Study guide
9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols
City & Guilds 2365 Level 2 Diploma in Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Qualification Overview
1.1 About the City & Guilds 2365 Level 2 Qualification 1.2 Study Strategy, Exam Technique & Resource Navigation
2 Health, Safety & Environmental Legislation, Risk Assessment & Permits
2.1 Statutory Framework & Health and Safety Law 2.2 Hazardous Substances, Incident Reporting & Welfare 2.3 Work Equipment, Manual Handling & PPE 2.4 Environmental Legislation, Pollution & Site Waste 2.5 Risk Assessments, Method Statements, Permits to Work & Safety Signs
3 Electrical Safety, Safe Isolation, Site Hazards & Emergencies
3.1 Safe Isolation Procedures & GS38 Compliance 3.2 Electrical Hazards & Electric Shock Physiology 3.3 Fire Safety, Site Supplies & Emergency Response 3.4 Accidents, First Aid, Emergency Procedures & Reporting
4 Working at Height & Access Equipment
4.1 Work at Height Regulations & Risk Management 4.2 Ladders, Stepladders & Podiums 4.3 Mobile Access Towers & Scaffolding Systems
5 Mathematical Principles, Units & Basic Mechanics
5.1 Mathematical Foundations & Transposition for Electricians 5.2 SI Units of Measurement in Electrotechnology 5.3 Basic Mechanics: Force, Work, Power & Mechanical Energy 5.4 Mass, Weight, Levers, Gears & Pulleys
6 Electron Theory, Resistance, Resistivity & DC Circuits
6.1 Resistance, Resistivity & Conductor Dimensions 6.2 Temperature Coefficient of Resistance 6.3 Ohm's Law, Power & Direct Current Calculations 6.4 Series, Parallel & Combination DC Circuits 6.5 Electron Theory, Conductors, Insulators & the Effects of Current
7 Magnetism, Electromagnetism & Transformers
7.1 Magnetic Fields, Flux & Solenoid Properties 7.2 Electromagnetic Induction & Motor/Generator Principles 7.3 Transformer Principles, Construction & Calculations
8 Alternating Current, Three-Phase Systems & Electronic Components
8.1 AC Waveform Generation & Key Values 8.2 AC Circuit Theory: Reactance, Impedance & Power Factor 8.3 Three-Phase Generation, Star-Delta & UK Distribution 8.4 Electronic Components in Electrical Systems
9 Industry Regulations, Technical Information & Drawings
9.1 Electrical Regulations, Standards & Part P 9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols 9.3 Technical Specifications, Schedules & Environmental Influences
10 Wiring Systems, Cables, Containment & Practical Installation
10.1 Thermoplastic, Armoured & Flexible Cables 10.2 Specialised Cables: MICC & Fire-Performance Cables 10.3 Conduit Systems: Steel & PVC 10.4 Trunking, Cable Tray & Cable Supports 10.5 Unit 204 Practical Skills: Tools, Preparation & Installing Wiring Systems
11 Final Circuits, Protective Devices, Alarm & Control Circuits
11.1 Lighting Circuits & Switching Arrangements 11.2 Power Circuits: Ring Final, Radial & Dedicated Circuits 11.3 Consumer Units, Distribution Boards & Protective Devices 11.4 Alarm, Emergency Lighting, Data & Control Circuits
12 Cable Selection & Structural Installation
12.1 Cable Current-Carrying Capacity & Correction Factors 12.2 Voltage Drop Principles & Calculations 12.3 Structural Integrity & Concealed Cable Routing
13 Supply Systems, Earthing, Shock Protection & Micro-Renewables
13.1 UK Electricity Supply Networks & Distribution 13.2 Earthing System Configurations: TN-S, TN-C-S (PME and PNB) & TT 13.3 Protective Conductors, Bonding & Earth Electrodes 13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs 13.5 Micro-Renewable Energy Technologies
14 Electrical Inspection & Dead Testing Sequence
14.1 Inspection Principles & Testing Safety to GS38 14.2 Continuity Testing: Protective Conductors & Ring Circuits 14.3 Insulation Resistance & Polarity Verification
15 Live Testing, Certification & Handover
15.1 Live Testing: Earth Loop Impedance, PFC & RCD Testing 15.2 Certification, Handover & Commissioning
16 Communicating within Building Services Engineering (Unit 210)
16.1 The Construction Team: Site Management, Trades & Site Visitors 16.2 Information Sources: Legislation, Guidance & Workplace Documents 16.3 Customer Information, Company Policies & Limits of Authority 16.4 Communicating Effectively: Methods, Accessibility & Conflict
9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols
Key Takeaways Explain This Topic AI
Electrotechnical drawings fulfill distinct operational roles: block diagrams portray high-level system functions, schematics detail circuit logic without physical scale, wiring diagrams specify terminal interconnections, and architectural layouts show scaled physical component locations.
Architectural installation plans are drawn to standard metric scales—predominantly 1:50 (1 cm = 0.5 m) and 1:100 (1 cm = 1.0 m)—allowing accurate containment routing and materials take-off.
Title blocks, revision tables, and alphanumeric column grids (letters and numbers) provide configuration control, ensuring electricians build from current, approved drawing revisions.
As-fitted (as-built) drawings record all on-site variations and actual cable routes at completion, and are normally included in the CDM Health and Safety File and the client's O&M manuals.
BS EN 60617 provides the harmonized graphical symbol standard used across the UK and Europe for accessories, lighting, distribution boards, and protective devices.
Last updated: October 2026
9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols
Technical drawings form the universal visual language of the electrotechnical industry. From initial design engineering and client tendering to site erection, containment routing, testing, and eventual maintenance, electricians must accurately interpret diverse drawing types. Misreading a drawing scale or confusing a graphical symbol can cause serious structural conflicts, material waste, or fatal circuit wiring errors.
Types of Electrical Drawings in Building Services
Electrotechnical projects rely on five fundamental categories of engineering drawings, each designed to communicate specific technical data:
Drawing Type Defining Characteristics & Contents Physical Scale Primary Functional Purpose
Block Diagram High-level functional overview using simple geometric blocks and single interconnecting lines. Omits terminal markings, component internal circuitry, and cable routing details. Not drawn to scale. Illustrates the overall architecture and sequence of power distribution, sub-distribution, fire alarm networks, or security interlocks.
Schematic (Circuit) Diagram Detailed diagram showing the electrical logic and operational sequence of a circuit. Uses standardized graphical symbols arranged logically by function from positive to negative (DC) or line to neutral (AC). Not drawn to scale; positions do not match physical room layout. Essential for understanding circuit operation, control sequence logic (e.g. motor DOL starters, two-way lighting), and systematic fault-finding.
Wiring (Interconnection) Diagram Practical diagram showing actual point-to-point wiring, cable cores, conductor color codes, internal link wires, and terminal designations (e.g. L1, L2, N, COM, 1, 2, E). Not to physical scale, but mirrors the internal arrangement of enclosures. Guides assembly, panel wiring, consumer unit internal connections, and accessory termination on site.
Architectural Layout Plan (Site Installation Drawing) Physical building floor plan drawn to an exact metric scale, overlaying civil features (walls, doors, windows) with electrotechnical symbols indicating equipment locations. Drawn to an exact metric scale (typically 1:50 or 1:100 ). Instructs electricians where to position sockets, switches, luminaires, consumer units, and containment runs during first-fix and second-fix.
As-Fitted (As-Built) Drawing Updated final layout drawing revised after physical installation to record all site variations, rerouted conduits, structural offsets, and junction box coordinates. Drawn to an exact metric scale. Normally included in the client's CDM 2015 Health and Safety File and in the Operation & Maintenance (O&M) manuals.
Note
Under BS 7671 Regulation 514.9.1 , diagrams, charts, or tables must be provided for every installation, indicating the type and composition of circuits, the method of protection against indirect contact, and the identification of protective devices. Providing accurate as-fitted drawings satisfies this mandatory regulation.
Drawing Scales, Scaling Rules & Layout Navigation
Architectural site installation plans are drafted using standardized metric reduction scales to fit large buildings onto manageable sheets (A0, A1, A2, or A3). ┌─────────────────────────────────┐
- │ Reading Standard Metric Scales │
- └────────────────┬────────────────┘
- │
- ┌─────────────────────────────┴─────────────────────────────┐
- ▼ ▼
- 1:50 Scale 1:100 Scale
- 1 cm on drawing = 50 cm on site • 1 cm on drawing = 100 cm on site
- 1 cm = 0.5 m • 1 cm = 1.0 m
- 20 mm on paper = 1.0 m physical • 10 mm on paper = 1.0 m physical
- Factor: Multiply paper mm by 50 • Factor: Multiply paper mm by 100
- Metric Scale Rules
Electricians must use a dedicated metric scale rule (triangular or oval cross-section). Standard scales include:
Scale 1:50: Commonly used for detailed room plans, domestic layouts, plant rooms, and risers. On this scale, 1 cm on paper = 50 cm (0.5 m) in reality . A wall measured as 80 mm on the drawing represents a physical distance of 80 mm × 50 = 4000 mm = 4.0 m.
Scale 1:100: Standard for large commercial floor plans, multi-story office blocks, and industrial units. On this scale, 1 cm on paper = 100 cm (1.0 m) in reality . A measurement of 65 mm represents 65 mm × 100 = 6500 mm = 6.5 m.
Scale 1:20 / 1:25: Used for complex assembly details, consumer unit enclosure internal layouts, and distribution board glanding plates.
Scale 1:500 / 1:1250: Site location plans showing external underground cable trenches, substation compounds, DNO intake cables, and external street lighting.
Dimension Lines and Grid References
Dimension Lines: Unbroken lines terminating in arrowheads, slashes, or dots, interrupted by numerical dimension values. Always prioritize stated numerical dimensions over scaled ruler measurements, as printing and paper expansion can distort paper scaling.
Alphanumeric Grid System: Modern drawings feature structural column grid lines labelled with letters along one axis (A, B, C...) and numbers along the other (1, 2, 3...). An operative can quickly locate a lighting distribution panel at grid intersection "C4" without searching through the entire floor plan.
Title Blocks & Revision Tables: Located in the bottom right-hand corner of the sheet. Displays the client name, project title, drawing number, scale, designer's initials, and critical revision history table (e.g. Rev A, Rev B, Rev C).
Warning
Always verify that you are working from the current, approved revision of a drawing before measuring cable lengths or cutting conduit. Installing work from a superseded revision (e.g. Rev A when Rev C has been issued) can result in demolished containment, rejected work, and unpaid rectification costs.
Standard Electrotechnical Graphical Symbols (BS EN 60617)
In the UK, electrotechnical graphical symbols comply with BS EN 60617 (IEC 60617), which superseded the legacy BS 3939 standard. Electricians must memorize these symbols for site plans and qualification exams.
1. Socket-Outlets
Symbol Description Graphical Representation Details Typical Application
Unswitched Socket-Outlet Semi-circle with a single straight radial line projecting outward. Clock points, behind refrigeration appliances.
Switched Socket-Outlet Semi-circle with a radial line carrying a single perpendicular flag or cross-bar. General domestic single switched socket.
Twin Switched Socket-Outlet Semi-circle with two radial lines, each carrying a perpendicular switch flag. Standard double 13A switched socket.
Switched Socket with Pilot Lamp Semi-circle with flagged radial line plus a filled small circle or adjacent pilot dot. Workshops, computer suites, remote appliance control.
Floor-Mounted Socket Standard socket symbol enclosed inside a rectangular outline. Open-plan office commercial floor boxes.
Weatherproof Socket Standard socket symbol with the letter W or IP56 adjacent. Outdoor garden and exterior patio supplies.
2. Lighting Switches & Controls
Symbol Description Graphical Representation Details Operation & Circuit Function
One-Way Single-Pole Switch Open circle with a single radial arm ending in an angled open flag ( —o/ ). Controls a lighting circuit from one single position.
Two-Way Switch Open circle with two radial arms projecting in opposite directions ( \o/ ). Controls lighting from two distinct positions (e.g. top and bottom of stairs).
Intermediate Switch Open circle with two intersecting diagonal crossing arms forming an "X" ( Xo ). Inserted between two two-way switches for control from 3 or more locations.
Pull-Cord Ceiling Switch Standard switch circle with an inverted small triangle or letter P attached. Bathrooms, shower rooms, and damp locations.
Double-Pole Switch with Neon Circle with two parallel switch bars and an integrated pilot indicator lamp. Immersion heaters, waste disposal units, water heaters.
3. Luminaires & Emergency Lighting
Symbol Description Graphical Representation Details Installation Role
Ceiling Lighting Point Simple "X" or cross ( + or × ) representing a generic luminaire position. Pendant lamp holder, baton holder, downlight.
Linear (Fluorescent / LED) Luminaire Elongated rectangle with an internal line or cross; length indicates lamp length. Commercial offices, modular suspended ceilings.
Wall-Mounted Luminaire (Bulkhead) Standard cross or semi-circle resting against a solid wall baseline ( T shape). Outdoor security lighting, stairwell bulkheads.
LED Luminaire Luminaire symbol annotated LED (or as shown in the drawing key). Downlights, LED panels and battens.
Self-Contained Emergency Luminaire Luminaire symbol with one quadrant or half filled solid black. Maintained or non-maintained escape route lighting.
4. Distribution, Metering & Isolation
Symbol Description Graphical Representation Details System Placement
Consumer Unit / Distribution Board Rectangular box divided diagonally, half filled solid black, or cross-hatched. Main electrical intake and sub-distribution positions.
Electricity Meter (kWh Meter) Rectangular box inscribed with the letters kWh or M . DNO intake position recording consumed energy.
Service Cutout (Head) Rectangular box containing a fuse symbol ( —[──]— ) at the cable head. DNO incoming termination point housing supply fuse.
Switch Disconnector (Isolator) Two open contact circles linked by an open knife line with a mechanical T-bar. Main isolation next to plant, HVAC, and motors.
Fuse A small rectangle drawn across the conductor line. Cut-outs, fused switches and fused connection units on circuit diagrams.
Circuit Breaker A switch symbol with a small cross on the moving contact. MCBs and RCBOs on single-line and circuit diagrams.
5. Auxiliary, Protective & Heating Accessories
Symbol Description Graphical Representation Details Installation Role
Cooker Control Unit Rectangle with internal switch and socket symbols, or labelled CCU . Kitchen cooker radial isolator with auxiliary socket.
Fused Connection Unit (FCU) Rectangle enclosing a fuse rectangle ( [──] ), with switch line if switched. Fixed appliances: boilers, hand dryers, towel rails.
Smoke Detector Circle containing the letter S or an internal optical chamber graphic. Automatic fire detection on escape routes.
Heat Detector Circle containing the letter H or a thermometer graphic. Kitchens and boiler rooms where smoke would false-alarm.
Room Thermostat Circle or square containing the Greek letter theta (θ) or letter T . Heating zone and underfloor heating control.
Bell Push & Sounder Circle with small dot (push); semi-circle with two striking lines (buzzer/bell). Doorbell entry circuits and local alarms.
Tip
On the City & Guilds 2365 exam, pay special attention to the difference between switch symbols: a one-way switch has a single arm, a two-way switch has two divergent arms, and an intermediate switch has crossing arms forming an "X". In socket symbols, a single radial line denotes an unswitched socket, whereas perpendicular flags denote switched outlets.