Study guide
8.4 Electronic Components in Electrical Systems
City & Guilds 2365 Level 2 Diploma in Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Qualification Overview
1.1 About the City & Guilds 2365 Level 2 Qualification 1.2 Study Strategy, Exam Technique & Resource Navigation
2 Health, Safety & Environmental Legislation, Risk Assessment & Permits
2.1 Statutory Framework & Health and Safety Law 2.2 Hazardous Substances, Incident Reporting & Welfare 2.3 Work Equipment, Manual Handling & PPE 2.4 Environmental Legislation, Pollution & Site Waste 2.5 Risk Assessments, Method Statements, Permits to Work & Safety Signs
3 Electrical Safety, Safe Isolation, Site Hazards & Emergencies
3.1 Safe Isolation Procedures & GS38 Compliance 3.2 Electrical Hazards & Electric Shock Physiology 3.3 Fire Safety, Site Supplies & Emergency Response 3.4 Accidents, First Aid, Emergency Procedures & Reporting
4 Working at Height & Access Equipment
4.1 Work at Height Regulations & Risk Management 4.2 Ladders, Stepladders & Podiums 4.3 Mobile Access Towers & Scaffolding Systems
5 Mathematical Principles, Units & Basic Mechanics
5.1 Mathematical Foundations & Transposition for Electricians 5.2 SI Units of Measurement in Electrotechnology 5.3 Basic Mechanics: Force, Work, Power & Mechanical Energy 5.4 Mass, Weight, Levers, Gears & Pulleys
6 Electron Theory, Resistance, Resistivity & DC Circuits
6.1 Resistance, Resistivity & Conductor Dimensions 6.2 Temperature Coefficient of Resistance 6.3 Ohm's Law, Power & Direct Current Calculations 6.4 Series, Parallel & Combination DC Circuits 6.5 Electron Theory, Conductors, Insulators & the Effects of Current
7 Magnetism, Electromagnetism & Transformers
7.1 Magnetic Fields, Flux & Solenoid Properties 7.2 Electromagnetic Induction & Motor/Generator Principles 7.3 Transformer Principles, Construction & Calculations
8 Alternating Current, Three-Phase Systems & Electronic Components
8.1 AC Waveform Generation & Key Values 8.2 AC Circuit Theory: Reactance, Impedance & Power Factor 8.3 Three-Phase Generation, Star-Delta & UK Distribution 8.4 Electronic Components in Electrical Systems
9 Industry Regulations, Technical Information & Drawings
9.1 Electrical Regulations, Standards & Part P 9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols 9.3 Technical Specifications, Schedules & Environmental Influences
10 Wiring Systems, Cables, Containment & Practical Installation
10.1 Thermoplastic, Armoured & Flexible Cables 10.2 Specialised Cables: MICC & Fire-Performance Cables 10.3 Conduit Systems: Steel & PVC 10.4 Trunking, Cable Tray & Cable Supports 10.5 Unit 204 Practical Skills: Tools, Preparation & Installing Wiring Systems
11 Final Circuits, Protective Devices, Alarm & Control Circuits
11.1 Lighting Circuits & Switching Arrangements 11.2 Power Circuits: Ring Final, Radial & Dedicated Circuits 11.3 Consumer Units, Distribution Boards & Protective Devices 11.4 Alarm, Emergency Lighting, Data & Control Circuits
12 Cable Selection & Structural Installation
12.1 Cable Current-Carrying Capacity & Correction Factors 12.2 Voltage Drop Principles & Calculations 12.3 Structural Integrity & Concealed Cable Routing
13 Supply Systems, Earthing, Shock Protection & Micro-Renewables
13.1 UK Electricity Supply Networks & Distribution 13.2 Earthing System Configurations: TN-S, TN-C-S (PME and PNB) & TT 13.3 Protective Conductors, Bonding & Earth Electrodes 13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs 13.5 Micro-Renewable Energy Technologies
14 Electrical Inspection & Dead Testing Sequence
14.1 Inspection Principles & Testing Safety to GS38 14.2 Continuity Testing: Protective Conductors & Ring Circuits 14.3 Insulation Resistance & Polarity Verification
15 Live Testing, Certification & Handover
15.1 Live Testing: Earth Loop Impedance, PFC & RCD Testing 15.2 Certification, Handover & Commissioning
16 Communicating within Building Services Engineering (Unit 210)
16.1 The Construction Team: Site Management, Trades & Site Visitors 16.2 Information Sources: Legislation, Guidance & Workplace Documents 16.3 Customer Information, Company Policies & Limits of Authority 16.4 Communicating Effectively: Methods, Accessibility & Conflict
8.4 Electronic Components in Electrical Systems
Key Takeaways Explain This Topic AI
A diode conducts in one direction only (about 0.7 V forward drop for silicon), and four diodes in a bridge rectifier convert a.c. into full-wave d.c.
A Zener diode is used in reverse breakdown to hold a fixed voltage, and an LED needs a series resistor or a driver to limit its current.
NTC thermistors lose resistance as temperature rises and are used as temperature sensors, while light-dependent resistors lose resistance as light increases and are used in photocells.
A thyristor conducts in one direction once triggered at its gate, a triac conducts in both directions, and a diac is the trigger device used with a triac in a dimmer.
Transistors act as electronic switches or amplifiers, and inverters convert d.c. to a.c. for PV systems, UPS units and variable speed drives.
Last updated: October 2026
8.4 Electronic Components in Electrical Systems
Unit 202 learning outcome 6 (4 of the 40 test questions) asks you to describe the function, applications and basic operating principles of the electronic components found in electrical systems. The range lists capacitors, resistors, rectifiers, diodes, Zener diodes, LEDs, photo devices, thermistors, diacs, triacs, transistors, thyristors and inverters, used in security alarms, telephones, dimmer switches, heating and boiler controls, motor control and wireless control systems.
- Passive Components
- Resistors
Resistors limit current and divide voltage. They may be fixed (carbon film, metal film or wire-wound for higher power) or variable (potentiometers and presets, such as the control knob of a dimmer). A resistor is specified by its resistance and its power rating in watts. Small resistors are marked with coloured bands: for example, brown (1), black (0) and red (× 100) gives 10 × 100 = 1,000 Ω 10 \times 100 = 1{,}000\ \Omega 10 × 100 = 1 , 000 Ω (1 kΩ).
Capacitors
A capacitor stores electric charge on two plates separated by an insulating dielectric . Capacitance is measured in farads (in practice microfarads, nanofarads or picofarads), and the charge stored is Q = C V Q = CV Q = C V : a 100 µF capacitor charged to 12 V holds 100 × 10 − 6 × 12 = 1.2 × 10 − 3 100 \times 10^{-6} \times 12 = 1.2 \times 10^{-3} 100 × 1 0 − 6 × 12 = 1.2 × 1 0 − 3 C (1.2 mC).
A capacitor blocks steady d.c. but passes a.c. Uses include smoothing the output of power supplies, start and run capacitors for single-phase motors, power factor correction, suppressing interference, and timing circuits. Electrolytic capacitors are polarised and must be connected the right way round.
Warning
Capacitors can hold a dangerous charge after the supply is switched off. Discharge them safely, or wait for the manufacturer's stated time, before touching their terminals.
- Semiconductor Devices
- Diodes
A diode is a p-n junction that lets current flow in one direction only. When forward biased it conducts once the voltage across it exceeds about 0.6 to 0.7 V (for silicon); when reverse biased it blocks current until its breakdown voltage is reached. On a circuit symbol the arrow points in the direction of conventional current, from the anode to the cathode (marked by a bar).
Uses include rectification, protection against reversed polarity, and flywheel (suppression) diodes across relay and contactor coils, which absorb the back e.m.f. produced when the coil is switched off (Section 7.2).
Rectifiers
A rectifier converts a.c. into d.c.:
- Type How it works Output
- Half-wave One diode passes only the positive half-cycles Pulsating d.c. with gaps; inefficient
Full-wave bridge Four diodes route both half-cycles the same way through the load Pulsating d.c. at twice the supply frequency, then smoothed by a capacitor
Rectifiers are found in battery chargers, LED drivers, d.c. supplies for alarms and controls, and emergency lighting.
Zener diodes
A Zener diode is designed to operate in reverse breakdown at a precise voltage (for example 5.1 V or 12 V). With a series resistor it holds a steady voltage across a load, so it is used as a simple voltage regulator or reference and for overvoltage protection.
Light-emitting diodes (LEDs)
An LED gives out light when forward biased. Its forward voltage is roughly 2 V for red LEDs and about 3 V or more for white and blue ones. Its current must be limited by a series resistor or a constant-current driver.
Example: a 2 V, 20 mA indicator LED run from a 12 V supply needs a series resistor of R = ( 12 − 2 ) ÷ 0.02 = 500 Ω R = (12 - 2) \div 0.02 = 500\ \Omega R = ( 12 − 2 ) ÷ 0.02 = 500 Ω (a 510 Ω preferred value would be chosen).
Photo devices
A light-dependent resistor (LDR) has a resistance that falls as the light level rises. It is used in dusk-to-dawn photocell switches for external lighting.
Photodiodes and phototransistors respond quickly to light and are used in light sensors and beam detectors.
Photovoltaic cells generate electricity directly from light (Section 13.5).
Thermistors
A thermistor is a resistor whose resistance changes sharply with temperature:
NTC (negative temperature coefficient): resistance falls as temperature rises. Used as temperature sensors in boilers, hot water cylinders and electronic thermostats, and to limit inrush current.
PTC (positive temperature coefficient): resistance rises sharply above a set temperature. Used in motor winding protection and self-regulating heaters.
Loading diagram... Traditional Leading-Edge Dimmer: Diac Triggering a Triac
Transistors
A transistor has three terminals (base, collector and emitter for a bipolar transistor; gate, drain and source for a MOSFET). A small current or voltage at the base or gate controls a much larger current through the device, so a transistor can act as an electronic switch or as an amplifier . Transistors switch relays from low-power control circuits, amplify signals in telephones and door-entry systems, run alarm panels, and are the switching devices in trailing-edge dimmers and inverters.
Thyristors
A thyristor (silicon-controlled rectifier, SCR) has an anode, a cathode and a gate . It blocks current until a small pulse is applied to the gate; it then conducts in one direction until the current falls below its holding current, for example when an a.c. supply passes through zero. By delaying the gate pulse in each half-cycle, a thyristor controls the power delivered to d.c. motors, heaters and battery chargers, and it is used in soft starters.
Diacs
A diac is a two-terminal trigger device. It does not conduct until the voltage across it reaches its breakover voltage (typically around 30 V), in either direction, and then it conducts suddenly. Its main job is to deliver a sharp trigger pulse to the gate of a triac.
Triacs
A triac behaves like two thyristors connected back to back with a common gate, so it can be triggered to conduct in both directions . It is the power-control device in leading-edge dimmers, speed controllers for fans and small universal motors, heater controls and solid-state relays.
Inverters
An inverter converts d.c. into a.c. by switching transistors (such as IGBTs or MOSFETs) rapidly. Inverters connect PV panels and batteries to the a.c. supply, provide mains power in UPS units and central battery systems, and form the output stage of variable speed drives , which rectify the supply to d.c. and then invert it to a variable frequency to control motor speed.
Where You Will Meet These Components
System (from the Unit 202 range) Typical components What they do
Security alarms PIR detectors, transistors, microcontrollers, LEDs, rechargeable battery with a rectifier-based charger Detect movement, process signals, drive sounders and keep the system running in a power cut
Telephones and door entry Capacitors, diodes, transistors, integrated circuits Amplify and route signals and protect against reversed polarity and surges
Dimmer switches Diac and triac (leading edge), or MOSFET/IGBT (trailing edge), potentiometer and capacitor Phase control: switch on part-way through each half-cycle to vary the power to the lamp
Heating and boiler controls Thermistors, transistors, relays, microcontrollers Sense temperatures and switch pumps, valves and burners
Motor control Thyristors, triacs, rectifiers, inverters (variable speed drives), transistors Soft starting, speed control, reversing and braking
Wireless control systems Radio transmitter and receiver modules, transistors, batteries Switch lighting, heating, blinds and alarms remotely
Important