year under a pressure of at least a quarter of its maximum allowable pressure, and all its refrigerant-containing parts must be permanently sealed by welding, brazing, or a similar permanent connection. Valves and capped service ports are permitted, provided they are securely sealed.
Practical Application on the Job
As an engineer, you must check the system logbook or the equipment data plate upon arrival at a site. If the data plate only lists the charge in kilograms and the refrigerant type, you must manually calculate the CO2e to determine the correct testing interval. If you service an R-410A (GWP 2088) system with a 3 kg charge:
CO2e = (3 × 2088) / 1000 = 6.26 tonnes CO2e.
Because 6.26 is greater than 5, this system requires a mandatory leak test at least once every 12 months. If the operator lacks a logbook for this system, they are currently in breach of the regulations, and it is your duty to inform them and initiate the proper record-keeping procedures.