6.3 Ohm's Law, Power & Direct Current Calculations
City & Guilds 2365 Level 2 Diploma in Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Qualification Overview
1.1 About the City & Guilds 2365 Level 2 Qualification 1.2 Study Strategy, Exam Technique & Resource Navigation
2 Health, Safety & Environmental Legislation, Risk Assessment & Permits
2.1 Statutory Framework & Health and Safety Law 2.2 Hazardous Substances, Incident Reporting & Welfare 2.3 Work Equipment, Manual Handling & PPE 2.4 Environmental Legislation, Pollution & Site Waste 2.5 Risk Assessments, Method Statements, Permits to Work & Safety Signs
3 Electrical Safety, Safe Isolation, Site Hazards & Emergencies
3.1 Safe Isolation Procedures & GS38 Compliance 3.2 Electrical Hazards & Electric Shock Physiology 3.3 Fire Safety, Site Supplies & Emergency Response 3.4 Accidents, First Aid, Emergency Procedures & Reporting
4 Working at Height & Access Equipment
4.1 Work at Height Regulations & Risk Management 4.2 Ladders, Stepladders & Podiums 4.3 Mobile Access Towers & Scaffolding Systems
5 Mathematical Principles, Units & Basic Mechanics
5.1 Mathematical Foundations & Transposition for Electricians 5.2 SI Units of Measurement in Electrotechnology 5.3 Basic Mechanics: Force, Work, Power & Mechanical Energy 5.4 Mass, Weight, Levers, Gears & Pulleys
6 Electron Theory, Resistance, Resistivity & DC Circuits
6.1 Resistance, Resistivity & Conductor Dimensions 6.2 Temperature Coefficient of Resistance 6.3 Ohm's Law, Power & Direct Current Calculations 6.4 Series, Parallel & Combination DC Circuits 6.5 Electron Theory, Conductors, Insulators & the Effects of Current
7 Magnetism, Electromagnetism & Transformers
7.1 Magnetic Fields, Flux & Solenoid Properties 7.2 Electromagnetic Induction & Motor/Generator Principles 7.3 Transformer Principles, Construction & Calculations
8 Alternating Current, Three-Phase Systems & Electronic Components
8.1 AC Waveform Generation & Key Values 8.2 AC Circuit Theory: Reactance, Impedance & Power Factor 8.3 Three-Phase Generation, Star-Delta & UK Distribution 8.4 Electronic Components in Electrical Systems
9 Industry Regulations, Technical Information & Drawings
9.1 Electrical Regulations, Standards & Part P 9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols 9.3 Technical Specifications, Schedules & Environmental Influences
10 Wiring Systems, Cables, Containment & Practical Installation
10.1 Thermoplastic, Armoured & Flexible Cables 10.2 Specialised Cables: MICC & Fire-Performance Cables 10.3 Conduit Systems: Steel & PVC 10.4 Trunking, Cable Tray & Cable Supports 10.5 Unit 204 Practical Skills: Tools, Preparation & Installing Wiring Systems
11 Final Circuits, Protective Devices, Alarm & Control Circuits
11.1 Lighting Circuits & Switching Arrangements 11.2 Power Circuits: Ring Final, Radial & Dedicated Circuits 11.3 Consumer Units, Distribution Boards & Protective Devices 11.4 Alarm, Emergency Lighting, Data & Control Circuits
12 Cable Selection & Structural Installation
12.1 Cable Current-Carrying Capacity & Correction Factors 12.2 Voltage Drop Principles & Calculations 12.3 Structural Integrity & Concealed Cable Routing
13 Supply Systems, Earthing, Shock Protection & Micro-Renewables
13.1 UK Electricity Supply Networks & Distribution 13.2 Earthing System Configurations: TN-S, TN-C-S (PME and PNB) & TT 13.3 Protective Conductors, Bonding & Earth Electrodes 13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs 13.5 Micro-Renewable Energy Technologies
14 Electrical Inspection & Dead Testing Sequence
14.1 Inspection Principles & Testing Safety to GS38 14.2 Continuity Testing: Protective Conductors & Ring Circuits 14.3 Insulation Resistance & Polarity Verification
15 Live Testing, Certification & Handover
15.1 Live Testing: Earth Loop Impedance, PFC & RCD Testing 15.2 Certification, Handover & Commissioning
16 Communicating within Building Services Engineering (Unit 210)
16.1 The Construction Team: Site Management, Trades & Site Visitors 16.2 Information Sources: Legislation, Guidance & Workplace Documents 16.3 Customer Information, Company Policies & Limits of Authority 16.4 Communicating Effectively: Methods, Accessibility & Conflict
6.3 Ohm's Law, Power & Direct Current Calculations
Key Takeaways Explain This Topic AI
Ohm's Law states that the current flowing through a conductor is directly proportional to the potential difference across it, provided all physical conditions (notably temperature) remain constant ( V = I × R V = I \times R V = I × R ).
Non-ohmic devices—including tungsten filament lamps, semiconductor diodes, and discharge tubes—exhibit non-linear V-I curves because dynamic resistance varies with applied voltage or thermal rise.
Electrical power ( P P P in Watts) is the instantaneous rate of electrical energy conversion ( 1 W = 1 J/s 1\text{ W} = 1\text{ J/s} 1 W = 1 J/s ), calculated via P = V × I = I 2 R = V 2 R P = V \times I = I^2 R = \frac{V^2}{R} P = V × I = I 2 R = R V 2 .
Electrical energy is commercially metered in kilowatt-hours (kWh), where 1 kWh = 3.6 × 10 6 J 1\text{ kWh} = 3.6 \times 10^6\text{ J} 1 kWh = 3.6 × 1 0 6 J ( 3.6 MJ 3.6\text{ MJ} 3.6 MJ ), calculated via E = [ P ( W ) × t ( hours ) ] / 1000 E = [P(\text{W}) \times t(\text{hours})] / 1000 E = [ P ( W ) × t ( hours )] /1000 .
Utility cost calculations require multiplying total energy consumption in kilowatt-hours by the agreed unit tariff rate, requiring careful conversions between Watts, kilowatts, minutes, and hours.
Last updated: October 2026
Ohm's Law, Power & Direct Current Calculations
The fundamental relationship linking potential difference, electric current, and resistance was formulated in 1827 by Bavarian physicist Georg Simon Ohm. Known universally as Ohm's Law , it forms the mathematical cornerstone of electrical engineering science and installation practice.
Alongside Ohm's Law, understanding how electrical potential and current transfer energy over time— electrical power ( P P P ) and electrical energy ( E E E )—is vital for selecting cable sizes, rating protective switchgear, evaluating thermal dissipation, and calculating commercial electrical running costs.
Ohm's Law: Statement and Mathematical Formulations
Ohm's Law states that:
The electric current flowing through a conductor is directly proportional to the potential difference across its ends, provided that all physical conditions (particularly temperature) remain strictly constant.
Mathematically, this direct proportionality is expressed as:
V ∝ I ⟹ V I = Constant = R V \propto I \implies \frac{V}{I} = \text{Constant} = R V ∝ I ⟹ I V = Constant = R
Where:
- V V V = Potential difference (voltage) across the conductor in Volts ( V \text{V} V )
- I I I = Electric current flowing through the conductor in Amperes ( A \text{A} A )
- R R R = Electrical resistance of the conductor in Ohms ( Ω \Omega Ω )
- The Three Mathematical Formulations
Depending on which circuit variable is unknown, Ohm's Law is transposed into three forms:
V = I × R , I = V R , R = V I V = I \times R, \qquad I = \frac{V}{R}, \qquad R = \frac{V}{I} V = I × R , I = R V , R = I V
Calculating Voltage ( V = I R V = IR V = I R ) : If a current of 4.0 A 4.0\text{ A} 4.0 A passes through a circuit resistance of 25 Ω 25\ \Omega 25 Ω , the potential difference is V = 4.0 × 25 = 100 V V = 4.0 \times 25 = 100\text{ V} V = 4.0 × 25 = 100 V .
Calculating Current ( I = V R I = \frac{V}{R} I = R V ) : If a 230 V 230\text{ V} 230 V supply is connected across an element having a resistance of 46 Ω 46\ \Omega 46 Ω , the current is I = 230 46 = 5.0 A I = \frac{230}{46} = 5.0\text{ A} I = 46 230 = 5.0 A .
Calculating Resistance ( R = V I R = \frac{V}{I} R = I V ) : If a potential difference of 24 V 24\text{ V} 24 V causes a current of 1.5 A 1.5\text{ A} 1.5 A to flow, the resistance is R = 24 1.5 = 16 Ω R = \frac{24}{1.5} = 16\ \Omega R = 1.5 24 = 16 Ω .
Note
A graph plotting potential difference ( V V V ) against current ( I I I ) for an ohmic conductor produces a straight line passing through the origin ( 0 , 0 ) (0,0) ( 0 , 0 ) . The constant slope (gradient) of this V V V - I I I line equals the resistance R R R of the conductor.
Ohmic versus Non-Ohmic Components
Ohm's Law holds true only when physical conditions—most critically conductor temperature—remain constant. Components that comply with this linear relationship are termed ohmic conductors , whereas components whose resistance changes under varying electrical conditions are termed non-ohmic .
1. Ohmic Conductors
Standard Carbon or Metal Film Resistors : When operated within their rated power dissipation limits so that temperature rise is negligible, these components exhibit a constant resistance regardless of applied voltage or current direction.
Metallic Conductor Wires at Constant Temperature : Test circuits maintained in oil baths or subjected to brief, low-current measurement pulses exhibit linear V V V - I I I behaviour.
2. Non-Ohmic Devices
Tungsten Filament Lamps : A filament lamp is a prime example of a non-ohmic device. When unenergized at room temperature ( 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ), the cold resistance of the fine tungsten wire is very low (typically less than 10 % 10\% 10% of its rated operating resistance). When switched on, a large initial inrush current surge flows. Within milliseconds, resistive heating elevates the filament temperature to over 2 , 500 ∘ C 2,500^\circ\text{C} 2 , 50 0 ∘ C . Because tungsten has a strong Positive Temperature Coefficient (PTC), its resistance increases by a factor of 10 to 12. As a result, the V V V - I I I curve flattens out at higher voltages—current increases much more slowly than voltage.
Semiconductor Diodes : A p-n junction diode conducts current predominantly in one direction. In forward bias, virtually zero current flows until the applied voltage overcomes the internal barrier potential (approximately 0.6 V 0.6\text{ V} 0.6 V to 0.7 V 0.7\text{ V} 0.7 V for silicon). Once this threshold is exceeded, current increases exponentially with negligible additional voltage rise. In reverse bias, only microamperes of leakage current flow until catastrophic reverse breakdown occurs. The V V V - I I I curve is completely non-linear.
Gas Discharge Lamps (Fluorescent, Sodium, Metal Halide) : Once an electric arc is struck through the ionized gas, the dynamic resistance of the lamp drops sharply. In fact, discharge lamps display negative incremental resistance —as current increases, more gas atoms ionize, lowering the resistance further. Without a series inductive choke (ballast) or electronic control gear to limit current, the lamp would draw destructive overcurrent and self-destruct instantly.
Electrical Power ( P P P ) in Direct Current Circuits
Electrical power ( P P P ) is defined as the rate at which electrical energy is converted into other forms of energy (such as heat, light, mechanical motion, or chemical change). The SI unit of electrical power is the Watt (symbol W \text{W} W ), named after Scottish engineer James Watt. One Watt equals one Joule of energy converted per second ( 1 W = 1 J/s 1\text{ W} = 1\text{ J/s} 1 W = 1 J/s ).
Derivation of the Three Fundamental Power Formulas
The Primary Power Formula: P = V × I P = V \times I P = V × I By definition, electric potential difference ( V V V ) represents work done ( W W W ) per unit charge ( Q Q Q ), so V = W Q ⟹ W = V × Q V = \frac{W}{Q} \implies W = V \times Q V = Q W ⟹ W = V × Q . Current ( I I I ) represents the rate of charge flow, so I = Q t ⟹ Q = I × t I = \frac{Q}{t} \implies Q = I \times t I = t Q ⟹ Q = I × t . Substituting this into work done yields W = V × I × t W = V \times I \times t W = V × I × t . Power is rate of work done ( P = W t P = \frac{W}{t} P = t W ): P = V × I × t t = V × I P = \frac{V \times I \times t}{t} = V \times I P = t V × I × t = V × I Power (Watts) = Potential Difference (Volts) × \times × Current (Amperes).
The Joule Heating Formula: P = I 2 R P = I^2 R P = I 2 R Substituting Ohm's Law ( V = I × R V = I \times R V = I × R ) into P = V × I P = V \times I P = V × I : P = ( I × R ) × I = I 2 R P = (I \times R) \times I = I^2 R P = ( I × R ) × I = I 2 R This equation reveals that power dissipated as heat in a conductor is proportional to the square of the current . Doubling the current flowing through a distribution cable quadruples the heat dissipation ( 2 2 = 4 2^2 = 4 2 2 = 4 ). This formula is essential for calculating cable thermal ratings, volt drop energy losses, and protective device clearing capacities.
The Constant-Resistance Voltage Formula: P = V 2 R P = \frac{V^2}{R} P = R V 2 Substituting Ohm's Law transposed for current ( I = V R I = \frac{V}{R} I = R V ) into P = V × I P = V \times I P = V × I : P = V × ( V R ) = V 2 R P = V \times \left(\frac{V}{R}\right) = \frac{V^2}{R} P = V × ( R V ) = R V 2 This equation is used to calculate the power output of fixed-resistance electrical appliances (such as immersion heaters, panel heaters, and shower elements) when subjected to variations in supply voltage.
The Ohm's Law and Power Summary Circle
The combined relationships yield 12 fundamental equations connecting V V V , I I I , R R R , and P P P :
Unknown Quantity In terms of V V V and I I I In terms of I I I and R R R In terms of V V V and R R R In terms of P P P and R R R In terms of P P P and I I I In terms of P P P and V V V
Voltage ( V V V ) — V = I R V = I R V = I R — V = P R V = \sqrt{P R} V = PR V = P I V = \frac{P}{I} V = I P —
Current ( I I I ) — — I = V R I = \frac{V}{R} I = R V I = P R I = \sqrt{\frac{P}{R}} I = R P — I = P V I = \frac{P}{V} I = V P
Resistance ( R R R ) R = V I R = \frac{V}{I} R = I V — — — R = P I 2 R = \frac{P}{I^2} R = I 2 P R = V 2 P R = \frac{V^2}{P} R = P V 2
Power ( P P P ) P = V I P = V I P = V I P = I 2 R P = I^2 R P = I 2 R P = V 2 R P = \frac{V^2}{R} P = R V 2 — — —
Electrical Energy: Joules vs Kilowatt-Hours (kWh)
Electrical energy ( E E E or W W W ) represents the total quantity of work performed by an electrical system over a period of time:
- Energy = Power × Time \text{Energy} = \text{Power} \times \text{Time} Energy = Power × Time
- 1. Base SI Unit: The Joule ( J \text{J} J )
In physical science, energy is measured in Joules (symbol J \text{J} J ), where one Joule is the energy transferred by a power of one Watt operating for one second ( 1 J = 1 W ⋅ s 1\text{ J} = 1\text{ W}\cdot\text{s} 1 J = 1 W ⋅ s ):
E ( Joules ) = P ( Watts ) × t ( seconds ) E(\text{Joules}) = P(\text{Watts}) \times t(\text{seconds}) E ( Joules ) = P ( Watts ) × t ( seconds )
While the Joule is the base SI unit, it is impractical for commercial electricity metering because it is too small. For example, a standard domestic kettle consuming 3 , 000 W 3,000\text{ W} 3 , 000 W for just 5 minutes converts: E = 3 , 000 W × ( 5 × 60 s ) = 3 , 000 × 300 = 900 , 000 Joules E = 3,000\text{ W} \times (5 \times 60\text{ s}) = 3,000 \times 300 = 900,000\text{ Joules} E = 3 , 000 W × ( 5 × 60 s ) = 3 , 000 × 300 = 900 , 000 Joules Recording residential or industrial consumption in Joules would require multi-digit numbers running into hundreds of millions.
2. Commercial Metering Unit: The Kilowatt-Hour ( kWh \text{kWh} kWh )
To provide a practical commercial unit, utility providers meter electricity in kilowatt-hours (symbol kWh \text{kWh} kWh ), historically designated the "Board of Trade Unit" or simply the "Unit" of electricity.
One kilowatt-hour is defined as the total electrical energy converted by a device consuming one kilowatt ( 1 , 000 W 1,000\text{ W} 1 , 000 W ) continuously for one hour ( 3 , 600 seconds 3,600\text{ seconds} 3 , 600 seconds ):
1 kWh = 1 , 000 W × 3 , 600 s = 3 , 600 , 000 Joules = 3.6 × 10 6 J = 3.6 MJ 1\text{ kWh} = 1,000\text{ W} \times 3,600\text{ s} = 3,600,000\text{ Joules} = 3.6 \times 10^6\text{ J} = 3.6\text{ MJ} 1 kWh = 1 , 000 W × 3 , 600 s = 3 , 600 , 000 Joules = 3.6 × 1 0 6 J = 3.6 MJ
To calculate commercial energy consumption in kWh \text{kWh} kWh :
E ( kWh ) = P ( Watts ) × t ( hours ) 1 , 000 = P ( kW ) × t ( hours ) E(\text{kWh}) = \frac{P(\text{Watts}) \times t(\text{hours})}{1,000} = P(\text{kW}) \times t(\text{hours}) E ( kWh ) = 1 , 000 P ( Watts ) × t ( hours ) = P ( kW ) × t ( hours )
3. Utility Tariff Calculations
The financial cost of operating electrical installations is calculated directly from energy consumed in kWh \text{kWh} kWh :
Total Operating Cost = Energy Consumed (kWh) × Tariff Rate (pence or £per kWh) \text{Total Operating Cost} = \text{Energy Consumed (kWh)} \times \text{Tariff Rate (pence or \pounds per kWh)} Total Operating Cost = Energy Consumed (kWh) × Tariff Rate (pence or £per kWh)
- Multi-Step Worked Calculation Examples
- Worked Example 1: Domestic Immersion Heater Analysis
Problem: A domestic hot water immersion heater is connected to a 230 V 230\text{ V} 230 V single-phase AC supply and is rated at 3.0 kW 3.0\text{ kW} 3.0 kW . Calculate:
The continuous load current drawn by the heater.
The electrical resistance of the heating element.
The total electrical energy consumed in Joules and in kWh \text{kWh} kWh if the heater runs continuously for 4 hours and 30 minutes 4\text{ hours and } 30\text{ minutes} 4 hours and 30 minutes .
The financial running cost of this heating cycle at an electricity tariff of 26 p per kWh 26\text{p per kWh} 26 p per kWh .
Solution:
Load Current ( I I I ) : I = P V = 3 , 000 W 230 V ≈ 13.04 A I = \frac{P}{V} = \frac{3,000\text{ W}}{230\text{ V}} \approx 13.04\text{ A} I = V P = 230 V 3 , 000 W ≈ 13.04 A
Element Resistance ( R R R ) : R = V 2 P = 230 2 3 , 000 = 52 , 900 3 , 000 ≈ 17.63 Ω R = \frac{V^2}{P} = \frac{230^2}{3,000} = \frac{52,900}{3,000} \approx 17.63\ \Omega R = P V 2 = 3 , 000 23 0 2 = 3 , 000 52 , 900 ≈ 17.63 Ω (Verification via Ohm's Law: R = V I = 230 13.04 = 17.64 Ω R = \frac{V}{I} = \frac{230}{13.04} = 17.64\ \Omega R = I V = 13.04 230 = 17.64 Ω .)
Energy Consumed ( E E E ) :
In kWh \text{kWh} kWh : Time t = 4.5 hours t = 4.5\text{ hours} t = 4.5 hours . E ( kWh ) = 3.0 kW × 4.5 h = 13.5 kWh E(\text{kWh}) = 3.0\text{ kW} \times 4.5\text{ h} = 13.5\text{ kWh} E ( kWh ) = 3.0 kW × 4.5 h = 13.5 kWh
In Joules: Time t = 4.5 × 3 , 600 s = 16 , 200 s t = 4.5 \times 3,600\text{ s} = 16,200\text{ s} t = 4.5 × 3 , 600 s = 16 , 200 s . E ( Joules ) = 3 , 000 W × 16 , 200 s = 48 , 600 , 000 J = 48.6 MJ E(\text{Joules}) = 3,000\text{ W} \times 16,200\text{ s} = 48,600,000\text{ J} = 48.6\text{ MJ} E ( Joules ) = 3 , 000 W × 16 , 200 s = 48 , 600 , 000 J = 48.6 MJ (Check: 13.5 kWh × 3.6 MJ/kWh = 48.6 MJ 13.5\text{ kWh} \times 3.6\text{ MJ/kWh} = 48.6\text{ MJ} 13.5 kWh × 3.6 MJ/kWh = 48.6 MJ .)
Running Cost : Cost = 13.5 kWh × £ 0.26 = £ 3.51 \text{Cost} = 13.5\text{ kWh} \times \pounds 0.26 = \pounds 3.51 Cost = 13.5 kWh × £0.26 = £3.51
Worked Example 2: Voltage Sag Impact on an Electric Shower
Problem: An instantaneous electric shower has an element rated at 9.6 kW 9.6\text{ kW} 9.6 kW when supplied at a nominal voltage of 240 V 240\text{ V} 240 V . During peak winter evening demand, network loading causes the supply voltage at the shower terminals to drop by 10 % 10\% 10% to 216 V 216\text{ V} 216 V . Assuming the heating element resistance remains constant, calculate:
The resistance of the shower element.
The actual heat power output at 216 V 216\text{ V} 216 V .
The percentage reduction in heating performance.
Solution:
Element Resistance ( R R R ) : R = V 2 P = 240 2 9 , 600 = 57 , 600 9 , 600 = 6.0 Ω R = \frac{V^2}{P} = \frac{240^2}{9,600} = \frac{57,600}{9,600} = 6.0\ \Omega R = P V 2 = 9 , 600 24 0 2 = 9 , 600 57 , 600 = 6.0 Ω
Actual Power at Reduced Voltage ( 216 V 216\text{ V} 216 V ) : P actual = V 2 R = 216 2 6.0 = 46 , 656 6.0 = 7 , 776 W = 7.776 kW P_{\text{actual}} = \frac{V^2}{R} = \frac{216^2}{6.0} = \frac{46,656}{6.0} = 7,776\text{ W} = 7.776\text{ kW} P actual = R V 2 = 6.0 21 6 2 = 6.0 46 , 656 = 7 , 776 W = 7.776 kW
Percentage Reduction in Heat Output : Reduction = 9.600 − 7.776 9.600 × 100 % = 1.824 9.600 × 100 % = 19.0 % \text{Reduction} = \frac{9.600 - 7.776}{9.600} \times 100\% = \frac{1.824}{9.600} \times 100\% = 19.0\% Reduction = 9.600 9.600 − 7.776 × 100% = 9.600 1.824 × 100% = 19.0%
Warning
Notice that a 10 % 10\% 10% reduction in terminal voltage produces a 19 % 19\% 19% reduction in heating power output. Because power depends on the square of the voltage ( P ∝ V 2 P \propto V^2 P ∝ V 2 ), small voltage drops across distribution cables cause substantial losses in heating and illumination performance.
Worked Example 3: Commercial LED Lighting Installation Costing
Problem: An industrial warehouse installation contains 80 commercial LED luminaire fittings. Each fitting consumes 60 W 60\text{ W} 60 W . The lighting installation operates 12 hours per day 12\text{ hours per day} 12 hours per day , 5 days per week 5\text{ days per week} 5 days per week , for 50 weeks per year 50\text{ weeks per year} 50 weeks per year . Calculate:
The total connected lighting load in kilowatts.
The annual energy consumption in kWh \text{kWh} kWh .
The annual electricity running cost at a commercial tariff of 22 p per kWh 22\text{p per kWh} 22 p per kWh .
Solution:
Total Connected Load ( P P P ) : P = 80 × 60 W = 4 , 800 W = 4.8 kW P = 80 \times 60\text{ W} = 4,800\text{ W} = 4.8\text{ kW} P = 80 × 60 W = 4 , 800 W = 4.8 kW
Annual Operating Hours ( t t t ) : t = 12 hours/day × 5 days/week × 50 weeks/year = 3 , 000 hours/year t = 12\text{ hours/day} \times 5\text{ days/week} \times 50\text{ weeks/year} = 3,000\text{ hours/year} t = 12 hours/day × 5 days/week × 50 weeks/year = 3 , 000 hours/year
Annual Energy Consumption ( E E E ) : E = 4.8 kW × 3 , 000 hours = 14 , 400 kWh E = 4.8\text{ kW} \times 3,000\text{ hours} = 14,400\text{ kWh} E = 4.8 kW × 3 , 000 hours = 14 , 400 kWh
Annual Running Cost : Cost = 14 , 400 kWh × £ 0.22 = £ 3 , 168.00 \text{Cost} = 14,400\text{ kWh} \times \pounds 0.22 = \pounds 3,168.00 Cost = 14 , 400 kWh × £0.22 = £3 , 168.00