Study guide

6.1 Resistance, Resistivity & Conductor Dimensions

City & Guilds 2365 Level 2 Diploma in Electrical Installations Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Qualification Overview

1.1 About the City & Guilds 2365 Level 2 Qualification 1.2 Study Strategy, Exam Technique & Resource Navigation

2 Health, Safety & Environmental Legislation, Risk Assessment & Permits

2.1 Statutory Framework & Health and Safety Law 2.2 Hazardous Substances, Incident Reporting & Welfare 2.3 Work Equipment, Manual Handling & PPE 2.4 Environmental Legislation, Pollution & Site Waste 2.5 Risk Assessments, Method Statements, Permits to Work & Safety Signs

3 Electrical Safety, Safe Isolation, Site Hazards & Emergencies

3.1 Safe Isolation Procedures & GS38 Compliance 3.2 Electrical Hazards & Electric Shock Physiology 3.3 Fire Safety, Site Supplies & Emergency Response 3.4 Accidents, First Aid, Emergency Procedures & Reporting

4 Working at Height & Access Equipment

4.1 Work at Height Regulations & Risk Management 4.2 Ladders, Stepladders & Podiums 4.3 Mobile Access Towers & Scaffolding Systems

5 Mathematical Principles, Units & Basic Mechanics

5.1 Mathematical Foundations & Transposition for Electricians 5.2 SI Units of Measurement in Electrotechnology 5.3 Basic Mechanics: Force, Work, Power & Mechanical Energy 5.4 Mass, Weight, Levers, Gears & Pulleys

6 Electron Theory, Resistance, Resistivity & DC Circuits

6.1 Resistance, Resistivity & Conductor Dimensions 6.2 Temperature Coefficient of Resistance 6.3 Ohm's Law, Power & Direct Current Calculations 6.4 Series, Parallel & Combination DC Circuits 6.5 Electron Theory, Conductors, Insulators & the Effects of Current

7 Magnetism, Electromagnetism & Transformers

7.1 Magnetic Fields, Flux & Solenoid Properties 7.2 Electromagnetic Induction & Motor/Generator Principles 7.3 Transformer Principles, Construction & Calculations

8 Alternating Current, Three-Phase Systems & Electronic Components

8.1 AC Waveform Generation & Key Values 8.2 AC Circuit Theory: Reactance, Impedance & Power Factor 8.3 Three-Phase Generation, Star-Delta & UK Distribution 8.4 Electronic Components in Electrical Systems

9 Industry Regulations, Technical Information & Drawings

9.1 Electrical Regulations, Standards & Part P 9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols 9.3 Technical Specifications, Schedules & Environmental Influences

10 Wiring Systems, Cables, Containment & Practical Installation

10.1 Thermoplastic, Armoured & Flexible Cables 10.2 Specialised Cables: MICC & Fire-Performance Cables 10.3 Conduit Systems: Steel & PVC 10.4 Trunking, Cable Tray & Cable Supports 10.5 Unit 204 Practical Skills: Tools, Preparation & Installing Wiring Systems

11 Final Circuits, Protective Devices, Alarm & Control Circuits

11.1 Lighting Circuits & Switching Arrangements 11.2 Power Circuits: Ring Final, Radial & Dedicated Circuits 11.3 Consumer Units, Distribution Boards & Protective Devices 11.4 Alarm, Emergency Lighting, Data & Control Circuits

12 Cable Selection & Structural Installation

12.1 Cable Current-Carrying Capacity & Correction Factors 12.2 Voltage Drop Principles & Calculations 12.3 Structural Integrity & Concealed Cable Routing

13 Supply Systems, Earthing, Shock Protection & Micro-Renewables

13.1 UK Electricity Supply Networks & Distribution 13.2 Earthing System Configurations: TN-S, TN-C-S (PME and PNB) & TT 13.3 Protective Conductors, Bonding & Earth Electrodes 13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs 13.5 Micro-Renewable Energy Technologies

14 Electrical Inspection & Dead Testing Sequence

14.1 Inspection Principles & Testing Safety to GS38 14.2 Continuity Testing: Protective Conductors & Ring Circuits 14.3 Insulation Resistance & Polarity Verification

15 Live Testing, Certification & Handover

15.1 Live Testing: Earth Loop Impedance, PFC & RCD Testing 15.2 Certification, Handover & Commissioning

16 Communicating within Building Services Engineering (Unit 210)

16.1 The Construction Team: Site Management, Trades & Site Visitors 16.2 Information Sources: Legislation, Guidance & Workplace Documents 16.3 Customer Information, Company Policies & Limits of Authority 16.4 Communicating Effectively: Methods, Accessibility & Conflict

6.1 Resistance, Resistivity & Conductor Dimensions

Key Takeaways Explain This Topic AI

Electrical resistance ( R R R ), measured in Ohms ( Ω \Omega Ω ), represents the opposition encountered by electric charge drifting through a material under an applied electric field.

Four physical factors dictate conductor resistance: conductor length (directly proportional), cross-sectional area (inversely proportional), material resistivity (in Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m ), and operating temperature.

The fundamental conductor resistance formula is R = ( ρ × L ) / A R = (\rho \times L) / A R = ( ρ × L ) / A ; cross-sectional area in mm 2 \text{mm}^2 mm 2 must always be converted to base SI square metres ( m 2 \text{m}^2 m 2 ) by multiplying by 10 − 6 10^{-6} 1 0 − 6 .

Standard annealed copper conductor resistivity at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C is taken as 1.72 × 10 − 8 Ω ⋅ m 1.72 \times 10^{-8}\ \Omega\cdot\text{m} 1.72 × 1 0 − 8 Ω ⋅ m ( 0.0172 μ Ω ⋅ m 0.0172\ \mu\Omega\cdot\text{m} 0.0172 μ Ω ⋅ m ), whereas aluminium exhibits higher resistivity at 2.82 × 10 − 8 Ω ⋅ m 2.82 \times 10^{-8}\ \Omega\cdot\text{m} 2.82 × 1 0 − 8 Ω ⋅ m .

Geometric scaling exhibits non-linear relationships: doubling conductor length doubles resistance ( 2 × 2\times 2 × ), whereas doubling conductor diameter quadruples cross-sectional area and reduces resistance to one-quarter ( 0.25 × 0.25\times 0.25 × ).

Last updated: October 2026

Resistance, Resistivity & Conductor Dimensions

In electrotechnical engineering, electrical resistance ( R R R ) is defined as the property of a material or circuit element that opposes the flow of electric charge (current). When a potential difference (voltage) is established across a conductive path, an electric field accelerates mobile charge carriers—free electrons—through the material. As these electrons drift through the crystalline lattice of the conductor, they repeatedly collide with vibrating positive metal ions.

Each collision transfers kinetic energy from the drifting electrons to the lattice ions, increasing thermal kinetic energy and causing the conductor to warm up. This energy transformation, known as Joule heating ( I 2 R I^2R I 2 R ), represents the physical manifestation of electrical resistance. Resistance is measured in the SI unit Ohm (symbol Ω \Omega Ω ), named in honour of German physicist Georg Simon Ohm. By definition, a conductor exhibits a resistance of one Ohm ( 1 Ω 1\ \Omega 1 Ω ) when a constant potential difference of one volt ( 1 V 1\text{ V} 1 V ) across its terminals produces a current of one ampere ( 1 A 1\text{ A} 1 A ).

Note

Resistance is not an intrinsic property of a chemical element alone; rather, it is an extrinsic property of a specific component, determined by both its physical dimensions (length and cross-sectional area) and its internal atomic material characteristics.

The Four Factors Determining Conductor Resistance

The electrical resistance of any conductor depends on four distinct physical variables:

Length ( L L L ) : Resistance is directly proportional to conductor length ( R ∝ L R \propto L R ∝ L ). As an electric charge travels through a longer path, it encounters a proportionally greater number of lattice ions, leading to more frequent collisions and higher cumulative opposition. Doubling the length doubles the electrical resistance.

Cross-Sectional Area ( A A A ) : Resistance is inversely proportional to cross-sectional area ( R ∝ 1 A R \propto \frac{1}{A} R ∝ A 1 ​ ). A larger cross-sectional area provides a broader conductive pathway with more parallel routes through which mobile electrons can drift simultaneously. Doubling the cross-sectional area halves the electrical resistance.

Material Type (Resistivity, ρ \rho ρ ) : Different elements and alloys possess differing atomic structures, valence electron densities, and lattice configurations. The intrinsic property quantifying how strongly a given material opposes charge movement is called its resistivity (symbolized by the Greek letter rho, ρ \rho ρ ).

Temperature ( θ \theta θ ) : The kinetic energy and vibration amplitude of the conductor's lattice ions vary directly with temperature. In metallic conductors, rising temperature causes the lattice ions to vibrate more violently across larger amplitudes, significantly increasing collision cross-sections and raising electrical resistance.

Material Resistivity ( ρ \rho ρ )

Resistivity is the intrinsic electrical resistance of a uniform sample of a material having unit length and unit cross-sectional area—specifically, a solid cube measuring one metre on each side ( 1 m × 1 m × 1 m 1\text{ m} \times 1\text{ m} \times 1\text{ m} 1 m × 1 m × 1 m ). Resistivity is expressed in Ohm-metres ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m ), or in micro-Ohm metres ( μ Ω ⋅ m \mu\Omega\cdot\text{m} μ Ω ⋅ m ).

ρ = R × A L = Ω × m 2 m = Ω ⋅ m \rho = \frac{R \times A}{L} = \frac{\Omega \times \text{m}^2}{\text{m}} = \Omega\cdot\text{m} ρ = L R × A ​ = m Ω × m 2 ​ = Ω ⋅ m

Materials with very low resistivity are excellent electrical conductors, whereas materials with very high resistivity serve as insulators. Below are standard resistivity values for common engineering materials evaluated at a reference ambient temperature of 20 ∘ C 20^\circ\text{C} 2 0 ∘ C :

Material Typical Resistivity at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m ) Electrical Classification & Practical Application

Silver 1.59 × 10 − 8 1.59 \times 10^{-8} 1.59 × 1 0 − 8 ( 0.0159 μ Ω ⋅ m 0.0159\ \mu\Omega\cdot\text{m} 0.0159 μ Ω ⋅ m ) Highest electrical conductivity of all metals; used for switchgear contacts and high-rupture-capacity (HRC) fuse elements.

Copper (Annealed) 1.72 × 10 − 8 1.72 \times 10^{-8} 1.72 × 1 0 − 8 ( 0.0172 μ Ω ⋅ m 0.0172\ \mu\Omega\cdot\text{m} 0.0172 μ Ω ⋅ m ) Industry standard for building wiring, flexible cords, busbars, and electric motor windings due to superior conductivity and ductility.

Gold 2.44 × 10 − 8 2.44 \times 10^{-8} 2.44 × 1 0 − 8 ( 0.0244 μ Ω ⋅ m 0.0244\ \mu\Omega\cdot\text{m} 0.0244 μ Ω ⋅ m ) Excellent conductivity with total resistance to surface oxidation; widely applied in low-voltage data terminals and edge connectors.

Aluminium 2.82 × 10 − 8 2.82 \times 10^{-8} 2.82 × 1 0 − 8 ( 0.0282 μ Ω ⋅ m 0.0282\ \mu\Omega\cdot\text{m} 0.0282 μ Ω ⋅ m ) Lightweight conductor used in overhead transmission lines (ACSR) and large commercial subterranean distribution cables.

Tungsten 5.60 × 10 − 8 5.60 \times 10^{-8} 5.60 × 1 0 − 8 ( 0.0560 μ Ω ⋅ m 0.0560\ \mu\Omega\cdot\text{m} 0.0560 μ Ω ⋅ m ) High melting point ( 3 , 422 ∘ C 3,422^\circ\text{C} 3 , 42 2 ∘ C ); used in incandescent lamp filaments and specialised arc contacts.

Constantan (Eureka) 49.0 × 10 − 8 49.0 \times 10^{-8} 49.0 × 1 0 − 8 ( 0.490 μ Ω ⋅ m 0.490\ \mu\Omega\cdot\text{m} 0.490 μ Ω ⋅ m ) Copper-nickel alloy (55% Cu, 45% Ni) with near-zero temperature coefficient; used for precision laboratory standard resistors and instrument shunts.

Nichrome 100.0 × 10 − 8 100.0 \times 10^{-8} 100.0 × 1 0 − 8 ( 1.00 μ Ω ⋅ m 1.00\ \mu\Omega\cdot\text{m} 1.00 μ Ω ⋅ m ) Nickel-chromium alloy exhibiting high resistivity and oxidation resistance at high heat; standard element for domestic heaters and showers.

Carbon (Graphite) 3 , 500 × 10 − 8 3,500 \times 10^{-8} 3 , 500 × 1 0 − 8 ( 35.0 μ Ω ⋅ m 35.0\ \mu\Omega\cdot\text{m} 35.0 μ Ω ⋅ m ) Non-metal conductor with negative temperature coefficient; used for DC motor commutator brushes and arc electrodes.

Copper versus Aluminium in Installation Practice

Comparing the resistivities of copper and aluminium reveals an important engineering relationship:

ρ Al ρ Cu = 2.82 × 10 − 8 1.72 × 10 − 8 ≈ 1.64 \frac{\rho_{\text{Al}}}{\rho_{\text{Cu}}} = \frac{2.82 \times 10^{-8}}{1.72 \times 10^{-8}} \approx 1.64 ρ Cu ​ ρ Al ​ ​ = 1.72 × 1 0 − 8 2.82 × 1 0 − 8 ​ ≈ 1.64

Because aluminium's resistivity is approximately 1.64 times that of copper, an aluminium cable requires roughly a 64% larger cross-sectional area than a copper cable of identical length to achieve the same electrical resistance. However, aluminium's mass density is only one-third that of copper. As a result, for equivalent current-carrying capacity, an aluminium conductor weighs roughly half as much as a copper conductor, making aluminium the economical choice for long-span high-voltage overhead grid lines.

The Conductor Resistance Formula: R = ρ L A R = \frac{\rho L}{A} R = A ρ L ​

Combining the physical relationships yields the fundamental resistance formula:

R = ρ × L A R = \frac{\rho \times L}{A} R = A ρ × L ​

Where:

  • R R R = Conductor resistance in Ohms ( Ω \Omega Ω )
  • ρ \rho ρ = Material resistivity in Ohm-metres ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m )
  • L L L = Conductor length in metres ( m \text{m} m )
  • A A A = Conductor cross-sectional area in square metres ( m 2 \text{m}^2 m 2 )
  • Formula Transpositions

Depending on the unknown quantity required in examination questions, the formula transposes as follows:

ρ = R × A L , L = R × A ρ , A = ρ × L R \rho = \frac{R \times A}{L}, \qquad L = \frac{R \times A}{\rho}, \qquad A = \frac{\rho \times L}{R} ρ = L R × A ​ , L = ρ R × A ​ , A = R ρ × L ​

Warning

In electrical contracting, cable cross-sectional area is universally quoted in square millimetres ( mm 2 \text{mm}^2 mm 2 ), such as 1.5 mm 2 1.5\text{ mm}^2 1.5 mm 2 or 2.5 mm 2 2.5\text{ mm}^2 2.5 mm 2 . However, the resistivity formula strictly requires cross-sectional area in base SI square metres ( m 2 \text{m}^2 m 2 ). Failing to execute this metric conversion is the single most common cause of calculation failure on examination papers.

Converting Square Millimetres ( mm 2 \text{mm}^2 mm 2 ) to Square Metres ( m 2 \text{m}^2 m 2 )

Because one linear metre contains 1 , 000 1,000 1 , 000 millimetres ( 10 3 mm 10^3\text{ mm} 1 0 3 mm ), one square metre consists of a square 1 , 000 mm 1,000\text{ mm} 1 , 000 mm wide by 1 , 000 mm 1,000\text{ mm} 1 , 000 mm high:

1 m 2 = 1 , 000 mm × 1 , 000 mm = 1 , 000 , 000 mm 2 = 10 6 mm 2 1\text{ m}^2 = 1,000\text{ mm} \times 1,000\text{ mm} = 1,000,000\text{ mm}^2 = 10^6\text{ mm}^2 1 m 2 = 1 , 000 mm × 1 , 000 mm = 1 , 000 , 000 mm 2 = 1 0 6 mm 2

To convert an area from mm 2 \text{mm}^2 mm 2 to m 2 \text{m}^2 m 2 , you must divide by 1 , 000 , 000 1,000,000 1 , 000 , 000 or multiply by 10 − 6 10^{-6} 1 0 − 6 :

A ( m 2 ) = A ( mm 2 ) × 10 − 6 A(\text{m}^2) = A(\text{mm}^2) \times 10^{-6} A ( m 2 ) = A ( mm 2 ) × 1 0 − 6

Standard UK metric cable sizes convert to base units as follows:

  • 1.0 mm 2 = 1.0 × 10 − 6 m 2 1.0\text{ mm}^2 = 1.0 \times 10^{-6}\text{ m}^2 1.0 mm 2 = 1.0 × 1 0 − 6 m 2
  • 1.5 mm 2 = 1.5 × 10 − 6 m 2 1.5\text{ mm}^2 = 1.5 \times 10^{-6}\text{ m}^2 1.5 mm 2 = 1.5 × 1 0 − 6 m 2
  • 2.5 mm 2 = 2.5 × 10 − 6 m 2 2.5\text{ mm}^2 = 2.5 \times 10^{-6}\text{ m}^2 2.5 mm 2 = 2.5 × 1 0 − 6 m 2
  • 4.0 mm 2 = 4.0 × 10 − 6 m 2 4.0\text{ mm}^2 = 4.0 \times 10^{-6}\text{ m}^2 4.0 mm 2 = 4.0 × 1 0 − 6 m 2
  • 6.0 mm 2 = 6.0 × 10 − 6 m 2 6.0\text{ mm}^2 = 6.0 \times 10^{-6}\text{ m}^2 6.0 mm 2 = 6.0 × 1 0 − 6 m 2

10.0 mm 2 = 10.0 × 10 − 6 m 2 = 1.0 × 10 − 5 m 2 10.0\text{ mm}^2 = 10.0 \times 10^{-6}\text{ m}^2 = 1.0 \times 10^{-5}\text{ m}^2 10.0 mm 2 = 10.0 × 1 0 − 6 m 2 = 1.0 × 1 0 − 5 m 2

16.0 mm 2 = 16.0 × 10 − 6 m 2 = 1.6 × 10 − 5 m 2 16.0\text{ mm}^2 = 16.0 \times 10^{-6}\text{ m}^2 = 1.6 \times 10^{-5}\text{ m}^2 16.0 mm 2 = 16.0 × 1 0 − 6 m 2 = 1.6 × 1 0 − 5 m 2

25.0 mm 2 = 25.0 × 10 − 6 m 2 = 2.5 × 10 − 5 m 2 25.0\text{ mm}^2 = 25.0 \times 10^{-6}\text{ m}^2 = 2.5 \times 10^{-5}\text{ m}^2 25.0 mm 2 = 25.0 × 1 0 − 6 m 2 = 2.5 × 1 0 − 5 m 2

Cross-Sectional Area of Circular Conductor Cores

Where an examination problem specifies the diameter ( d d d ) or radius ( r r r ) of a solid circular conductor core rather than stating the area directly, apply standard circular geometry:

A = π r 2 = π d 2 4 A = \pi r^2 = \frac{\pi d^2}{4} A = π r 2 = 4 π d 2 ​

If measuring a conductor core with a digital micrometer reveals a diameter of 1.78 mm 1.78\text{ mm} 1.78 mm : r = 1.78 2 = 0.89 mm r = \frac{1.78}{2} = 0.89\text{ mm} r = 2 1.78 ​ = 0.89 mm A = π × ( 0.89 ) 2 ≈ 2.488 mm 2 ≈ 2.5 mm 2 A = \pi \times (0.89)^2 \approx 2.488\text{ mm}^2 \approx 2.5\text{ mm}^2 A = π × ( 0.89 ) 2 ≈ 2.488 mm 2 ≈ 2.5 mm 2

  • Step-by-Step Worked Calculations
  • Worked Example 1: Resistance of a 2.5 mm 2 2.5\text{ mm}^2 2.5 mm 2 Radial Run

Problem: Calculate the resistance of a single copper conductor 50 metres 50\text{ metres} 50 metres long having a cross-sectional area of 2.5 mm 2 2.5\text{ mm}^2 2.5 mm 2 at an ambient temperature of 20 ∘ C 20^\circ\text{C} 2 0 ∘ C . Take copper resistivity as ρ = 1.72 × 10 − 8 Ω ⋅ m \rho = 1.72 \times 10^{-8}\ \Omega\cdot\text{m} ρ = 1.72 × 1 0 − 8 Ω ⋅ m .

Solution:

State given values in base SI units:

  • ρ = 1.72 × 10 − 8 Ω ⋅ m \rho = 1.72 \times 10^{-8}\ \Omega\cdot\text{m} ρ = 1.72 × 1 0 − 8 Ω ⋅ m
  • L = 50 m L = 50\text{ m} L = 50 m

A = 2.5 mm 2 = 2.5 × 10 − 6 m 2 A = 2.5\text{ mm}^2 = 2.5 \times 10^{-6}\text{ m}^2 A = 2.5 mm 2 = 2.5 × 1 0 − 6 m 2

Apply the resistivity equation: R = ρ L A = 1.72 × 10 − 8 × 50 2.5 × 10 − 6 R = \frac{\rho L}{A} = \frac{1.72 \times 10^{-8} \times 50}{2.5 \times 10^{-6}} R = A ρ L ​ = 2.5 × 1 0 − 6 1.72 × 1 0 − 8 × 50 ​

Calculate the numerator: 1.72 × 10 − 8 × 50 = 8.60 × 10 − 7 1.72 \times 10^{-8} \times 50 = 8.60 \times 10^{-7} 1.72 × 1 0 − 8 × 50 = 8.60 × 1 0 − 7

Divide by the cross-sectional area: R = 8.60 × 10 − 7 2.5 × 10 − 6 = 0.344 Ω R = \frac{8.60 \times 10^{-7}}{2.5 \times 10^{-6}} = 0.344\ \Omega R = 2.5 × 1 0 − 6 8.60 × 1 0 − 7 ​ = 0.344 Ω

Tip

In practical circuit verification, a single radial circuit consists of both an outgoing line conductor and a returning neutral or protective conductor. If evaluating the total loop resistance ( R 1 + R 2 R_1 + R_2 R 1 ​ + R 2 ​ ) of a 50 m 50\text{ m} 50 m run where both line and return are 2.5 mm 2 2.5\text{ mm}^2 2.5 mm 2 , the total conductor length is 100 m 100\text{ m} 100 m , yielding 0.344 × 2 = 0.688 Ω 0.344 \times 2 = 0.688\ \Omega 0.344 × 2 = 0.688 Ω .

Worked Example 2: Resistance of an Aluminium Sub-Main

Problem: A commercial sub-main feeder uses a 120 metre 120\text{ metre} 120 metre single-core aluminium conductor with a cross-sectional area of 16 mm 2 16\text{ mm}^2 16 mm 2 . Calculate its resistance at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C given aluminium resistivity is 2.82 × 10 − 8 Ω ⋅ m 2.82 \times 10^{-8}\ \Omega\cdot\text{m} 2.82 × 1 0 − 8 Ω ⋅ m .

Solution:

Identify quantities:

  • ρ = 2.82 × 10 − 8 Ω ⋅ m \rho = 2.82 \times 10^{-8}\ \Omega\cdot\text{m} ρ = 2.82 × 1 0 − 8 Ω ⋅ m
  • L = 120 m L = 120\text{ m} L = 120 m
  • A = 16 mm 2 = 16 × 10 − 6 m 2 A = 16\text{ mm}^2 = 16 \times 10^{-6}\text{ m}^2 A = 16 mm 2 = 16 × 1 0 − 6 m 2

Substitute into formula: R = 2.82 × 10 − 8 × 120 16 × 10 − 6 = 3.384 × 10 − 6 16 × 10 − 6 = 0.2115 Ω R = \frac{2.82 \times 10^{-8} \times 120}{16 \times 10^{-6}} = \frac{3.384 \times 10^{-6}}{16 \times 10^{-6}} = 0.2115\ \Omega R = 16 × 1 0 − 6 2.82 × 1 0 − 8 × 120 ​ = 16 × 1 0 − 6 3.384 × 1 0 − 6 ​ = 0.2115 Ω

Worked Example 3: Transposition to Determine Required Area

Problem: A lighting sub-circuit requires an 80 metre 80\text{ metre} 80 metre run of single-core copper conductor. Design criteria dictate that the conductor resistance must not exceed 0.55 Ω 0.55\ \Omega 0.55 Ω at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C . Calculate the minimum required cross-sectional area in mm 2 \text{mm}^2 mm 2 and select the appropriate standard metric size.

Solution:

Transpose the resistance formula for area A A A : A = ρ L R A = \frac{\rho L}{R} A = R ρ L ​

Substitute values ( ρ = 1.72 × 10 − 8 Ω ⋅ m \rho = 1.72 \times 10^{-8}\ \Omega\cdot\text{m} ρ = 1.72 × 1 0 − 8 Ω ⋅ m ): A = 1.72 × 10 − 8 × 80 0.55 = 1.376 × 10 − 6 0.55 ≈ 2.502 × 10 − 6 m 2 A = \frac{1.72 \times 10^{-8} \times 80}{0.55} = \frac{1.376 \times 10^{-6}}{0.55} \approx 2.502 \times 10^{-6}\text{ m}^2 A = 0.55 1.72 × 1 0 − 8 × 80 ​ = 0.55 1.376 × 1 0 − 6 ​ ≈ 2.502 × 1 0 − 6 m 2

Convert back to mm 2 \text{mm}^2 mm 2 by multiplying by 10 6 10^6 1 0 6 : A = 2.502 × 10 − 6 × 10 6 = 2.502 mm 2 A = 2.502 \times 10^{-6} \times 10^6 = 2.502\text{ mm}^2 A = 2.502 × 1 0 − 6 × 1 0 6 = 2.502 mm 2

Select the standard cable size: A 2.5 mm 2 2.5\text{ mm}^2 2.5 mm 2 conductor would yield a resistance slightly over the 0.55 Ω 0.55\ \Omega 0.55 Ω limit ( R = 0.5504 Ω R = 0.5504\ \Omega R = 0.5504 Ω ). Therefore, to guarantee compliance, the next standard size of 4.0 mm 2 4.0\text{ mm}^2 4.0 mm 2 must be selected.

Geometric Proportionality and Scaling Effects

Examiners regularly test candidate understanding of proportional relationships without providing full numerical values:

Doubling Conductor Length ( L → 2 L L \rightarrow 2L L → 2 L ) : R new = ρ ( 2 L ) A = 2 × ( ρ L A ) = 2 R R_{\text{new}} = \frac{\rho (2L)}{A} = 2 \times \left(\frac{\rho L}{A}\right) = 2R R new ​ = A ρ ( 2 L ) ​ = 2 × ( A ρ L ​ ) = 2 R Doubling length doubles resistance ( 2 × 2\times 2 × ).

Halving Conductor Length ( L → 0.5 L L \rightarrow 0.5L L → 0.5 L ) : Halving length halves resistance ( 0.5 × 0.5\times 0.5 × ).

Doubling Conductor Cross-Sectional Area ( A → 2 A A \rightarrow 2A A → 2 A ) : R new = ρ L 2 A = 1 2 × ( ρ L A ) = 0.5 R R_{\text{new}} = \frac{\rho L}{2A} = \frac{1}{2} \times \left(\frac{\rho L}{A}\right) = 0.5R R new ​ = 2 A ρ L ​ = 2 1 ​ × ( A ρ L ​ ) = 0.5 R Doubling area halves resistance ( 0.5 × 0.5\times 0.5 × ).

Doubling Conductor Diameter ( d → 2 d d \rightarrow 2d d → 2 d ) :

Because area depends on the square of the diameter ( A = π d 2 4 A = \frac{\pi d^2}{4} A = 4 π d 2 ​ ): A new = π ( 2 d ) 2 4 = π × 4 d 2 4 = 4 A A_{\text{new}} = \frac{\pi (2d)^2}{4} = \frac{\pi \times 4d^2}{4} = 4A A new ​ = 4 π ( 2 d ) 2 ​ = 4 π × 4 d 2 ​ = 4 A Substituting 4 A 4A 4 A into the resistance equation: R new = ρ L 4 A = 1 4 × ( ρ L A ) = 0.25 R R_{\text{new}} = \frac{\rho L}{4A} = \frac{1}{4} \times \left(\frac{\rho L}{A}\right) = 0.25R R new ​ = 4 A ρ L ​ = 4 1 ​ × ( A ρ L ​ ) = 0.25 R Doubling diameter quadruples area and reduces resistance to one-quarter ( 0.25 × 0.25\times 0.25 × ).

Doubling Length AND Doubling Diameter : R new = ρ ( 2 L ) 4 A = 2 4 R = 0.5 R R_{\text{new}} = \frac{\rho (2L)}{4A} = \frac{2}{4} R = 0.5R R new ​ = 4 A ρ ( 2 L ) ​ = 4 2 ​ R = 0.5 R Doubling both length and diameter halves the original resistance.

Loading diagram... Factors Dictating Conductor Resistance and Geometric Scaling Relationships