Study guide
5.2 SI Units of Measurement in Electrotechnology
City & Guilds 2365 Level 2 Diploma in Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Qualification Overview
1.1 About the City & Guilds 2365 Level 2 Qualification 1.2 Study Strategy, Exam Technique & Resource Navigation
2 Health, Safety & Environmental Legislation, Risk Assessment & Permits
2.1 Statutory Framework & Health and Safety Law 2.2 Hazardous Substances, Incident Reporting & Welfare 2.3 Work Equipment, Manual Handling & PPE 2.4 Environmental Legislation, Pollution & Site Waste 2.5 Risk Assessments, Method Statements, Permits to Work & Safety Signs
3 Electrical Safety, Safe Isolation, Site Hazards & Emergencies
3.1 Safe Isolation Procedures & GS38 Compliance 3.2 Electrical Hazards & Electric Shock Physiology 3.3 Fire Safety, Site Supplies & Emergency Response 3.4 Accidents, First Aid, Emergency Procedures & Reporting
4 Working at Height & Access Equipment
4.1 Work at Height Regulations & Risk Management 4.2 Ladders, Stepladders & Podiums 4.3 Mobile Access Towers & Scaffolding Systems
5 Mathematical Principles, Units & Basic Mechanics
5.1 Mathematical Foundations & Transposition for Electricians 5.2 SI Units of Measurement in Electrotechnology 5.3 Basic Mechanics: Force, Work, Power & Mechanical Energy 5.4 Mass, Weight, Levers, Gears & Pulleys
6 Electron Theory, Resistance, Resistivity & DC Circuits
6.1 Resistance, Resistivity & Conductor Dimensions 6.2 Temperature Coefficient of Resistance 6.3 Ohm's Law, Power & Direct Current Calculations 6.4 Series, Parallel & Combination DC Circuits 6.5 Electron Theory, Conductors, Insulators & the Effects of Current
7 Magnetism, Electromagnetism & Transformers
7.1 Magnetic Fields, Flux & Solenoid Properties 7.2 Electromagnetic Induction & Motor/Generator Principles 7.3 Transformer Principles, Construction & Calculations
8 Alternating Current, Three-Phase Systems & Electronic Components
8.1 AC Waveform Generation & Key Values 8.2 AC Circuit Theory: Reactance, Impedance & Power Factor 8.3 Three-Phase Generation, Star-Delta & UK Distribution 8.4 Electronic Components in Electrical Systems
9 Industry Regulations, Technical Information & Drawings
9.1 Electrical Regulations, Standards & Part P 9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols 9.3 Technical Specifications, Schedules & Environmental Influences
10 Wiring Systems, Cables, Containment & Practical Installation
10.1 Thermoplastic, Armoured & Flexible Cables 10.2 Specialised Cables: MICC & Fire-Performance Cables 10.3 Conduit Systems: Steel & PVC 10.4 Trunking, Cable Tray & Cable Supports 10.5 Unit 204 Practical Skills: Tools, Preparation & Installing Wiring Systems
11 Final Circuits, Protective Devices, Alarm & Control Circuits
11.1 Lighting Circuits & Switching Arrangements 11.2 Power Circuits: Ring Final, Radial & Dedicated Circuits 11.3 Consumer Units, Distribution Boards & Protective Devices 11.4 Alarm, Emergency Lighting, Data & Control Circuits
12 Cable Selection & Structural Installation
12.1 Cable Current-Carrying Capacity & Correction Factors 12.2 Voltage Drop Principles & Calculations 12.3 Structural Integrity & Concealed Cable Routing
13 Supply Systems, Earthing, Shock Protection & Micro-Renewables
13.1 UK Electricity Supply Networks & Distribution 13.2 Earthing System Configurations: TN-S, TN-C-S (PME and PNB) & TT 13.3 Protective Conductors, Bonding & Earth Electrodes 13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs 13.5 Micro-Renewable Energy Technologies
14 Electrical Inspection & Dead Testing Sequence
14.1 Inspection Principles & Testing Safety to GS38 14.2 Continuity Testing: Protective Conductors & Ring Circuits 14.3 Insulation Resistance & Polarity Verification
15 Live Testing, Certification & Handover
15.1 Live Testing: Earth Loop Impedance, PFC & RCD Testing 15.2 Certification, Handover & Commissioning
16 Communicating within Building Services Engineering (Unit 210)
16.1 The Construction Team: Site Management, Trades & Site Visitors 16.2 Information Sources: Legislation, Guidance & Workplace Documents 16.3 Customer Information, Company Policies & Limits of Authority 16.4 Communicating Effectively: Methods, Accessibility & Conflict
5.2 SI Units of Measurement in Electrotechnology
Key Takeaways Explain This Topic AI
The International System of Units (SI) establishes four primary base units used in electrotechnology: meter (m) for length, kilogram (kg) for mass, second (s) for time, and ampere (A) for electric current.
Derived electrotechnical units are formed from combinations of base units: the Volt ( 1 V = 1 J/C 1\text{ V} = 1\text{ J/C} 1 V = 1 J/C ), the Ohm ( 1 Ω = 1 V/A 1\ \Omega = 1\text{ V/A} 1 Ω = 1 V/A ), the Coulomb ( 1 C = 1 A ⋅ s 1\text{ C} = 1\text{ A}\cdot\text{s} 1 C = 1 A ⋅ s ), and the Watt ( 1 W = 1 J/s 1\text{ W} = 1\text{ J/s} 1 W = 1 J/s ).
Magnetic and alternating current parameters have dedicated derived units: magnetic flux in Webers (Wb), magnetic flux density in Teslas ( 1 T = 1 Wb/m 2 1\text{ T} = 1\text{ Wb/m}^2 1 T = 1 Wb/m 2 ), inductance in Henrys (H), capacitance in Farads (F), and frequency in Hertz ( 1 Hz = 1 s − 1 1\text{ Hz} = 1\text{ s}^{-1} 1 Hz = 1 s − 1 ).
SI prefixes scale base and derived units in powers of ten; engineering calculations primarily utilize multiples of three: Mega ( 10 6 10^6 1 0 6 ), Kilo ( 10 3 10^3 1 0 3 ), Milli ( 10 − 3 10^{-3} 1 0 − 3 ), Micro ( 10 − 6 10^{-6} 1 0 − 6 ), Nano ( 10 − 9 10^{-9} 1 0 − 9 ), and Pico ( 10 − 12 10^{-12} 1 0 − 12 ).
Converting conductor cross-sectional area from square millimeters ( mm 2 \text{mm}^2 mm 2 ) to square meters ( m 2 \text{m}^2 m 2 ) requires multiplying by 10 − 6 10^{-6} 1 0 − 6 because area scales with the square of the linear conversion factor ( 1 mm = 10 − 3 m ⟹ 1 mm 2 = 10 − 6 m 2 1\text{ mm} = 10^{-3}\text{ m} \implies 1\text{ mm}^2 = 10^{-6}\text{ m}^2 1 mm = 1 0 − 3 m ⟹ 1 mm 2 = 1 0 − 6 m 2 ).
Last updated: October 2026
5.2 SI Units of Measurement in Electrotechnology
In electrotechnical engineering, accurate communication and calculation depend on the International System of Units ( Système International d'Unités , abbreviated SI ). Standardized units ensure that electrical quantities measured on site—such as loop impedance, insulation resistance, voltage drop, and luminous flux—can be directly verified against the criteria published in BS 7671 (IET Wiring Regulations).
SI Base Units in Electrotechnology
The SI system is constructed upon seven fundamental base units, four of which form the bedrock of electrical and mechanical calculations:
Length — Meter ( m \text{m} m ): The fundamental unit of distance, cable runs, and physical dimensions.
Mass — Kilogram ( kg \text{kg} kg ): The fundamental measure of the quantity of matter in an object, used to calculate gravitational weight and mechanical force.
Time — Second ( s \text{s} s ): The fundamental unit of time duration, used in defining frequency, current rate, velocity, and power.
Electric Current — Ampere ( A \text{A} A ): The fundamental electrical base unit, formally defined in terms of elementary charge flow ( 1 A ≈ 6.242 × 10 18 1\text{ A} \approx 6.242 \times 10^{18} 1 A ≈ 6.242 × 1 0 18 electrons passing a cross-section per second).
Note
In the SI system, the Ampere (A) is the base unit, not the Coulomb (C). The Coulomb is a derived unit defined as the quantity of electric charge transported by a constant current of one ampere in one second ( 1 C = 1 A ⋅ s 1\text{ C} = 1\text{ A}\cdot\text{s} 1 C = 1 A ⋅ s ).
Derived Electrotechnical Units
All electrical and magnetic units other than the Ampere are derived units , constructed by combining the base units of mass, length, time, and electric current.
Quantity Symbol Unit Name Unit Abbr. Base SI / Physical Definition Electrical Relationship
Potential Difference / EMF V V V or E E E Volt V \text{V} V 1 V = 1 J/C = 1 W/A 1\text{ V} = 1\text{ J/C} = 1\text{ W/A} 1 V = 1 J/C = 1 W/A Energy transferred per unit electric charge
Electrical Resistance R R R Ohm Ω \Omega Ω 1 Ω = 1 V/A 1\ \Omega = 1\text{ V/A} 1 Ω = 1 V/A Opposition to the flow of electric current
Electric Charge Q Q Q Coulomb C \text{C} C 1 C = 1 A ⋅ s 1\text{ C} = 1\text{ A}\cdot\text{s} 1 C = 1 A ⋅ s Charge transferred by 1 A 1\text{ A} 1 A in 1 s 1\text{ s} 1 s ( Q = I × t Q = I \times t Q = I × t )
Electrical Power P P P Watt W \text{W} W 1 W = 1 J/s = 1 V ⋅ A 1\text{ W} = 1\text{ J/s} = 1\text{ V}\cdot\text{A} 1 W = 1 J/s = 1 V ⋅ A Rate of doing work or transferring electrical energy
Energy / Work W W W or E E E Joule J \text{J} J 1 J = 1 N ⋅ m = 1 W ⋅ s 1\text{ J} = 1\text{ N}\cdot\text{m} = 1\text{ W}\cdot\text{s} 1 J = 1 N ⋅ m = 1 W ⋅ s Work done when a force of 1 N 1\text{ N} 1 N moves through 1 m 1\text{ m} 1 m
Frequency f f f Hertz Hz \text{Hz} Hz 1 Hz = 1 cycle/s = 1 s − 1 1\text{ Hz} = 1\text{ cycle/s} = 1\text{ s}^{-1} 1 Hz = 1 cycle/s = 1 s − 1 Number of complete alternating cycles per second
Magnetic Flux Φ \Phi Φ Weber Wb \text{Wb} Wb 1 Wb = 1 V ⋅ s 1\text{ Wb} = 1\text{ V}\cdot\text{s} 1 Wb = 1 V ⋅ s Total quantity of magnetic field lines produced
Magnetic Flux Density B B B Tesla T \text{T} T 1 T = 1 Wb/m 2 1\text{ T} = 1\text{ Wb/m}^2 1 T = 1 Wb/m 2 Magnetic flux passing per unit perpendicular area
Capacitance C C C Farad F \text{F} F 1 F = 1 C/V 1\text{ F} = 1\text{ C/V} 1 F = 1 C/V Charge stored per unit potential difference
Inductance L L L Henry H \text{H} H 1 H = 1 V ⋅ s/A 1\text{ H} = 1\text{ V}\cdot\text{s/A} 1 H = 1 V ⋅ s/A Induced EMF of 1 V 1\text{ V} 1 V when current changes at 1 A/s 1\text{ A/s} 1 A/s
In-Depth Unit Analysis
The Volt ( V \text{V} V ): A potential difference of one volt exists between two points if one joule of energy is released or absorbed in moving one coulomb of charge between those points ( V = W Q V = \frac{W}{Q} V = Q W ). It also represents the potential difference that drives one ampere of current through a resistance of one ohm ( V = I × R V = I \times R V = I × R ).
The Ohm ( Ω \Omega Ω ): Named after Georg Simon Ohm, one ohm is the electrical resistance between two points of a conductor when a constant potential difference of one volt applied between these points produces a current of one ampere ( R = V I R = \frac{V}{I} R = I V ).
The Watt ( W \text{W} W ): Named after James Watt, one watt represents one joule of energy transferred per second ( P = W t P = \frac{W}{t} P = t W ). In direct current circuits, one watt is produced when a current of one ampere flows under a pressure of one volt ( P = V × I P = V \times I P = V × I ).
The Joule ( J \text{J} J ) and the Kilowatt-Hour ( kWh \text{kWh} kWh ): While the Joule is the coherent SI unit of energy, commercial electricity metering uses the kilowatt-hour ( kWh \text{kWh} kWh ) , commonly called a "Unit" of electricity: 1 kWh = 1 , 000 W × 3 , 600 s = 3 , 600 , 000 J = 3.6 × 10 6 J = 3.6 MJ 1\text{ kWh} = 1,000\text{ W} \times 3,600\text{ s} = 3,600,000\text{ J} = 3.6 \times 10^6\text{ J} = 3.6\text{ MJ} 1 kWh = 1 , 000 W × 3 , 600 s = 3 , 600 , 000 J = 3.6 × 1 0 6 J = 3.6 MJ
SI Prefixes and Scaling Multipliers
Metric prefixes are attached to base and derived units to represent very large or very small quantities. In electrotechnology, prefixes generally scale in steps of 10 3 10^3 1 0 3 (thousands):
Prefix Name Symbol Mathematical Factor Power of 10 Electrotechnical Practical Example
Giga G \text{G} G 1 , 000 , 000 , 000 1,000,000,000 1 , 000 , 000 , 000 10 9 10^9 1 0 9 National grid generation capacity: 2.5 GW 2.5\text{ GW} 2.5 GW
Mega M \text{M} M 1 , 000 , 000 1,000,000 1 , 000 , 000 10 6 10^6 1 0 6 Insulation resistance test minimum: ≥ 1.0 M Ω \ge 1.0\text{ M}\Omega ≥ 1.0 M Ω
Kilo k \text{k} k 1 , 000 1,000 1 , 000 10 3 10^3 1 0 3 Substation line voltage: 11 kV 11\text{ kV} 11 kV ; Fault level: 6 kA 6\text{ kA} 6 kA
(Unit) — 1 1 1 10 0 10^0 1 0 0 Supply voltage: 230 V 230\text{ V} 230 V ; Current: 16 A 16\text{ A} 16 A
Milli m \text{m} m 0.001 0.001 0.001 10 − 3 10^{-3} 1 0 − 3 RCD trip sensitivity: 30 mA 30\text{ mA} 30 mA ; Millivolts: m V / A / m mV/A/m mV / A / m
Micro μ \mu μ 0.000001 0.000001 0.000001 10 − 6 10^{-6} 1 0 − 6 Power factor correction capacitor: 47 μ F 47\ \mu\text{F} 47 μ F
Nano n \text{n} n 0.000000001 0.000000001 0.000000001 10 − 9 10^{-9} 1 0 − 9 High-frequency cable capacitance: 120 nF/km 120\text{ nF/km} 120 nF/km
Pico p \text{p} p 0.000000000001 0.000000000001 0.000000000001 10 − 12 10^{-12} 1 0 − 12 Radio frequency filter capacitor: 220 pF 220\text{ pF} 220 pF
Tip
When converting from a smaller prefix to a larger prefix (e.g., mA \text{mA} mA to A \text{A} A ), divide by the factor (or multiply by 10 − 3 10^{-3} 1 0 − 3 ). When converting from a larger prefix to a smaller prefix (e.g., k Ω \text{k}\Omega k Ω to Ω \Omega Ω ), multiply by the factor (or multiply by 10 3 10^3 1 0 3 ).
- Step-by-Step Unit Conversion Worked Examples
- Example 1: Current and Resistance Conversions
Convert a leakage current of 750 μ A 750\ \mu\text{A} 750 μ A to Amperes ( A \text{A} A ): 750 μ A = 750 × 10 − 6 A = 0.00075 A 750\ \mu\text{A} = 750 \times 10^{-6}\text{ A} = 0.00075\text{ A} 750 μ A = 750 × 1 0 − 6 A = 0.00075 A
Convert an insulation resistance reading of 200 M Ω 200\text{ M}\Omega 200 M Ω to Ohms ( Ω \Omega Ω ): 200 M Ω = 200 × 10 6 Ω = 200 , 000 , 000 Ω 200\text{ M}\Omega = 200 \times 10^6\ \Omega = 200,000,000\ \Omega 200 M Ω = 200 × 1 0 6 Ω = 200 , 000 , 000 Ω
Convert a prospective fault current of 4.5 kA 4.5\text{ kA} 4.5 kA to Amperes ( A \text{A} A ): 4.5 kA = 4.5 × 10 3 A = 4 , 500 A 4.5\text{ kA} = 4.5 \times 10^3\text{ A} = 4,500\text{ A} 4.5 kA = 4.5 × 1 0 3 A = 4 , 500 A
Example 2: Cable Cross-Sectional Area ( mm 2 \text{mm}^2 mm 2 to m 2 \text{m}^2 m 2 )
This conversion is a critical step in conductor resistance calculations using R = ρ L A R = \frac{\rho L}{A} R = A ρ L . Resistivity ρ \rho ρ is given in ohm-meters ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m ), and length L L L is in meters ( m \text{m} m ). Consequently, the cross-sectional area A A A must be expressed in square meters ( m 2 \text{m}^2 m 2 ) , not square millimeters ( mm 2 \text{mm}^2 mm 2 ).
Because 1 m = 1 , 000 mm = 10 3 mm 1\text{ m} = 1,000\text{ mm} = 10^3\text{ mm} 1 m = 1 , 000 mm = 1 0 3 mm : 1 m 2 = 1 , 000 mm × 1 , 000 mm = 1 , 000 , 000 mm 2 = 10 6 mm 2 1\text{ m}^2 = 1,000\text{ mm} \times 1,000\text{ mm} = 1,000,000\text{ mm}^2 = 10^6\text{ mm}^2 1 m 2 = 1 , 000 mm × 1 , 000 mm = 1 , 000 , 000 mm 2 = 1 0 6 mm 2 Therefore, to convert from mm 2 \text{mm}^2 mm 2 to m 2 \text{m}^2 m 2 , you must divide by 10 6 10^6 1 0 6 (multiply by 10 − 6 10^{-6} 1 0 − 6 ): 1 mm 2 = 1 × 10 − 6 m 2 1\text{ mm}^2 = 1 \times 10^{-6}\text{ m}^2 1 mm 2 = 1 × 1 0 − 6 m 2
For a 2.5 mm 2 2.5\text{ mm}^2 2.5 mm 2 conductor: A = 2.5 mm 2 = 2.5 × 10 − 6 m 2 A = 2.5\text{ mm}^2 = 2.5 \times 10^{-6}\text{ m}^2 A = 2.5 mm 2 = 2.5 × 1 0 − 6 m 2
For a 16 mm 2 16\text{ mm}^2 16 mm 2 sub-main conductor: A = 16 mm 2 = 16 × 10 − 6 m 2 = 1.6 × 10 − 5 m 2 A = 16\text{ mm}^2 = 16 \times 10^{-6}\text{ m}^2 = 1.6 \times 10^{-5}\text{ m}^2 A = 16 mm 2 = 16 × 1 0 − 6 m 2 = 1.6 × 1 0 − 5 m 2
Warning
Never multiply mm 2 \text{mm}^2 mm 2 by 10 − 3 10^{-3} 1 0 − 3 to convert to m 2 \text{m}^2 m 2 . A factor of 10 − 3 10^{-3} 1 0 − 3 converts linear millimeters to linear meters ( 1 mm = 10 − 3 m 1\text{ mm} = 10^{-3}\text{ m} 1 mm = 1 0 − 3 m ). Area requires squaring the linear factor: ( 10 − 3 ) 2 = 10 − 6 (10^{-3})^2 = 10^{-6} ( 1 0 − 3 ) 2 = 1 0 − 6 . Using 10 − 3 10^{-3} 1 0 − 3 will cause calculated cable resistance to be incorrect by a factor of 1 , 000 1,000 1 , 000 .
Example 3: Period to Frequency Conversion
An alternating waveform displays a single cycle periodic time of T = 20 ms T = 20\text{ ms} T = 20 ms . Calculate the supply frequency ( f f f ):
Convert periodic time to seconds: 20 ms = 20 × 10 − 3 s = 0.02 s 20\text{ ms} = 20 \times 10^{-3}\text{ s} = 0.02\text{ s} 20 ms = 20 × 1 0 − 3 s = 0.02 s .
Use the frequency formula f = 1 T f = \frac{1}{T} f = T 1 : f = 1 0.02 s = 50 Hz f = \frac{1}{0.02\text{ s}} = 50\text{ Hz} f = 0.02 s 1 = 50 Hz This confirms the standard UK mains electrical supply frequency.
Other SI Quantities in Unit 202
The Unit 202 range also covers the SI units for everyday physical quantities and for the a.c. quantities you meet later:
Quantity SI unit Symbol Notes
Area square metre m² Cable cross-sections are quoted in mm² ( 1 mm 2 = 10 − 6 m 2 1\text{ mm}^2 = 10^{-6}\text{ m}^2 1 mm 2 = 1 0 − 6 m 2 )
Volume cubic metre m³ 1 m 3 = 1,000 1\text{ m}^3 = 1{,}000 1 m 3 = 1 , 000 litres, so a 150-litre cylinder holds 0.15 m 3 0.15\text{ m}^3 0.15 m 3
Density kilogram per cubic metre kg/m³ Mass divided by volume; copper is about 8,900 kg/m³ and aluminium about 2,700 kg/m³
Velocity metre per second m/s Distance divided by time in a stated direction
Temperature kelvin K Practical work uses degrees Celsius; a temperature difference of 1 K equals 1°C, and 0°C is about 273 K
Impedance ohm Ω The total opposition to alternating current ( Z Z Z )
Inductive reactance ohm Ω X L = 2 π f L X_L = 2\pi f L X L = 2 π f L , where inductance L L L is in henrys (H)
Capacitive reactance ohm Ω X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C = 2 π f C 1 , where capacitance C C C is in farads (F)
- Power factor no unit none A ratio between 0 and 1 ( cos ϕ = P ÷ S \cos\phi = P \div S cos ϕ = P ÷ S )
- Instruments for Measuring Electrical Quantities
Unit 202 LO2 also asks you to identify the right instrument for each electrical quantity:
Quantity Instrument How it is connected
Current Ammeter (or clamp meter) In series with the load so that all the current passes through it; an ammeter has a very low resistance. A clamp meter measures current without breaking the circuit by clamping around a single conductor.
Voltage Voltmeter In parallel (across) the component or supply; a voltmeter has a very high resistance so it draws almost no current.
Resistance Ohmmeter (or a multimeter's resistance range; a low-resistance ohmmeter for continuity tests) Across the component with the circuit isolated and dead , because the meter drives its own test current from a battery.
Power Wattmeter Current coil in series and voltage coil in parallel with the load.
Energy Energy (kWh) meter Installed at the supply intake, recording the kilowatt-hours used.
A multimeter combines several of these functions, but remember the rule from Section 3.1: never use a multimeter to prove an installation dead.
Tip
Series measures current (ammeter); parallel measures voltage (voltmeter). Connecting an ammeter in parallel across a supply creates a near short circuit and can blow the meter's fuse or damage it.
Measurement Tolerances and Instrument Scales
When using test equipment (such as multifunction installation testers complying with BS EN 61557), readings must be interpreted with an understanding of measurement resolution and scale tolerance.
Analogue Meter Scales: Feature a physical pointer moving over a graduated arc. Reading analogue scales requires avoiding parallax error (viewing the needle from an angle). Quality analogue instruments incorporate an anti-parallax mirrored scale strip behind the needle; the user aligns their line of sight so the needle directly obscures its own reflection.
Digital Meter Resolution: Displays numerical values on an LCD/OLED screen. A meter reading 0.05 Ω 0.05\ \Omega 0.05 Ω on a 0.01 Ω 0.01\ \Omega 0.01 Ω resolution scale has an inherent quantization uncertainty of ± 1 \pm 1 ± 1 least significant digit.
Instrument Accuracy Tolerance: Typically expressed as ± ( % of reading + number of digits ) \pm (\%\text{ of reading} + \text{number of digits}) ± ( % of reading + number of digits ) . For instance, an instrument rated at ± ( 2 % + 3 digits ) \pm (2\% + 3\text{ digits}) ± ( 2% + 3 digits ) displaying 230.0 V 230.0\text{ V} 230.0 V has an allowable variance of ( 230 × 0.02 ) + 0.3 = 4.6 + 0.3 = ± 4.9 V (230 \times 0.02) + 0.3 = 4.6 + 0.3 = \pm 4.9\text{ V} ( 230 × 0.02 ) + 0.3 = 4.6 + 0.3 = ± 4.9 V , meaning the actual voltage lies between 225.1 V 225.1\text{ V} 225.1 V and 234.9 V 234.9\text{ V} 234.9 V .